Home › Engine / Hybrid System › 2GR-FKS (COOLING) › THERMOSTAT
RM37A0E _51 Engine / Hybrid System _086855 2GR-FKS COOLING _0419160 THERMOSTAT G

2GR-FKS COOLING  THERMOSTAT  INSPECTION  


PROCEDURE

Hide 16031 1.INSPECT WATER INLET WITH THERMOSTAT SUB-ASSEMBLY

a.

Check the valve opening.

HINT:
A368732

The valve opening temperature is inscribed on the water inlet with thermostat sub-assembly.


i.
A380422C01
1,0.5 1.333,0.5 1.333,0.5 1.417,0.719 false 1.177,1.729 1.594,1.729 false 0.833,0.427 1.146,0.583 0.313,0.156 10 false *a 1.635,1.646 1.948,1.802 0.313,0.156 10 false *b
*a Inlet Pipe Side
*b Valve Side


Add 15 cc (0.9 cu. in.) of water to the water inlet with thermostat sub-assembly from the inlet pipe side.


ii.

Confirm that water does not flow out from the valve side of the water inlet with thermostat sub-assembly.

If water flows out from the valve side of the water inlet with thermostat sub-assembly, replace the water inlet with thermostat sub-assembly with a new one.


iii.
A380424C01
2.083,0.667 2.417,0.667 2.417,0.667 2.5,0.938 false 0.917,0.917 1.083,0.917 1.083,0.917 1.146,1.188 false 1.906,0.573 2.219,0.729 0.313,0.156 10 false *b 0.74,0.833 1.052,0.99 0.313,0.156 10 false *a
*a Connector
*b Inlet Pipe
V100144

Temperature Sensor


Immerse the water inlet with thermostat sub-assembly in water that is between 92°C (198°F) and 96°C (205°F) for 5 minutes or more.

NOTICE:
·

Do not allow any water to come into contact with the connector of the water inlet with thermostat sub-assembly.

·

Make sure that the end of the inlet pipe of the water inlet with thermostat sub-assembly is not facing downward.

·

Make sure to immerse the water inlet with thermostat sub-assembly in the water as shown in the illustration.




iv.
A380426C01
1.917,0.75 2.333,0.75 2.333,0.75 2.396,1.073 false 1.75,0.656 2.063,0.813 0.313,0.156 10 false *a
*a Inlet Pipe


Leave the water inlet with thermostat sub-assembly at ambient temperature for 5 minutes so that the valve closes.

NOTICE:

Make sure that the end of the inlet pipe of the water inlet with thermostat sub-assembly is not facing downward.



v.

Check that the water that was added to the water inlet with thermostat sub-assembly has completely flowed out.

If the water that was added to the water inlet with thermostat sub-assembly has not completely flowed out, replace the water inlet with thermostat sub-assembly with a new one.



b.

Check the resistance of the temperature sensor.

i.

Measure the resistance according to the value(s) in the table below.

Standard Resistance:
Tester Connection Condition Specified Condition
1 - 2 Always 10.6 to 14.2 Ω


If the result is not as specified, replace the water inlet with thermostat sub-assembly.