Home › HEATER & AIR CONDITIONING SYSTEM › AIR CONDITIONING › AIR CONDITIONING SYSTEM

DTC    B1423/23    Pressure Sensor Circuit

for Preparation Click here


DESCRIPTION

This DTC is output when refrigerant pressure is extremely low (0.19 MPa (2.0 kgf/cm2, 28 psi) or less) or extremely high (3.14 MPa (32.0 kgf/cm2, 455 psi) or more). The pressure sensor, which is installed on the pipe of the high pressure side to detect refrigerant pressure, outputs a refrigerant pressure signal to the A/C amplifier. The A/C amplifier converts this signal to pressure according to the sensor characteristics to control the compressor.

HINT:
Be sure to check the refrigerant volume first when this DTC is output because this DTC can also be output if there is no refrigerant in the system.


DTC No.
DTC Detection Condition
Trouble Area
B1423/23
Open or short in pressure sensor circuit
  1. Pressure sensor
  2. Harness or connector between pressure sensor and A/C amplifier
  3. Refrigerant pipe line
  4. A/C amplifier

WIRING DIAGRAM


E116878E04


INSPECTION PROCEDURE

1.CHECK REFRIGERANT PRESSURE
  1. Install the manifold gauge set .



    E050573
  1. Read the manifold gauge pressure when the following conditions are established.

    1. Prepare the vehicle according to the chart below.
      Item
      Condition
      Vehicle Doors
      Fully open
      Temperature Setting
      MAX COLD
      Blower Speed
      HI
      A/C Switch
      ON
      R/F Switch
      RECIRCULATION
      (30 to 35°C (86 to 95°F))

      Standard pressure:
      Low pressure side:
      0.15 to 0.25 MPa (1.5 to 2.5 kgf/cm2, 21.3 to 35.6 psi)
      High pressure side:
      1.37 to 1.57 MPa (14 to 16 kgf/cm2, 199 to 228 psi)



NG
CHARGE REFRIGERANT
OK


2.CHECK HARNESS AND CONNECTOR (PRESSURE SENSOR - A/C AMPLIFIER)


    E124477E02
  1. Disconnect the pressure sensor connector.



    E124470E08
  1. Disconnect the A/C amplifier connector.

  1. Measure the resistance according to the value(s) in the table below.

    Standard resistance:
    Tester Connection
    Condition
    Specified Condition
    A27-2 (PR) - E38-9 (PRE)
    Always
    Below 1 Ω
    A27-3 (+) - E38-10 (S5-3)
    Always
    Below 1 Ω
    A27-1 (-) - E38-13 (SG-2)
    Always
    Below 1 Ω
    E38-9 (PRE) - Body ground
    Always
    10 kΩ or higher
    E38-10 (S5-3) - Body ground
    Always
    10 kΩ or higher
    E38-13 (SG-2) - Body ground
    Always
    10 kΩ or higher



NG
REPAIR OR REPLACE HARNESS OR CONNECTOR
OK


3.INSPECT PRESSURE SENSOR
  1. Install the manifold gauge set .



    E107326E05
  1. Connect the three 1.5 V dry cell batterie's positive (+) lead to terminal 3, and the negative (-) lead to terminal 1. Then connect the voltmeter's positive (+) lead to terminal 2, and the negative (-) lead to terminal 1. Measure the voltage.

    OK:
    The voltage changes according to refrigerant pressure, as shown in the graph.

Result:
Result
Proceed to
NG
A
OK (When troubleshooting according to the DTC)
B
OK (When troubleshooting according to the PROBLEM SYMPTOMS TABLE)
C



B
REPLACE AIR CONDITIONING AMPLIFIER

C
PROCEED TO NEXT CIRCUIT INSPECTION SHOWN IN PROBLEM SYMPTOMS TABLE
A

REPLACE PRESSURE SENSOR