Home › HEATER & AIR CONDITIONING SYSTEM › AIR CONDITIONING › SOLAR SENSOR

SOLAR SENSOR > INSPECTION

for Preparation Click here



1. INSPECT SOLAR SENSOR


    E109215E41
  1. Remove the A/C solar sensor with the connector still connected.

  1. Apply battery voltage between terminals 6 (CLTB) and 3 (CLTE) of the A/C solar sensor.

  1. Measure the voltage according to the value(s) in the table below.

    Standard voltage:
    Tester Connection
    Condition
    Specified Condition
    F1-1 (TSL) - F1-3 (CLTE)
    Sensor is subjected to electric light
    0.8 to 4.3 V
    F1-1 (TSL) - F1-3 (CLTE)
    Sensor is covered by a cloth
    Below 0.8 V
    F1-2 (TSR) - F1-3 (CLTE)
    Sensor is subjected to electric light
    0.8 to 4.3 V
    F1-2 (TSR) - F1-3 (CLTE)
    Sensor is covered by a cloth
    Below 0.8 V

    NOTICE:
    1. The connection procedure for using a digital tester such as a TOYOTA electrical tester is shown above. When using an analog tester, connect the positive (+) lead to terminal 2 and negative (-) lead to terminal 1 of the solar sensor.
    2. While using the battery during inspection, do not bring the positive and negative tester probes too close to each other as a short circuit may occur.

    HINT:
    1. Use an incandescent light for inspection. Bring it within about 30 cm (11.8 in.) of the solar sensor.
    2. As the inspection light is moved away from the sensor, the voltage increases.