Honda STREAM 2003 · Service Manual

DTC Troubleshooting: 14

DTC Troubleshooting: 14

DTC 14:  A Short in the Evaporator Temperature Sensor Circuit


1.Remove the evaporator temperature sensor.

2.Test the evaporator temperature sensor.

Is the resistance within the specifications shown on the graph?


YES - Go to 3.


NO - Replace the  evaporator temperature sensor.n


3.Disconnect heater control panel connector B (20P).

4.Check for continuity between the No. 7 terminal of heater control panel connector B (20P) and body ground.

 

S7A1E00K73100081140FAAD01Wire side of female terminalsHEATER CONTROL PANEL CONNECTOR B (20P)BRN

Is there continuity?


YES - Repair short to body ground in the wire between the heater control panel and the  evaporator temperature sensor.n


NO - Substitute a known-good heater control panel, and recheck. If the symptom/indication goes away, replace the original heater control panel.n