Home › HEATER & AIR CONDITIONING SYSTEM › AIR CONDITIONING › COMPRESSOR AND MAGNETIC CLUTCH (for 2UZ-FE)

COMPRESSOR AND MAGNETIC CLUTCH (for 2UZ-FE) > INSTALLATION

for Preparation Click here



1. INSTALL COMPRESSOR AND MAGNETIC CLUTCH


    I033928
  1. Install the compressor and magnetic clutch and stay, compressor with the 3 bolts.

    Torque:
    46 N*m{ 469 kgf*cm , 34 ft.*lbf }

  1. Install the nut.

    Torque:
    24 N*m{ 245 kgf*cm , 18 ft.*lbf }

  1. Connect the connector.



2. INSTALL SUCTION HOSE SUB-ASSEMBLY
  1. Remove the attached vinyl tape from the hose.

  1. Sufficiently apply compressor oil to a new O-ring and fitting surface of the compressor and magnetic clutch.

    Compressor oil:
    ND-OIL8 or equivalent

  1. Install the O-ring on the suction hose sub-assembly.



    I033927
  1. Install the suction hose sub-assembly on the compressor and magnetic clutch with the nut.

    Torque:
    9.8 N*m{ 100 kgf*cm , 87 in.*lbf }



3. INSTALL DISCHARGE HOSE SUB-ASSEMBLY
  1. Remove the attached vinyl tape from the hose.

  1. Sufficiently apply compressor oil to the new O-ring and fitting surface of the compressor and magnetic clutch.

    Compressor oil:
    ND-OIL8 or equivalent

  1. Install an O-ring on the discharge hose sub-assembly.



    I033926
  1. Install the discharge hose sub-assembly on the compressor and magnetic clutch with the nut.

    Torque:
    9.8 N*m{ 100 kgf*cm , 87 in.*lbf }



4. INSPECT V-RIBBED BELT TENSIONER ASSEMBLY
  1. Remove the V belt from the tensioner pulley. Then check that nothing gets caught the tensioner by turning it clockwise and counterclockwise.

  1. When a malfunction exists, replace the tensioner.



5. INSTALL FAN AND GENERATOR V BELT


6. CHARGE REFRIGERANT
  1. Perform vacuum purging using a vacuum pump.



  1. Charge refrigerant HFC-134a (R134a).

    Standard:
    600 +- 30 g (21.16 +- 1.06 oz.)

    SST
    07110-58060   (07117-58060, 07117-58070, 07117-58080, 07117-58090, 07117-78050, 07117-88060, 07117-88070, 07117-88080)


    I037365E06

    NOTICE:
    1. Do not operate the cooler compressor before charging refrigerant as the cooler compressor will not work properly without any refrigerant, and will overheat.
    2. Approximately 100 g (3.53 oz.) of refrigerant may need to be charged after bubbles disappear. The refrigerant amount should be checked by measuring its quantity, and not with the sight glass.



7. WARM UP ENGINE
  1. Warm up the engine at less than 1,850 rpm for 2 minutes or more after charging the refrigerant.

    NOTICE:
    Be sure to warm up the compressor when turning the A/C switch ON after removing and installing the cooler refrigerant lines (including the compressor), to prevent damage to the compressor.



8. INSPECT LEAKAGE OF REFRIGERANT
  1. After recharging the refrigerant gas, check for refrigerant gas leakage using a halogen leak detector.

  1. Perform the operation under the following conditions:

    1. Stop the engine.
    2. Secure good ventilation (the gas leak detector may react to volatile gases other than refrigerant, such as evaporated gasoline or exhaust gas).
    3. Repeat the test 2 or 3 times.
    4. Make sure that some refrigerant remains in the refrigeration system. When compressor is off: approximately 392 to 588 kPa (4 to 6 kgf*cm2 57 to 85 psi)



    I042222E10
  1. Using a gas leak detector, check the refrigerant line for leakage.

  1. If a gas leak is not detected on the drain hose, remove the blower motor control (blower resistor) from the cooling unit. Insert the gas leak detector sensor into the unit and perform the test.

  1. Disconnect the connector and leave the pressure switch on for approximately 20 minutes. Bring the gas leak detector close to the pressure switch and perform the test.