DTC B1411/11 Room Temperature Sensor Circuit |
| DTC No. | DTC Detecting Condition | Trouble Area |
| B1411/11 | Open or short in room temperature sensor circuit |
|

| 1.READ VALUE OF INTELLIGENT TESTER |
Connect the intelligent tester to the DLC3.
Turn the ignition switch ON and push the intelligent tester main switch on.
Select the item below in the DATA LIST, and read the display on the intelligent tester.
| Item | Measurement Item/Display (Range) | Normal Condition | Diagnostic Note |
| ROOM TEMP | Room temperature sensor / min.: -6.5°C (20.3°F) max.: 57.25°C (135.05°F) | Actual cabin temperature is displayed | Open in the circuit: -6.5°C (20.3°F) Short in the circuit: 57.25°C (135.05°F) |
| Result | Proceed to |
| NG | A |
| OK (Checking from the PROBLEM SYMPTOMS TABLE) | B |
| OK (Checking from the DTC) | C |
|
| ||||
|
| ||||
| A | |
| 2.INSPECT AIR CONDITIONING AMPLIFIER ASSEMBLY |
![]() |
Remove the A/C amplifier assembly with the connectors still connected.
Measure the voltage according to the value(s) in the table below.
| Tester connection (Symbols) | Condition | Specified condition |
| A11-21 (TR) - A11-26 (SG-5) | Ignition switch ON at 25°C (77°F) | 1.8 to 2.2 V |
| A11-21 (TR) - A11-26 (SG-5) | Ignition switch ON at 40°C (104°F) | 1.3 to 1.7 V |
| Result | Proceed to |
| NG | A |
| OK (Checking from the PROBLEM SYMPTOMS TABLE) | B |
| OK (Checking from the DTC) | C |
|
| ||||
|
| ||||
| A | |
| 3.INSPECT A/C ROOM TEMPERATURE SENSOR |
![]() |
Remove the A/C room temperature sensor.
Disconnect the connector from the A/C room temperature sensor.
Measure the resistance according to the value(s) in the table below.

| Tester connection (Symbols) | Condition | Specified condition |
| A33-1 (THR) - A33-2 (GND) | 10°C (50°F) | 3.00 to 3.73 kΩ |
| A33-1 (THR) - A33-2 (GND) | 15°C (59°F) | 2.45 to 2.88 kΩ |
| A33-1 (THR) - A33-2 (GND) | 20°C (68°F) | 1.95 to 2.30 kΩ |
| A33-1 (THR) - A33-2 (GND) | 25°C (77°F) | 1.60 to 1.80 kΩ |
| A33-1 (THR) - A33-2 (GND) | 30°C (86°F) | 1.28 to 1.47 kΩ |
| A33-1 (THR) - A33-2 (GND) | 35°C (95°F) | 1.00 to 1.22 kΩ |
| A33-1 (THR) - A33-2 (GND) | 40°C (104°F) | 0.80 to 1.00 kΩ |
| A33-1 (THR) - A33-2 (GND) | 45°C (113°F) | 0.65 to 0.85 kΩ |
| A33-1 (THR) - A33-2 (GND) | 50°C (122°F) | 0.50 to 0.70 kΩ |
| A33-1 (THR) - A33-2 (GND) | 55°C (131°F) | 0.44 to 0.60 kΩ |
| A33-1 (THR) - A33-2 (GND) | 60°C (140°F) | 0.36 to 0.50 kΩ |
|
| ||||
| OK | |
| 4.CHECK HARNESS AND CONNECTOR (A/C ROOM TEMPERATURE SENSOR - A/C AMPLIFIER ASSEMBLY) |
![]() |
Disconnect the connector from the A/C amplifier assembly.
Measure the resistance according to the value(s) in the table below.
| Tester connection (Symbols) | Condition | Specified condition |
| A11-21 (TR) - A33-1 (THR) | Always | Below 1 Ω |
| A11-26 (SG-5) - A33-2 (GND) | Always | Below 1 Ω |
| A11-21 (TR) - Body ground | Always | 10 kΩ or higher |
| A11-26 (SG-5) - Body ground | Always | 10 kΩ or higher |
|
| ||||
| OK | ||
| ||