Nissan GT-R (R35) · Service Manual VENTILATION, HEATER & AIR CONDITIONER

REFRIGERATION SYSTEM

Inspection


 
 1.CHECK BLOWER MOTOR OPERATION
 
 2.CHECK COMPRESSOR OPERATION
 
 3.CHECK REFRIGERANT CYCLE PRESSURE

Performance Chart

 
 TEST CONDITION

Testing must be performed as per the following:
Vehicle condition
Indoors or in the shade (in a well‐ventilated place)
Doors
Closed
Door windows
Open
Hood
Open
Temperature control switch or dial
Maximum cold
Mode switch
(Ventilation) set
Intake switch
(Recirculation) set
Fan (blower) speed
Maximum speed set
Engine speed
Idle speed
Operate the air conditioning system for 10 minutes before taking measurements.

 
 TEST READING

Recirculating‐to‐discharge Air Temperature Table
Inside air (Recirculating air) at blower assembly inlet
Discharge air temperature at center ventilator
°C (°F)
Relative humidity
%
Air temperature
°C (°F)
50 ‐ 60
20 (68)
6.0 – 8.0 (43 – 46)
25 (77)
8.4 – 10.9 (47 – 52)
30 (86)
14.5 – 17.5 (58 – 64)
60 ‐ 70
20 (68)
7.1 – 9.1 (45 – 48)
25 (77)
10.9 – 13.4 (52 – 57)
30 (86)
17.5 – 20.5 (64 – 69)


Ambient Air Temperature‐to‐operating Pressure Table
Ambient air
High‐pressure (Discharge side)
kPa (kg/cm2, psi)
Low‐pressure (Suction side)
kPa (kg/cm2, psi)
Relative humidity
%
Air temperature
°C (°F)
50 ‐ 70
25 (77)
1,204 – 1,471
(12.3 – 15.0, 174.6 – 213.3)
171 – 209
(1.7 – 2.1, 24.8 – 30.3)
30 (86)
1,300 – 1,590
(13.3 – 16.2, 188.5 – 230.6)
196 – 240
(2.0 – 2.4, 28.4 – 34.8)
35 (95)
1,500 – 1,820
(15.3 – 18.6, 217.5 – 263.9)
229 – 280
(2.3 – 2.9, 33.2 – 40.6)
40 (104)
1,870 – 2,285
(19.1 – 23.3, 271.2 – 331.3)
292 – 357
(3.0 – 3.6, 42.3 – 51.8)

Refrigerant Leakages


Perform a visual inspection of all refrigeration parts, fittings, hoses and components for signs of A/C lubricant leakage, damage and corrosion. A/C lubricant leakage may indicate an area of refrigerant leakage. Allow extra inspection time in these areas when using either an electrical leak detector or fluorescent dye leak detector (SST: J‐42220).
Confirm the leakage with an electrical leak detector if dye is observed. It is possible a prior leakage was repaired and not properly cleaned.
If a leakage is found but continue checking for additional leakages at all system components and connections when searching for leakages.
Move the probe along the suspected leakage area at 1 to 2 inches per second and no further than 1/4 inch from the component when searching for refrigerant leakages using an electrical leak detector.
NOTE:
Moving the electrical leak detector probe slower and closer to the suspected leakage area improves the chances of finding a leakage.