HEATING / AIR CONDITIONING  AIR CONDITIONING SYSTEM  B1423  Pressure Sensor Circuit  


DESCRIPTION

for HFC-134a(R134a):

This DTC is stored if refrigerant pressure on the high pressure side is extremely low (0.176 MPaG (1.8 kgf/cm2, 26 psi) or less) or extremely high (3.025 MPaG (30.8 kgf/cm2, 439 psi) or more). The air conditioner pressure sensor, which is installed to the high pressure side pipe to detect refrigerant pressure, sends a refrigerant pressure signal to the air conditioning amplifier assembly. The air conditioning amplifier assembly converts this signal to a pressure value according to the sensor characteristics and uses it to control the compressor.


for HFO-1234yf(R1234yf):

This DTC is stored if refrigerant pressure on the high pressure side is extremely low (0.196 MPaG (2.0 kgf/cm2, 28 psi) or less) or extremely high (2.812 MPaG (28.7 kgf/cm2, 408 psi) or more). The air conditioner pressure sensor, which is installed to the high pressure side pipe to detect refrigerant pressure, sends a refrigerant pressure signal to the air conditioning amplifier assembly. The air conditioning conditioner pressure converts this signal to a pressure value according to the sensor characteristics and uses it to control the compressor.


DTC No. Detection Item DTC Detection Condition Trouble Area Memory
B1423 Pressure Sensor Circuit
Any of the following conditions is met:
·

Open in air conditioner pressure sensor circuit

·

Short in air conditioner pressure sensor circuit

·

Refrigerant pressure on high pressure side is extremely low (0.176 MPa (1.8 kgf/cm2, 26 psi) or less) or extremely high (3.025 MPa (30.8 kgf cm2, 439 psi) or more)*1

·

Refrigerant pressure on high pressure side is extremely low (0.195 MPaG (2.0 kgf/cm2, 28 psi) or less) or extremely high (2.812 MPaG (28.7 kgf/cm2, 408 psi) or more)*2


·

Air conditioner pressure sensor

·

Harness or connector

·

Air conditioning amplifier assembly

·

Cooler expansion valve (blocked, stuck)

·

Cooler condenser assembly (blocked, deterioration of cooling capacity due to dirt)

·

Cooler dryer (moisture in the refrigerant cycle cannot be absorbed)

·

Cooling fan system (cooler condenser assembly cannot be cooled down)

·

Air conditioning system (leaks, blocked)

·

Refrigerant volume (excessive, low)


-

Vehicle Condition
Pattern 1 Pattern 2 Pattern 3
Diagnosis Condition Power switch on (IG) ○ ○ ○
Malfunction Status Open in air conditioner pressure sensor circuit ○ - -
Short in air conditioner pressure sensor circuit - ○ -
Refrigerant pressure on high pressure side is extremely low (0.176 MPa (1.8 kgf/cm2, 26 psi) or less) or extremely high (3.025 MPa (30.8 kgf cm2, 439 psi) or more)*1 - - ○
Refrigerant pressure on high pressure side is extremely low (0.195 MPaG (2.0 kgf/cm2, 28 psi) or less) or extremely high (2.812 MPaG (28.7 kgf/cm2, 408 psi) or more)*2 - - -
Detection Time 4 seconds or more 4 seconds or more 4 seconds or more
Number of Trips 1 trip 1 trip 1 trip

*1: for HFC-134a(R134a)

*2: for HFO-1234yf(R1234yf)


WIRING DIAGRAM

E332460E14
2.125,0.406 2.583,0.667 0.458,0.26 10 false 3 2.135,0.896 2.594,1.156 0.458,0.26 10 false 2 2.125,1.354 2.583,1.615 0.458,0.26 10 false 1 1.917,0.51 2.375,0.771 0.458,0.26 10 false + 1.844,0.979 2.302,1.24 0.458,0.26 10 false PR 1.906,1.469 2.365,1.729 0.458,0.26 10 false - 0.417,2 1.438,2.281 1.021,0.281 10 false A22 0.406,2.146 2.531,2.458 2.125,0.313 10 false Air Conditioner Pressure Sensor 4.729,2 5.188,2.26 0.458,0.26 10 false F71 4.708,2.146 7.063,2.563 2.354,0.417 10 false Air Conditioning Amplifier Assembly 4.76,0.896 5.219,1.156 0.458,0.26 10 false 24 4.823,0.396 5.281,0.656 0.458,0.26 10 false 6 5.021,0.385 5.479,0.646 0.458,0.26 10 false S5-3 4.823,1.365 5.281,1.625 0.458,0.26 10 false 2 5.031,0.885 5.49,1.146 0.458,0.26 10 false PRE 5.021,1.354 5.479,1.615 0.458,0.26 10 false SG-2 6.479,0.958 6.938,1.219 0.458,0.26 10 false AD 5.885,0.323 6.344,0.583 0.458,0.26 10 false 5 V

CAUTION / NOTICE / HINT

NOTICE:
·

Be sure to check the refrigerant volume first when this DTC is output because this DTC can also be stored if there is no refrigerant in the cycle.


·

If DTC B1423 and B14B8 are output at the same time, troubleshoot for DTC B14B8 first.

Click hereVehicle Interior>HEATING / AIR CONDITIONING>AIR CONDITIONING SYSTEM>B14B8



HINT:

Make sure that the connector is properly connected. If it is not, securely connect it and check for DTCs again.


PROCEDURE

1.CHECK FOR DTC
a.

Check for DTCs.

Click hereVehicle Interior>HEATING / AIR CONDITIONING>AIR CONDITIONING SYSTEM>DTC CHECK / CLEAR

Body Electrical > Air Conditioner > Trouble Codes
50001 121

Result:
Result Proceed to
DTC B14B8 is not output (for HFC-134a(R134a)) A
DTC B14B8 is not output (for HFO-1234yf(R1234yf)) B
DTC B14B8 is output C



A

2.COMPARE REFRIGERANT GAS PRESSURE VALUES SHOWN ON GTS AND MANIFOLD GAUGE SET

B

3.COMPARE REFRIGERANT GAS PRESSURE VALUES SHOWN ON GTS AND MANIFOLD GAUGE SET

C

2.COMPARE REFRIGERANT GAS PRESSURE VALUES SHOWN ON GTS AND MANIFOLD GAUGE SET
a.

Read the Data List according to the display on the GTS.

Body Electrical > Air Conditioner > Data List
Tester Display Measurement Item Range Normal Condition Diagnostic Note
Regulator Pressure Sensor Air conditioner pressure sensor Min.: -0.45668 MPaG
Max.: 3.29437 MPaG
Actual refrigerant pressure displayed -
Body Electrical > Air Conditioner > Data List
Tester Display
Regulator Pressure Sensor
50003 121 51


c.

Compare the values displayed in the Data List and on the manifold gauge set.


Result:
Result Proceed to
Data List value and manifold gauge set value do not match and Data List value: 0.176 MPaG (1.8 kgf/cm2, 26 psi) or less A
Data List value and manifold gauge set value do not match and Data List value: 3.025 MPaG (30.8 kgf/cm2, 439 psi) or more B
Data List value matches manifold gauge set value C



A

4.READ VALUE USING GTS (REGULATOR PRESSURE SENSOR)

B

9.CHECK HARNESS AND CONNECTOR

C

GO TO ON-VEHICLE INSPECTION (CHECK REFRIGERANT PRESSURE USING GAUGE)

3.COMPARE REFRIGERANT GAS PRESSURE VALUES SHOWN ON GTS AND MANIFOLD GAUGE SET
a.

Read the Data List according to the display on the GTS.

Body Electrical > Air Conditioner > Data List
Tester Display Measurement Item Range Normal Condition Diagnostic Note
Regulator Pressure Sensor Air conditioner pressure sensor Min.: -0.45668 MPaG
Max.: 3.29437 MPaG
Actual refrigerant pressure displayed -
Body Electrical > Air Conditioner > Data List
Tester Display
Regulator Pressure Sensor
50003 121 51


c.

Compare the values displayed in the Data List and on the manifold gauge set.


Result:
Result Proceed to
Data List value and manifold gauge set value do not match and Data List value: 0.195 MPaG (2.0 kgf/cm2, 28 psi) or less A
Data List value and manifold gauge set value do not match and Data List value: 2.812 MPaG (28.7 kgf/cm2, 408 psi) or more B
Data List value matches manifold gauge set value C



A

4.READ VALUE USING GTS (REGULATOR PRESSURE SENSOR)

B

9.CHECK HARNESS AND CONNECTOR

C

GO TO ON-VEHICLE INSPECTION (CHECK REFRIGERANT PRESSURE USING GAUGE)

4.READ VALUE USING GTS (REGULATOR PRESSURE SENSOR)
a.

Connect the GTS to the DLC3.


b.

Turn the power switch on (IG).


c.

Turn the GTS on.


d.

Enter the following menus: Body Electrical / Air Conditioner / Data List.


e.

Read the Data List according to the display on the GTS.

Body Electrical > Air Conditioner > Data List
Tester Display Measurement Item Range Normal Condition Diagnostic Note
Regulator Pressure Sensor Air conditioner pressure sensor Min.: -0.45668 MPaG
Max.: 3.29437 MPaG
Actual refrigerant pressure displayed -
Body Electrical > Air Conditioner > Data List
Tester Display
Regulator Pressure Sensor
50003 121 51

OK:

Disconnecting the A22 connector of the air conditioner pressure sensor causes the Data List value to change.


Result:
Result Proceed to
Regulator pressure sensor value changes A
Regulator pressure sensor value does not change B



A

5.CHECK TERMINAL VOLTAGE (AIR CONDITIONER PRESSURE SENSOR)

B

7.CHECK TERMINAL VOLTAGE (AIR CONDITIONING AMPLIFIER ASSEMBLY)
5.CHECK TERMINAL VOLTAGE (AIR CONDITIONER PRESSURE SENSOR)
a.

Measure the voltage according to the value(s) in the table below.

Standard Voltage:
Tester Connection Switch Condition Specified Condition
A22-3 (+) - Body ground Power switch on (IG) 4.75 to 5.25 V



Result:
Proceed to
OK
NG



OK

NG

6.CHECK HARNESS AND CONNECTOR (AIR CONDITIONER PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER ASSEMBLY)
6.CHECK HARNESS AND CONNECTOR (AIR CONDITIONER PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER ASSEMBLY)
a.

Disconnect the F71 air conditioning amplifier assembly connector.


b.

Measure the resistance according to the value(s) in the table below.

Standard Resistance:
Tester Connection Condition Specified Condition
A22-3 (+) - F71-6 (S5-3) Always Below 1 Ω



Result:
Proceed to
OK
NG



OK

REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY

NG

REPAIR OR REPLACE HARNESS OR CONNECTOR

7.CHECK TERMINAL VOLTAGE (AIR CONDITIONING AMPLIFIER ASSEMBLY)
a.

Measure the voltage according to the value(s) in the table below.

Standard Voltage:
Tester Connection Switch Condition Specified Condition
A22-2 (PR) - Body ground Power switch on (IG) 3.0 to 5.25 V



Result:
Proceed to
OK
NG



OK

REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY

NG

8.CHECK HARNESS AND CONNECTOR (AIR CONDITIONER PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER ASSEMBLY)
8.CHECK HARNESS AND CONNECTOR (AIR CONDITIONER PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER ASSEMBLY)
a.

Disconnect the F71 air conditioning amplifier assembly connector.


b.

Measure the resistance according to the value(s) in the table below.

Standard Resistance:
Tester Connection Condition Specified Condition
A22-2 (PR) or F71-24 (PRE) - Other terminals and body ground Always 10 kΩ or higher



Result:
Proceed to
OK
NG



OK

REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY

NG

REPAIR OR REPLACE HARNESS OR CONNECTOR

9.CHECK HARNESS AND CONNECTOR
a.

Disconnect the A22 air conditioner pressure sensor connector.


b.

Measure the resistance according to the value(s) in the table below.

Standard Resistance:
Tester Connection Condition Specified Condition
A22-1 (-) - Body ground Always Below 1 Ω



Result:
Proceed to
OK
NG



OK

10.CHECK TERMINAL VOLTAGE

NG

15.CHECK HARNESS AND CONNECTOR (AIR CONDITIONER PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER ASSEMBLY)
10.CHECK TERMINAL VOLTAGE
a.

Measure the voltage according to the value(s) in the table below.

Standard Voltage:
Tester Connection Switch Condition Specified Condition
A22-2 (PR) - Body ground Power switch on (IG) 3.0 to 5.25 V



Result:
Result Proceed to
5.25 V or higher A
3.0 to 5.25 V B
Below 3.0 V C



A

11.CHECK HARNESS AND CONNECTOR (AIR CONDITIONER PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER ASSEMBLY)

B

12.CHECK INTERNAL CIRCUIT RESISTANCE (AIR CONDITIONING AMPLIFIER ASSEMBLY)

C

14.CHECK HARNESS AND CONNECTOR (AIR CONDITIONER PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER ASSEMBLY)
11.CHECK HARNESS AND CONNECTOR (AIR CONDITIONER PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER ASSEMBLY)
a.

Disconnect the F71 air conditioning amplifier assembly connector.


b.

Measure the resistance according to the value(s) in the table below.

Standard Resistance:
Tester Connection Condition Specified Condition
A22-2 (PR) or F71-24 (PRE) - Other terminals Always 10 kΩ or higher



Result:
Proceed to
OK
NG



OK

REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY

NG

REPAIR OR REPLACE HARNESS OR CONNECTOR

12.CHECK INTERNAL CIRCUIT RESISTANCE (AIR CONDITIONING AMPLIFIER ASSEMBLY)
a.

Measure the resistance according to the value(s) in the table below.

Standard Resistance:
Tester Connection Switch Condition Specified Condition
A22-3 (+) - A22-2 (PR) Power switch off 180 to 220 kΩ



HINT:

After turning the power switch off, wait at least 30 seconds before performing the measurement.


Result:
Proceed to
OK
NG



OK

NG

13.CHECK HARNESS AND CONNECTOR (AIR CONDITIONER PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER ASSEMBLY)
13.CHECK HARNESS AND CONNECTOR (AIR CONDITIONER PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER ASSEMBLY)
a.

Disconnect the F71 air conditioning amplifier assembly connector.


b.

Measure the resistance according to the value(s) in the table below.

Standard Resistance:
Tester Connection Condition Specified Condition
A22-2 (PR) or F71-24 (PRE) - A22-3 (+) or F71-6 (S5-3) Always 10 kΩ or higher



Result:
Proceed to
OK
NG



OK

REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY

NG

REPAIR OR REPLACE HARNESS OR CONNECTOR

14.CHECK HARNESS AND CONNECTOR (AIR CONDITIONER PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER ASSEMBLY)
a.

Disconnect the F71 air conditioning amplifier assembly connector.


b.

Measure the resistance according to the value(s) in the table below.

Standard Resistance:
Tester Connection Condition Specified Condition
A22-2 (PR) - F71-24 (PRE) Always Below 1 Ω



Result:
Proceed to
OK
NG



OK

REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY

NG

REPAIR OR REPLACE HARNESS OR CONNECTOR

15.CHECK HARNESS AND CONNECTOR (AIR CONDITIONER PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER ASSEMBLY)
a.

Disconnect the F71 air conditioning amplifier assembly connector.


b.

Measure the resistance according to the value(s) in the table below.

Standard Resistance:
Tester Connection Condition Specified Condition
A22-1 (-) - F71-2 (SG-2) Always Below 1 Ω



Result:
Proceed to
OK
NG



OK

REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY

NG

REPAIR OR REPLACE HARNESS OR CONNECTOR