DATA LIST
In the table below, the values listed under "Normal Condition" are reference values. Do not depend solely on these reference values when deciding whether a part is faulty or not.
Using the GTS to read the Data List allows the values or states of switches, sensors, actuators and other items to be read without removing any parts. This non-intrusive inspection can be very useful because intermittent conditions or signals may be discovered before parts or wiring is disturbed. Reading the Data List information early in troubleshooting is one way to save diagnostic time.
Connect the GTS to the DLC3.
Turn the power switch on (IG).
Turn the GTS on.
Enter the following menus:
for Air Conditioner: Body Electrical / Air Conditioner / Data List.
for Engine: Powertrain / Engine / Data List.
Read the Data List according to the display on the GTS.
| Tester Display | Measurement Item | Range | Normal Condition | Diagnostic Note |
|---|---|---|---|---|
| Room Temperature Sensor | Cooler (room temp. sensor) thermistor | Min.: -6.50°C (20.30°F)
Max.: 57.25°C (135.05°F) |
Actual cabin temperature displayed | Cooler (room temp. sensor) thermistor circuit malfunction
·
When open circuit: -6.50°C (20.30°F) ·
When short circuit: 57.25°C (135.05°F) |
| Ambient Temp Sensor | Thermistor assembly | Min.: -23.30°C (-9.94°F)
Max.: 65.95°C (150.71°F) |
Actual ambient temperature displayed | Thermistor assembly circuit malfunction
·
When open circuit: -23.30°C (-9.94°F) ·
When short circuit: 65.95°C (150.71°F) |
| Adjusted Ambient Temp | Adjusted ambient temperature | Min.: -30.80°C (-23.44°F)
Max.: 50.80°C (123.44°F) |
Adjust ambient temperature displayed | Air conditioning amplifier assembly circuit malfunction |
| Evaporator Fin Thermistor | No. 1 cooler thermistor | Min.: -29.70°C (-21.46°F)
Max.: 59.55°C (139.19°F) |
Actual evaporator temperature displayed | No. 1 cooler thermistor circuit malfunction
·
When open circuit: -29.70°C (-21.46°F) ·
When short circuit: 59.55°C (139.19°F) |
| Evaporator Target Temp | Evaporator target temperature | Min.: -327.68°C (-557.82°F)
Max.: 327.67°C (621.81°F) |
Evaporator target temperature displayed | No. 1 cooler thermistor circuit malfunction
·
When open circuit: -327.68°C (-557.82°F) ·
When short circuit: 327.67°C (621.81°F) |
| Solar Sensor (D Side) | Driver side automatic light control sensor | Min.: 0
Max.: 255 |
Driver side automatic light control sensor value increases as brightness increases | Driver side automatic light control sensor circuit malfunction
·
When open circuit: 0 ·
When short circuit: 255 |
| Solar Sensor (P Side) | Front passenger side automatic light control sensor | Min.: 0
Max.: 255 |
Front passenger side automatic light control sensor value increases as brightness increases | Front passenger side automatic light control sensor circuit malfunction
·
When open circuit: 0 ·
When short circuit: 255 |
| Engine Coolant Temp | Engine coolant temperature sensor | Min.: 1.30°C (34.34°F)
Max.: 90.55°C (194.99°F) |
Actual engine coolant temperature displayed | ·
SFI system malfunction ·
CAN communication system malfunction |
| Blower Motor Speed Level | Blower motor speed level | Min.: 0
Max.: 31 |
Displayed speed level increases in range between 0 and 31 as blower motor speed increases | Blower motor with fan sub-assembly circuit malfunction |
| Regulator Pressure Sensor | Air conditioner pressure sensor | Min.: -0.4566 MPaG
Max.: 3.2943 MPaG |
Actual refrigerant pressure displayed | ·
Refrigerant line (gas leak etc.) ·
Air conditioner pressure sensor circuit malfunction |
| Air Outlet Servo Pulse (R) | No. 2 air conditioning radiator damper servo sub-assembly target pulse | Min.: 128
Max.: 383 |
·
FACE: 260 (pulse) ·
B/L: 212 (pulse) ·
FOOT: 182 (pulse) ·
F/D: 223 (pulse) ·
SHUT: 158 (pulse) ·
D/F: 177 (pulse) |
No. 2 air conditioning radiator damper servo sub-assembly circuit malfunction |
| Air Outlet Servo Actual Pls(R) | No. 2 air conditioning radiator damper servo sub-assembly actual pulse | Min.: 128
Max.: 383 |
·
FACE: 260 (pulse) ·
B/L: 212 (pulse) ·
FOOT: 182 (pulse) ·
F/D: 223 (pulse) ·
SHUT: 158 (pulse) ·
D/F: 177 (pulse) |
No. 2 air conditioning radiator damper servo sub-assembly circuit malfunction |
| Air Mix Servo Targ Pulse(R) | No. 3 air conditioning radiator damper servo sub-assembly target pulse | Min.: 128
Max.: 383 |
·
MAX COLD: 257 (pulse) ·
MAX HOT: 165 (pulse) |
No. 3 air conditioning radiator damper servo sub-assembly circuit malfunction*1 |
| Air Mix Servo Actual Pulse(R) | No. 3 air conditioning radiator damper servo sub-assembly actual pulse | Min.: 128
Max.: 383 |
·
MAX COLD: 257 (pulse) ·
MAX HOT: 165 (pulse) |
No. 3 air conditioning radiator damper servo sub-assembly circuit malfunction*1 |
| Air Mix Servo Targ Pulse(D) | No. 1 air conditioning radiator damper servo sub-assembly (driver side air mix) target pulse | Min.: 128
Max.: 383 |
for LHD:
·
MAX COLD: 257 (pulse) ·
MAX HOT: 165 (pulse) for RHD:
·
MAX COLD: 255 (pulse) ·
MAX HOT: 347 (pulse) |
No. 1 air conditioning radiator damper servo sub-assembly (driver side air mix) circuit malfunction |
| Air Mix Servo Actual Pulse(D) | No. 1 air conditioning radiator damper servo sub-assembly (driver side air mix) actual pulse | Min.: 128
Max.: 383 |
for LHD:
·
MAX COLD: 257 (pulse) ·
MAX HOT: 165 (pulse) for RHD:
·
MAX COLD: 255 (pulse) ·
MAX HOT: 347 (pulse) |
No. 1 air conditioning radiator damper servo sub-assembly (driver side air mix) circuit malfunction |
| Air Mix Servo Targ Pulse(P) | No. 1 air conditioning radiator damper servo sub-assembly (front passenger side air mix) target pulse | Min.: 128
Max.: 383 |
for LHD:
·
MAX COLD: 255 (pulse) ·
MAX HOT: 347 (pulse) for RHD:
·
MAX COLD: 257 (pulse) ·
MAX HOT: 165 (pulse) |
No. 1 air conditioning radiator damper servo sub-assembly (front passenger side air mix) circuit malfunction |
| Air Mix Servo Actual Pulse(P) | No. 1 air conditioning radiator damper servo sub-assembly (front passenger side air mix) actual pulse | Min.: 128
Max.: 383 |
for LHD:
·
MAX COLD: 255 (pulse) ·
MAX HOT: 347 (pulse) for RHD:
·
MAX COLD: 257 (pulse) ·
MAX HOT: 165 (pulse) |
No. 1 air conditioning radiator damper servo sub-assembly (front passenger side air mix) circuit malfunction |
| Air Outlet Servo Pulse (D) | for LHD (for 3 Zone Type):
No. 4 air conditioning radiator damper servo sub-assembly target pulse for LHD (except 3 Zone Type):
No. 1 air conditioning radiator damper servo sub-assembly (mode) target pulse for RHD:
No. 1 air conditioning radiator damper servo sub-assembly (driver side mode) target pulse |
Min.: 128
Max.: 383 |
for LHD (for 3 Zone Type):
·
FACE-R: 271 (pulse) ·
FACE: 256 (pulse) ·
FACE1: 256 (pulse) ·
FACE2: 256 (pulse) ·
B/L: 245 (pulse) ·
B/L2: 245 (pulse) ·
FOOT-R: 215 (pulse) ·
FOOT: 215 (pulse) ·
FOOT-D: 207 (pulse) ·
FOOT-0: 224 (pulse) ·
F/D: 192 (pulse) ·
DEF-FOOT: 173 (pulse) ·
DEF or SHUT: 164 (pulse) for LHD (except 3 Zone Type):
·
FACE-R: 241 (pulse) ·
FACE: 256 (pulse) ·
FACE1: 256 (pulse) ·
FACE2: 256 (pulse) ·
B/L: 267 (pulse) ·
B/L2: 267 (pulse) ·
FOOT-R: 297 (pulse) ·
FOOT: 297 (pulse) ·
FOOT-D: 305 (pulse) ·
FOOT-0: 288 (pulse) ·
F/D: 320 (pulse) ·
DEF-FOOT: 339 (pulse) ·
DEF or SHUT: 348 (pulse) for RHD:
·
FACE-R: 241 (pulse) ·
FACE: 256 (pulse) ·
FACE1: 256 (pulse) ·
FACE2: 256 (pulse) ·
B/L: 267 (pulse) ·
B/L2: 267 (pulse) ·
FOOT-R: 297 (pulse) ·
FOOT: 297 (pulse) ·
FOOT-D: 305 (pulse) ·
FOOT-0: 288 (pulse) ·
F/D: 320 (pulse) ·
DEF-FOOT: 339 (pulse) ·
DEF or SHUT: 348 (pulse) |
for LHD (for 3 Zone Type):
No. 4 air conditioning radiator damper servo sub-assembly circuit malfunction for LHD (except 3 Zone Type):
No. 1 air conditioning radiator damper servo sub-assembly (mode) circuit malfunction for RHD:
No. 1 air conditioning radiator damper servo sub-assembly (driver side mode) circuit malfunction |
| Air Outlet Servo Actu Pulse(D) | for LHD (for 3 Zone Type):
No. 4 air conditioning radiator damper servo sub-assembly actual pulse for LHD (except 3 Zone Type):
No. 1 air conditioning radiator damper servo sub-assembly (mode) actual pulse for RHD:
No. 1 air conditioning radiator damper servo sub-assembly (driver side mode) actual pulse |
Min.: 128
Max.: 383 |
for LHD (for 3 Zone Type):
·
FACE-R: 271 (pulse) ·
FACE: 256 (pulse) ·
FACE1: 256 (pulse) ·
FACE2: 256 (pulse) ·
B/L: 245 (pulse) ·
B/L2: 245 (pulse) ·
FOOT-R: 215 (pulse) ·
FOOT: 215 (pulse) ·
FOOT-D: 207 (pulse) ·
FOOT-0: 224 (pulse) ·
F/D: 192 (pulse) ·
DEF-FOOT: 173 (pulse) ·
DEF or SHUT: 164 (pulse) for LHD (except 3 Zone Type):
·
FACE-R: 241 (pulse) ·
FACE: 256 (pulse) ·
FACE1: 256 (pulse) ·
FACE2: 256 (pulse) ·
B/L: 267 (pulse) ·
B/L2: 267 (pulse) ·
FOOT-R: 297 (pulse) ·
FOOT: 297 (pulse) ·
FOOT-D: 305 (pulse) ·
FOOT-0: 288 (pulse) ·
F/D: 320 (pulse) ·
DEF-FOOT: 339 (pulse) ·
DEF or SHUT: 348 (pulse) for RHD:
·
FACE-R: 241 (pulse) ·
FACE: 256 (pulse) ·
FACE1: 256 (pulse) ·
FACE2: 256 (pulse) ·
B/L: 267 (pulse) ·
B/L2: 267 (pulse) ·
FOOT-R: 297 (pulse) ·
FOOT: 297 (pulse) ·
FOOT-D: 305 (pulse) ·
FOOT-0: 288 (pulse) ·
F/D: 320 (pulse) ·
DEF-FOOT: 339 (pulse) ·
DEF or SHUT: 348 (pulse) |
for LHD (for 3 Zone Type):
No. 4 air conditioning radiator damper servo sub-assembly circuit malfunction for LHD (except 3 Zone Type):
No. 1 air conditioning radiator damper servo sub-assembly (mode) circuit malfunction for RHD:
No. 1 air conditioning radiator damper servo sub-assembly (driver side mode) circuit malfunction |
| Air Outlet Servo Targ Pulse(P) | for LHD:
No. 1 air conditioning radiator damper servo sub-assembly (front passenger side mode) target pulse for RHD:
No. 4 air conditioning radiator damper servo sub-assembly target pulse |
Min.: 128
Max.: 383 |
for LHD:
·
FACE-R: 241 (pulse) ·
FACE: 256 (pulse) ·
FACE1: 256 (pulse) ·
FACE2: 256 (pulse) ·
B/L: 267 (pulse) ·
B/L2: 267 (pulse) ·
FOOT-R: 297 (pulse) ·
FOOT: 297 (pulse) ·
FOOT-D: 305 (pulse) ·
FOOT-0: 288 (pulse) ·
F/D: 320 (pulse) ·
DEF-FOOT: 339 (pulse) ·
DEF or SHUT: 348 (pulse) for RHD:
·
FACE-R: 271 (pulse) ·
FACE: 256 (pulse) ·
FACE1: 256 (pulse) ·
FACE2: 256 (pulse) ·
B/L: 245 (pulse) ·
B/L2: 245 (pulse) ·
FOOT-R: 215 (pulse) ·
FOOT: 215 (pulse) ·
FOOT-D: 207 (pulse) ·
FOOT-0: 224 (pulse) ·
F/D: 192 (pulse) ·
DEF-FOOT: 173 (pulse) ·
DEF or SHUT: 164 (pulse) |
for LHD:
No. 1 air conditioning radiator damper servo sub-assembly (front passenger side mode) circuit malfunction*1 for RHD:
No. 4 air conditioning radiator damper servo sub-assembly circuit malfunction |
| Air Outlet Servo Actu Pulse(P) | for LHD:
No. 1 air conditioning radiator damper servo sub-assembly (front passenger side mode) actual pulse for RHD:
No. 4 air conditioning radiator damper servo sub-assembly actual pulse |
Min.: 128
Max.: 383 |
for LHD:
·
FACE-R: 241 (pulse) ·
FACE: 256 (pulse) ·
FACE1: 256 (pulse) ·
FACE2: 256 (pulse) ·
B/L: 267 (pulse) ·
B/L2: 267 (pulse) ·
FOOT-R: 297 (pulse) ·
FOOT: 297 (pulse) ·
FOOT-D: 305 (pulse) ·
FOOT-0: 288 (pulse) ·
F/D: 320 (pulse) ·
DEF-FOOT: 339 (pulse) ·
DEF or SHUT: 348 (pulse) for RHD:
·
FACE-R: 271 (pulse) ·
FACE: 256 (pulse) ·
FACE1: 256 (pulse) ·
FACE2: 256 (pulse) ·
B/L: 245 (pulse) ·
B/L2: 245 (pulse) ·
FOOT-R: 215 (pulse) ·
FOOT: 215 (pulse) ·
FOOT-D: 207 (pulse) ·
FOOT-0: 224 (pulse) ·
F/D: 192 (pulse) ·
DEF-FOOT: 173 (pulse) ·
DEF or SHUT: 164 (pulse) |
for LHD:
No. 1 air conditioning radiator damper servo sub-assembly (front passenger side mode) circuit malfunction*1 for RHD:
No. 4 air conditioning radiator damper servo sub-assembly circuit malfunction |
| Air Inlet Damper Targ Pulse | No. 1 blower damper servo sub-assembly target pulse | Min.: 128
Max.: 383 |
for 2-tier Type:
·
Recirculation: 256 (pulse) ·
Fresh: 220 (pulse) for 1-tier Type:
·
Recirculation: 258 (pulse) ·
Fresh: 235 (pulse) |
No. 1 blower damper servo sub-assembly circuit malfunction |
| Air Inlet Damper Actual Pulse | No. 1 blower damper servo sub-assembly actual pulse | Min.: 128
Max.: 383 |
for 2-tier Type:
·
Recirculation: 256 (pulse) ·
Fresh: 220 (pulse) for 1-tier Type:
·
Recirculation: 258 (pulse) ·
Fresh: 235 (pulse) |
No. 1 blower damper servo sub-assembly circuit malfunction |
| Electric Heater Count | Maximum electric heater operation level | Min.: 0
Max.: 2 |
Maximum possible operation level of electric heater displayed | PTC heater circuit malfunction |
| Electric Heater Active Level | Actual electric heater operation level | Min.: 0
Max.: 2 |
Actual operation level of electric heater displayed | PTC heater circuit malfunction |
| Compressor Speed | Compressor speed | Min.: 0 rpm
Max.: 65535 rpm |
Actual compressor speed displayed | - |
| Compressor Target Speed | Compressor target speed | Min.: 0 rpm
Max.: 65535 rpm |
Compressor target speed displayed | - |
| Shift Set Temperature | Shift set temperature | 2C decr, 1C decr, Normal, 1C incr or 2C incr | Customized value displayed | - |
| Air Inlet Mode | Air inlet mode | Auto or Manual | Customized value displayed | - |
| Compressor Mode | Compressor mode | Auto or Manual | Customized value displayed | - |
| Noise and Vibration Reduction | Function to change the speed of the compressor when set to ON | OFF or ON | Customized value displayed | - |
| ECO MODE Cancel | Function to cancel ECO mode when set to ON | OFF or ON | Customized value displayed | - |
| ECO Switch | ECO switch assembly (electric parking brake switch assembly) | OFF or ON | OFF: ECO switch assembly (electric parking brake switch assembly) not pushed
ON: ECO switch assembly (electric parking brake switch assembly) pushed and held |
ECO switch assembly (electric parking brake switch assembly) circuit malfunction |
| Refrigerant Shortage Check | Refrigerant shortage check | ON or OFF | Customized value displayed | - |
| Fan speed increment control | Fan speed increment control | Slow, Normal or Fast | Customized value displayed | - |
| Foot/DEF Auto Mode | Foot/defroster auto mode | ON or OFF | Customized value displayed | - |
| Foot/DEF Auto Blow Up | Foot/defroster auto blower speed increase | ON or OFF | Customized value displayed | - |
| Ambient Temperature Shift | Ambient temperature shift | 3C decr, 2C decr, 1C decr, Normal, 1C incr, 2C incr or 3C incr | Customized value displayed | - |
| Compressor Drive Check | Compressor drive check | OK or NG | OK: Compressor drives
NG: Compressor does not drive |
- |
| Ion Generate Control | Ion generator switch function | ON or OFF | Customized value displayed | *2 |
| Refrigerant Gas Type | Refrigerant gas type | R134a or 1234yf | Refrigerant gas type displayed | - |
| Set Temperature (D Side) | Driver side set temperature | Min.: MAX COLD
Max.: MAX HOT |
Driver side set temperature displayed | - |
| Set Temperature (P Side) | Front passenger side set temperature | Min.: MAX COLD
Max.: MAX HOT |
Front passenger side set temperature displayed | - |
| Set Temperature (Rear) | Rear side set temperature | Min.: MAX COLD
Max.: MAX HOT |
Rear side set temperature displayed | *1 |
| Outside Air Mode Auto Switch Function | Outside air mode auto switch function | ON or OFF | Customized value displayed | - |
| Number of Trouble Codes | Number of trouble codes | Min.: 0
Max.: 255 |
Number of DTCs displayed | - |
| Refrigerant High Pressure History | Refrigerant high pressure history | Min.: 0
Max.: 255 |
Number of times refrigerant high pressure history stored displayed | *3 |
*1: for 3 Zone Type
*2: w/ Ion Generator
*3: Refer to the following procedure to clear the refrigerant high pressure history.
Click hereVehicle Interior>HEATING / AIR CONDITIONING>AIR CONDITIONING SYSTEM>UTILITY
| Tester Display | Measurement Item | Range | Normal Condition | Diagnostic Note |
|---|---|---|---|---|
| Coolant Temperature | Engine coolant temperature | Min.: -40°C (-40°F)
Max.: 140°C (284°F) |
75 to 100°C (167 to 212°F): After warming up | This is the engine coolant temperature.
|
ACTIVE TEST
Using the GTS to perform Active Tests allows relays, VSVs, actuators and other items to be operated without removing any parts. This non-intrusive functional inspection can be very useful because intermittent operation may be discovered before parts or wiring is disturbed. Performing Active Tests early in troubleshooting is one way to save diagnostic time. Data List information can be displayed while performing Active Tests.
Connect the GTS to the DLC3.
Turn the power switch on (IG).
Turn the GTS on.
Enter the following menus:
for Air Conditioner: Body Electrical / Air Conditioner / Active Test.
for Engine: Powertrain / Engine / Active Test.
Perform the Active Test according to the display on the GTS.
| Tester Display | Measurement Item | Control Range | Diagnostic Note |
|---|---|---|---|
| Blower Motor | Blower motor with fan sub-assembly | Min.: 0
Max.: 31 |
- |
| Compressor Target Speed | Compressor with motor assembly | Min.: 0
Max.: 7500 |
- |
| Defogger Relay (Rear) | Rear window defogger | OFF or ON | - |
| Heater Active Level | Quick heater assembly | Min.: 0
Max.: 2 |
- |
| Air Mix Servo Targ Pulse(D) | No. 1 air conditioning radiator damper servo sub-assembly (driver side air mix) pulse | Min.: 128
Max.: 383 |
for LHD:
Operates between 165 to 257 pulses for RHD:
Operates between 255 to 347 pulses |
| Air Mix Servo Targ Pulse(P) | No. 1 air conditioning radiator damper servo sub-assembly (front passenger side air mix) pulse | Min.: 128
Max.: 383 |
for LHD:
Operates between 255 to 347 pulses for RHD:
Operates between 165 to 257 pulses |
| Air Outlet Servo Pulse (D) | for LHD (for 3 Zone Type):
No. 4 air conditioning radiator damper servo sub-assembly pulse for LHD (except 3 Zone Type):
No. 1 air conditioning radiator damper servo sub-assembly (mode) pulse for RHD:
No. 1 air conditioning radiator damper servo sub-assembly (driver side mode) pulse |
Min.: 128
Max.: 383 |
for LHD (for 3 Zone Type):
Operates between 164 to 271 pulses for LHD (except 3 Zone Type):
Operates between 241 to 348 pulses for RHD:
Operates between 241 to 348 pulses |
| Air Inlet Damper Targ Pulse | No. 1 blower damper servo sub-assembly pulse | Min.: 128
Max.: 383 |
for 2-tier Type
Operates between 220 to 256 pulses for 1-tier Type
Operates between 235 to 258 pulses |
| Rear Air Mix Servo Targ Pulse | No. 3 air conditioning radiator damper servo sub-assembly pulse | Min.: 128
Max.: 383 |
Operates between 165 to 257 pulses*1 |
| Air Outlet Servo Pulse (P) | for LHD:
No. 1 air conditioning radiator damper servo sub-assembly (front passenger side mode) pulse for RHD:
No. 4 air conditioning radiator damper servo sub-assembly pulse |
Min.: 128
Max.: 383 |
for LHD:
Operates between 241 to 348 pulses*1 for RHD:
Operates between 164 to 271 pulses |
| A/O Servo Pulse(Rr D) | No. 2 air conditioning radiator damper servo sub-assembly pulse | Min.: 128
Max.: 383 |
Operates between 158 to 260 pulses |
| Ion Generator | Ion generator sub-assembly | OFF or ON | *2 |
*1: for 3 Zone Type
*2: w/ Ion Generator
| Tester Display | Measurement Item | Control Range | Diagnostic Note |
|---|---|---|---|
| Control the Engine Cooling Fan Duty Ratio | Control the cooling fan | 0 to 100% | Perform this test when vehicle is stopped. |