Home › HEATER & AIR CONDITIONING SYSTEM › AIR CONDITIONING › AIR CONDITIONING UNIT

AIR CONDITIONING UNIT > INSPECTION

for Preparation Click here



1. INSPECT NO. 1 COOLER THERMISTOR


I102503E01
  1. Measure the resistance.

    Standard resistance:
    Tester Connection
    Condition
    Specified Condition
    1 - 2
    -10°C (14°F)
    7.30 to 9.10 kΩ
    1 - 2
    -5°C (23°F)
    5.65 to 6.95 kΩ
    1 - 2
    0°C (32°F)
    4.40 to 5.35 kΩ
    1 - 2
    5°C (41°F)
    3.40 to 4.15 kΩ
    1 - 2
    10°C (50°F)
    2.70 to 3.25 kΩ
    1 - 2
    15°C (59°F)
    2.14 to 2.58 kΩ
    1 - 2
    20°C (68°F)
    1.71 to 2.05 kΩ
    1 - 2
    25°C (77°F)
    1.38 to 1.64 kΩ
    1 - 2
    30°C (86°F)
    1.11 to 1.32 kΩ

    NOTICE:
    1. Touching the sensor even slightly may change the resistance value. Hold the connector of the sensor.
    2. When measuring the resistance, the temperature of the sensor and the cooler thermistor must be the same.

    HINT:
    As the temperature increases, the resistance decreases (see the graph).
    If the operation is not as specified, replace the cooler thermistor.



2. INSPECT MODE CONTROL SERVO MOTOR


I102497E01
  1. Inspect the servo motor operation.

    1. Connect the positive (+) lead from the battery to terminal 4 (DEF) and negative (-) lead to terminal 5 (FACE), then check that the lever turns to the DEF position smoothly.

      Standard:
      The motor operates smoothly.

      If the operations are not as specified, replace the mode control servo motor.

    2. Connect the positive (+) lead from the battery to terminal 5 (FACE) and negative (-) lead to terminal 4 (DEF), then check that the lever turns to the FACE position smoothly.

      Standard:
      The motor operates smoothly.

      If the operations are not as specified, replace the mode control servo motor.

  1. Check the servo motor resistance.

    1. Using an ohmmeter, measure the resistance and check the results in accordance with the values in the table below.

      Standard resistance:
      Tester Connection
      Servo Motor Position
      Specified Condition
      1 (SG) - 2 (S5)
      Always
      4.2 to 7.8 kΩ
      1 (SG) - 3 (TPM)
      DEF Position
      3.4 to 6.2 kΩ
      1 (SG) - 3 (TPM)
      FACE Position
      0.8 to 1.6 kΩ

      If the result is not as specified, replace the mode control servo motor.



3. REMOVE AIR MIX CONTROL SERVO MOTOR


I102498E01
  1. Inspect the servo motor operation.

    1. Connect the positive (+) lead from the battery to terminal 4 (MH) and negative (-) lead to terminal 5 (MC), then check that the lever turns to the MAX HOT position smoothly.

      Standard:
      The motor operates smoothly.

      If the operations are not as specified, replace the air mix control servo motor.

    2. Connect the positive (+) lead from the battery to terminal 5 (MC) and negative (-) lead to terminal 4 (MH), then check that the lever turns to the MAX COOL position smoothly.

      Standard:
      The motor operates smoothly.

      If the operations are not as specified, replace the air mix control servo motor.

  1. Check the servo motor resistance.

    1. Using an ohmmeter, measure the resistance and check the results in accordance with the values in the table below.

      Standard resistance:
      Tester Connection
      Servo Motor Position
      Specified Condition
      1 (SG) - 2 (S5)
      Always
      4.2 to 7.8 kΩ
      1 (SG) - 3 (TP)
      MAX HOT Position
      3.4 to 6.2 kΩ
      1 (SG) - 3 (TP)
      MAX COOL Position
      0.8 to 1.6 kΩ

      If the result is not as specified, replace the air mix control servo motor.