Home › HEATER & AIR CONDITIONING SYSTEM › AIR CONDITIONING › ROOM TEMPERATURE SENSOR (for Front)

ROOM TEMPERATURE SENSOR (for Front) > INSPECTION

for Preparation Click here



1. INSPECT ROOM TEMPERATURE SENSOR (for Automatic Air Conditioning System)


    E158845E01
  1. Measure the resistance according to the value(s) in the table below.

    Standard resistance:
    Tester Connection
    Condition
    Specified Condition
    D26-1 (+) - D26-2 (-)
    10°C (50°F)
    3.00 to 3.73 kΩ
    D26-1 (+) - D26-2 (-)
    15°C (59°F)
    2.45 to 2.88 kΩ
    D26-1 (+) - D26-2 (-)
    20°C (68°F)
    1.95 to 2.30 kΩ
    D26-1 (+) - D26-2 (-)
    25°C (77°F)
    1.60 to 1.80 kΩ
    D26-1 (+) - D26-2 (-)
    30°C (86°F)
    1.28 to 1.47 kΩ
    D26-1 (+) - D26-2 (-)
    35°C (95°F)
    1.00 to 1.22 kΩ
    D26-1 (+) - D26-2 (-)
    40°C (104°F)
    0.80 to 1.00 kΩ
    D26-1 (+) - D26-2 (-)
    45°C (113°F)
    0.65 to 0.85 kΩ
    D26-1 (+) - D26-2 (-)
    50°C (122°F)
    0.50 to 0.70 kΩ
    D26-1 (+) - D26-2 (-)
    55°C (131°F)
    0.44 to 0.60 kΩ
    D26-1 (+) - D26-2 (-)
    60°C (140°F)
    0.36 to 0.50 kΩ

    NOTICE:
    1. Hold the sensor only by its connector. Touching the sensor may change the resistance value.
    2. When measuring, the sensor temperature must be the same as the ambient temperature.

    HINT:
    As the temperature increases, the resistance decreases (see the graph).

    If the resistance is not as specified, replace the room temperature sensor.



2. INSPECT ROOM TEMPERATURE SENSOR (for Manual Air Conditioning System)


    E117004E17
  1. Measure the resistance according to the value(s) in the table below.

    Standard resistance:
    Tester Connection
    Condition
    Specified Condition
    D26-1 (+) - D26-2 (-)
    10°C (50°F)
    3.00 to 3.73 kΩ
    D26-1 (+) - D26-2 (-)
    15°C (59°F)
    2.45 to 2.88 kΩ
    D26-1 (+) - D26-2 (-)
    20°C (68°F)
    1.95 to 2.30 kΩ
    D26-1 (+) - D26-2 (-)
    25°C (77°F)
    1.60 to 1.80 kΩ
    D26-1 (+) - D26-2 (-)
    30°C (86°F)
    1.28 to 1.47 kΩ
    D26-1 (+) - D26-2 (-)
    35°C (95°F)
    1.00 to 1.22 kΩ
    D26-1 (+) - D26-2 (-)
    40°C (104°F)
    0.80 to 1.00 kΩ
    D26-1 (+) - D26-2 (-)
    45°C (113°F)
    0.65 to 0.85 kΩ
    D26-1 (+) - D26-2 (-)
    50°C (122°F)
    0.50 to 0.70 kΩ
    D26-1 (+) - D26-2 (-)
    55°C (131°F)
    0.44 to 0.60 kΩ
    D26-1 (+) - D26-2 (-)
    60°C (140°F)
    0.36 to 0.50 kΩ

    NOTICE:
    1. Hold the sensor only by its connector. Touching the sensor may change the resistance value.
    2. When measuring, the sensor temperature must be the same as the ambient temperature.

    HINT:
    As the temperature increases, the resistance decreases (see the graph).

    If the resistance is not as specified, replace the room temperature sensor.