AIR OUTLET MODE CONTROL SWITCH > INSPECTION

for Preparation Click here



1. INSPECT AIR OUTLET MODE CONTROL SWITCH


    E103714E01
  1. Remove the air outlet mode control switch and disconnect the connector.

  1. Measure the resistance according to the value(s) in the table below.

    Standard resistance (2KD-FTV, 2TR-FE):
    Tester connection
    Condition
    Specified condition
    2 (L) - 3 (E)
    A/C switch OFF
    10 kΩ or higher
    2 (L) - 4 (B)
    A/C switch OFF
    10 kΩ or higher
    3 (E) - 4 (B)
    Always
    Below 1 Ω
    3 (E) - 2 (L)
    A/C switch ON
    Below 1 Ω
    2 (L - 4 (B)
    A/C switch ON
    Below 1 Ω
    5 (ILL+) - 6 ILL-)
    Always
    Below 1 Ω

    Standard resistance (5L-E):
    Tester connection
    Condition
    Specified condition
    2 (L) - 3 (E)
    A/C switch OFF
    10 kΩ or higher
    3 (E) - 4 (B)
    A/C switch OFF
    10 kΩ or higher
    2 (L) - 4 (B)
    Always
    Below 1 Ω
    2 (L) - 3 (E)
    A/C switch ON
    Below 1 Ω
    3 (E) - 4 (B)
    A/C switch ON
    Below 1 Ω
    5 (ILL+) - 6 ILL-)
    Always
    Below 1 Ω

    If the resistance value is not as specified, replace the air outlet mode control switch.

  1. Connect the positive battery terminal to terminal 5, and the negative battery terminal to terminal 6.

    OK:
    The illumination light of the heater control knob comes on.

    If the resistance value is not as specified, replace the air outlet mode control switch.