GENERAL
The air conditioning system has the following controls.
*1: w/ PTC Heater
*2: for 2GR-FKS
NEURAL NETWORK CONTROL
In previous automatic air conditioning systems, the air conditioning amplifier assembly determined the required outlet air temperature and blower air volume in accordance with the calculation formula that has been obtained based on information received from the sensors.
However, because the senses of a person are rather complex, a given temperature is sensed differently, depending on the environment in which the person is situated. For example, a given amount of solar radiation can feel comfortably warm in a cold climate, or extremely uncomfortable in a hot climate. Therefore, as a technique for effecting a higher level of control, a neural network has been adopted in the automatic air conditioning system. With this technique, the data that has been collected under varying environmental conditions is stored in the air conditioning amplifier assembly. The air conditioning amplifier assembly can then effect control to provide enhanced air conditioning comfort.
The neural network control consists of neurons in the input layer, intermediate layer and output layer. The input layer neurons process the input data of the outside temperature, the amount of sunlight and the room temperature based on the outputs of the switches and sensors, and output them to the intermediate layer neurons. Based on this data, the intermediate layer neurons adjust the strength of the links among the neurons. The sum of these is then calculated by the output layer neurons in the form of the required outlet temperature, solar correction, target airflow volume and outlet mode control volume. Accordingly, the air conditioning amplifier assembly controls the servo motors and blower motor in accordance with the control volumes that have been calculated by the neural network control.
MODE POSITION AND DAMPER OPERATION
Mode Position and Damper Operation.
for Front Side
| *a | Air also blows out of the side registers | *b | Air also blows out of the side registers and defrosters |
| Control Damper | Operation Position | Damper Position | Operation |
|---|---|---|---|
| Air Inlet Control Damper | FRESH | A | Allows fresh air to enter. |
| RECIRCULATION | B | Causes internal air to recirculate. | |
| Air Mix Control Damper | MAX COLD to MAX HOT Temperature Setting | C - D | Varies the mixture ratio of warm air and cool air in order to regulate the temperature continuously between hot and cold. |
| Air Outlet Control Damper | DEF
|
E, I | Air blows out of the center defroster, side defrosters and side registers. |
FOOT / DEF
|
E, H | Air blows out of the front footwell register ducts, side registers and center defroster. | |
FOOT
|
E, G | Air blows out of the side registers, front footwell register ducts. In addition, air blows out slightly from the center defroster and side defrosters. | |
BI-LEVEL
|
F, H | Air blows out of the front footwell register ducts, front center registers and side registers. | |
FACE
|
F, I | Air blows out of the front center registers and side registers. |
for Rear Side
| Control Damper | Operation Position | Damper Position | Operation |
|---|---|---|---|
| Air Mix Control Damper | MAX COLD to MAX HOT Temperature Setting | A - B | Varies the mixture ratio of the cold air and hot air in order to regulate the temperature continuously between hot and cold. |
| Air Outlet Control Damper | FACE
|
C | Air blows out of the rear roof side registers. |
BI-LEVEL
|
D | Air blows out of the rear roof side registers and rear footwell register ducts. | |
FOOT
|
E | Air blows out of the rear footwell register ducts. |
AIR OUTLETS AND AIRFLOW VOLUME
Air Outlets and Airflow Volume.
for Front Registers
| Mode | FACE | FOOT | DEF | |
|---|---|---|---|---|
| Center | Side | C | D | |
| A | B | |||
FACE
|
|
|
|
|
B/L
|
|
|
|
|
FOOT
|
|
|
|
|
FOOT/DEF
|
|
|
|
|
DEF
|
|
|
|
|
The size of each circle ○ indicates the ratio of airflow volume.
for Rear Registers
| Mode | ROOF | FOOT |
|---|---|---|
| A | B | |
FACE
|
|
|
B/L
|
|
|
FOOT
|
|
|
The size of each circle ○ indicates the ratio of airflow volume.
COMPRESSOR
General:
The compressor is a continuously variable capacity type in which its capacity can be varied in accordance with the cooling load of the air conditioning system.
The compressor consists of a pulley, shaft, lug plate, swash plate, piston, shoe, crank chamber, cylinder, solenoid valve with built-in crank chamber to suction passage (CS) valve, oil separator and variable suction side throttle.
The cooler compressor assembly has an A/C lock sensor that detects whether the compressor is locked.
A solenoid valve is provided to enable the suction pressure to be controlled as desired.
The crank chamber to suction passage (CS) valve, built into the solenoid valve, operates in accordance with the suction pressure.
The oil separator is installed in the refrigerant passage to separate compressor oil from the refrigerant that is discharged. This helps to prevent the compressor oil from flowing into the air conditioning system and reducing cooling effectiveness.
Solenoid Valve Operation:
The crank chamber is connected to the suction passage. A solenoid valve is provided between the suction passage (low pressure) and the discharge passage (high pressure).
The solenoid valve operates under duty cycle control in accordance with the signals from the air conditioning amplifier assembly.
When the solenoid valve closes (solenoid coil is energized), a difference in pressure is created and the pressure in the crank chamber decreases. Then, the pressure that is applied to the right side of the piston becomes greater than the pressure that is applied to the left side of the piston. This compresses the spring and tilts the swash plate. As a result, the piston stroke increases and the discharge capacity also increases.
When the solenoid valve opens (solenoid coil is not energized), the difference in pressure disappears. Then, the pressure that is applied to the left side of the piston becomes the same as the pressure that is applied to the right side of the piston. Thus, the spring elongates and eliminates the tilt of the swash plate. As a result, there is no piston stroke, and the discharge capacity is reduced.
CS Valve Operation:
The CS valve consists of passage A and passage B. If the vehicle is left parked for a long period, refrigerant may accumulate in the crank chamber due to the heat capacity difference.
The solenoid control valve is controlled by the air conditioning amplifier assembly. While the compressor is operating, the solenoid control valve pushes down the CS valve rod and opens passage A.
Under the above condition, only if the refrigerant accumulates in the crank chamber, the crank chamber pressure will become high. As a result, the bellows will contract because of the pressure difference with its internal pressure (vacuum), and opens passage B.
This causes the accumulated refrigerant to be drawn in via passage A and passage B, clearing the accumulated refrigerant earlier and ensuring a more immediate cooling effect.
A/C LOCK SENSOR (for 2GR-FKS)
The A/C lock sensor sends A/C pulley speed signals to the air conditioning amplifier assembly. The air conditioning amplifier assembly determines whether the A/C compressor is locked or not by using those signals and engine speed signals.
NO. 1 COOLER THERMISTOR
The No. 1 cooler thermistor detects the temperature of the cool air immediately after the evaporator in the form of resistance changes, and outputs it to the air conditioning amplifier assembly.
BLOWER MOTOR
for Front Side
The blower motor with fan sub-assembly has a built-in blower controller, and is controlled using duty control performed by the air conditioning amplifier assembly.
for Rear Side
The rear blower motor with fan sub-assembly is controlled using duty control performed by the air conditioning amplifier assembly.
BUS CONNECTOR
Bus connectors are used in the wire harness that connects the servo motors to the air conditioning amplifier assembly.
for Front Side
| *a | Example | *b | Bus Connector
(to Blower Damper Servo Sub-assembly) |
| *c | Bus Connector
(to Mode Damper Servo Sub-assembly) |
*d | Bus Connector
(to Air Mix Damper Servo Sub-assembly) |
| *e | to Air Conditioning Amplifier Assembly | *f | to No. 1 Cooler Thermistor |
for Rear Side
| *a | Example | *b | Bus Connector
(to Rear Mode Damper Servo Sub-assembly) |
| *c | Bus Connector
(to Rear Air Mix Damper Servo Sub-assembly) |
*d | to Air Conditioning Amplifier Assembly |
| *e | Rear Evaporator Temperature Sensor | - | - |
Each bus connector has a built-in communication/driver IC which communicates with the air conditioning amplifier assembly, actuates the servo motor, and has a position detection function. This enables bus communication for the servo motor wire harness, for a more lightweight construction and a reduced number of wires.
SERVO MOTOR
A pulse pattern type servo motor consists of a printed circuit board and a servo motor. The printed circuit board has three contact points, and can transmit two ON-OFF signals to the air conditioning amplifier assembly based on the difference of the pulse phases. The bus connector can detect the damper position and movement direction with these signals.
QUICK HEATER ASSEMBLY (w/ PTC Heater)
General
The quick heater assembly is located above the heater core in the air conditioning radiator assembly.
The quick heater assembly consists of a PTC element, aluminum fins, and brass plates. When current is applied to the PTC element, it generates heat to warm the air that passes through the unit.
| *1 | Quick Heater Assembly | *2 | Brass Plate |
| *3 | PTC Element | *4 | Aluminum Fin |
Quick Heater Assembly Operating Conditions
The quick heater assembly is turned on and off by the air conditioning amplifier assembly in accordance with the engine coolant temperature, ambient temperature, temperature setting, and electrical load (generator power ratio).
COOLER (ROOM TEMP. SENSOR) THERMISTOR
The cooler (room temp. sensor) thermistor detects the cabin temperature based on changes in the resistance of its built-in thermistor and sends a signal to the air conditioning amplifier assembly.
THERMISTOR ASSEMBLY
The thermistor assembly detects the outside temperature based on changes in the resistance of its built-in thermistor and sends a signal to the air conditioning amplifier assembly.
AUTOMATIC LIGHT CONTROL SENSOR
The automatic light control sensor detects (in the form of changes in the current that flows through the built-in photo diode) the changes in the amount of sunlight and outputs these sunlight strength signals to the air conditioning amplifier assembly.
AIR CONDITIONER TUBE AND ACCESSORY ASSEMBLY
The air conditioner tube and accessory assembly detects the refrigerant pressure and outputs it to the air conditioning amplifier assembly in the form of voltage changes.
COOLER (NO. 2 ROOM TEMP. SENSOR) THERMISTOR
The cooler (No. 2 room temp. sensor) thermistor detects the rear cabin temperature based on changes in the resistance of its built-in thermistor and sends a signal to the air conditioning amplifier assembly.