REFRIGERANT > ON-VEHICLE INSPECTION

for Preparation Click here



1. INSPECT REFRIGERANT VOLUME


  1. Check the sight glass on the air conditioning tube & accessory assembly.


    E111326E01


    1. Prepare the vehicle according the chart below.
      Item
      Condition
      Vehicle door
      Fully open
      Temperature setting
      MAX COLD
      Blower speed
      HI
      A/C
      ON

    2. Compare the sight glass to the following chart.

      Item
      Symptom
      Amount of refrigerant
      Corrective Actions
      1
      Bubbles exist
      Insufficient*
      1. Check for gas leakage and repair if necessary
      2. Add refrigerant until bubbles disappear
      2
      No bubbles exist (DTC 76 is output)
      Empty, insufficient or excessive
      Refer to 3 and 4
      3
      No temperature difference between compressor inlet and outlet
      Empty or nearly empty
      1. Check for gas leakage and repair if necessary
      2. Evacuate the AC system and recharge the proper amount of refrigerant
      4
      Considerable temperature difference between compressor inlet and outlet.
      Proper or excessive
      Refer to 5 and 6
      5
      Immediately after air conditioning is turned off, refrigerant remains clear
      Excessive
      1. Discharge refrigerant
      2. Evacuate the AC system and recharge the proper amount of refrigerant
      6
      Immediately after air conditioning is turned off, refrigerant foams and then becomes clear
      Proper
      -
      *: Bubbles in the sight glass with the vehicle's interior above 35°C (95°F) can be considered normal if cooling is sufficient.



2. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET

HINT:
This is a method where a manifold gauge set is used to help locate the problem.



  1. Read the manifold gauge pressure when these conditions are established.
    Test conditions:

    1. Temperature at the air inlet with the switch set at RECIRC is 30 to 35°C (86 to 95°F)
    2. Engine is running at 1,500 rpm
    3. Blower speed control switch is at "HI"
    4. Temperature control dial is at "COOL"
    5. A/C switch is ON
    6. Doors are fully open
    7. Ignition switch in a position that enables the AC compressor to run.



      E050573
    1. Normally functioning refrigeration system

      Gauge reading:
      Low pressure side:
      0.15 to 0.25 MPa (1.5 to 2.5 kgf/cm2, 21.3 to 35.5 psi)
      High pressure side:
      1.37 to 1.57 MPa (14 to 16 kgf/cm2, 199.1 to 227.5 psi)



    2. Moisture is present in refrigeration system.


      I022117E09


      Symptom
      Probable cause
      Diagnosis
      Corrective Actions
      During operation, pressure on low pressure side cycles between normal and vacuum
      Moisture in AC system will freeze at the expansion valve orifice, causing the refrigeration cycle to temporarily stop
      After the system stop, and warms up again, the ice will melt and normal operation will be temporarily restored
      1. Dryer in oversaturated state
      2. Moisture in refrigeration system freezes at expansion valve orifice and blocks circulation of refrigerant
      1. Replace condenser
      2. Remove moisture in system by repeatedly evacuating air
      3. Supply a proper amount of new refrigerant



    3. Insufficient cooling


      I022118E01


      Symptom
      Probable cause
      Diagnosis
      Corrective Actions
      1. Pressure is low on both low and high pressure sides
      2. Bubbles are seen through sight glass continuously
      3. Insufficient cooling performance
      Gas leakage from the refrigeration system
      1. Insufficient refrigerant
      2. Refrigerant leaking
      1. Check for gas leakage and repair if necessary
      2. Supply a proper amount of new refrigerant
      3. If the gauge indicates a pressure of close to 0, then it will be necessary to evacuate the system after repairing the leak



    4. Poor circulation of refrigerant


      I022119E01


      Symptom
      Probable cause
      Diagnosis
      Corrective Actions
      1. Pressure is low on both low and high pressure sides
      2. Frost exists on pipe from condenser to unit
      Refrigerant flow is obstructed by dirt inside the pipes of the condenser core
      Receiver is clogged
      Replace condenser



    5. Refrigerant does not circulate.


      I022120E01


      Symptom
      Probable cause
      Diagnosis
      Corrective Actions
      1. Vacuum is indicated on low pressure side and very low pressure is indicated on high pressure side
      2. Frost or condensation is seen on piping on both sides of receiver/drier or expansion valve
      1. Refrigerant flow is obstructed by moisture or dirt in refrigeration system
      2. Refrigerant flow is disrupted by gas leaking internally through the expansion valve
      Refrigerant does not circulate
      1. Check the expansion valve
      2. Replace expansion valve
      3. Replace condenser
      4. Evaporate air and supply a proper amount of new refrigerant
      5. For internal gas leak at expansion valve, replace expansion valve



    6. Refrigerant is overcharged or cooling effectiveness of condenser is insufficient.


      I022121E01


      Symptom
      Probable cause
      Diagnosis
      Corrective Actions
      1. Pressure is too high on both low and high pressure sides
      2. No air bubbles are seen through sight glass even when engine rpm lowers
      1. Unable to develop sufficient performance due to excessive use of refrigeration system
      2. Cooling effectiveness of condenser is insufficient
      1. Excessive refrigerant in cycle → excessive refrigerant was recharged
      2. Condenser cooling effectiveness is insufficient → condenser fins are clogged at cooling fan
      1. Clean condenser
      2. Check the operation of the condenser cooling fan
      3. If 1 and 2 are normal state, check the amount of refrigerant and supply proper amount of refrigerant



    7. Air is present in refrigeration system.


      I022122E06


      Symptom
      Probable cause
      Diagnosis
      Corrective Actions
      1. Pressure is too high on both low and high pressure sides
      2. The low pressure piping is too hot to touch
      3. Bubbles can be seen through sight glass
      Air in system
      1. Air present in refrigeration system
      2. Insufficient vacuum purging
      1. Check compressor oil to see if it is dirty or insufficient
      2. Evacuate the system and recharge it with new or purified refrigerant



    8. Expansion valve malfunction


      I022123E05


      Symptom
      Probable cause
      Diagnosis
      Corrective Actions
      1. Pressure is too high on both low and high pressure sides
      2. Frost or a large amount of condensation on piping on low pressure side
      Expansion valve may be sticking
      1. Excessive refrigerant in low pressure piping
      2. Expansion valve opened too wide
      Check expansion valve



    9. Insufficient compressor compression


      I022124E05


      Symptom
      Probable cause
      Diagnosis
      Corrective Actions
      1. Pressure is too high both on low and high pressure sides
      2. Pressure is too low on high pressure side
      Internal leak in compressor
      1. Low compression
      2. Leak from a damaged valve, or parts may be broken
      Replace compressor
      Gauge readings (Reference)


      I030081E10