REFRIGERANT > ON-VEHICLE INSPECTION |
| 1. INSPECT REFRIGERANT VOLUME |
![]() |
Check the sight glass on the liquid tube sub-assembly A.
Test conditions:
| Item | Symptom | Amount of refrigerant | Corrective Action |
| 1 | Bubbles exist | Insufficient* |
|
| 2 | No bubbles exist | Empty, insufficient or excessive | Refer to 3 and 4 |
| 3 | No temperature difference between compressor inlet and outlet | Empty or nearly empty |
|
| 4 | Considerable temperature difference between compressor inlet and outlet | Proper or excessive | Refer to 5 and 6 |
| 5 | Immediately after air conditioning is turned off, refrigerant clears | Excessive |
|
| 6 | Immediately after air conditioning is turned off, refrigerant foams and then becomes clear | Proper | - |
| 2. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET |
This is a method in which the trouble is located by using a manifold gauge set. Read the manifold gauge pressure when the following conditions are established.
Test conditions:
![]() |
Refrigerant system functions normally.
Moisture present in refrigeration system.

| Symptom | Probable cause | Diagnosis | Corrective Action |
| During operation, pressure on low pressure side cycles between normal and vacuum | Moisture in refrigeration system freezes at expansion valve orifice, causing a temporary stop of cycle. However, when it melts, normal state is restored. |
|
|
Insufficient cooling

| System | Probable cause | Diagnosis | Corrective Action |
| Gas leakage in refrigeration system |
|
|
Poor circulation of refrigerant

| System | Probable cause | Diagnosis | Corrective Action |
| Refrigerant flow is obstructed by dirt in the receiver | Receiver is clogged | Replace condenser |
Refrigerant does not circulate.

| System | Probable cause | Diagnosis | Corrective Action |
|
| Refrigerant does not circulate |
|
Refrigerant is overcharged or cooling effectiveness of condenser is insufficient.

| System | Probable cause | Diagnosis | Corrective Action |
|
|
|
|
Air is present in refrigeration system.

| System | Probable cause | Diagnosis | Corrective Action |
| Air in system |
|
|
Expansion valve malfunction

| System | Probable cause | Diagnosis | Corrective Action |
| Trouble in expansion valve |
| Check expansion valve |
Defective compressor

| System | Probable cause | Diagnosis | Corrective Action |
| Internal leak in compressor |
| Repair or replace compressor |