The blower motor with fan sub-assembly is operated by signals from the air conditioning amplifier assembly.
If the airflow volume is low or the blower speed cannot be changed, the following factors may be the cause.
| Symptom | Factor |
|---|---|
| Airflow volume cannot be changed | ·
Air conditioning amplifier assembly malfunction ·
Blower motor with fan sub-assembly malfunction ·
Harness or connector |
Inspect the fuses for circuits related to this system before performing the following procedure.
Perform the Active Test according to the display on the GTS.
| Tester Display | Measurement Item | Control Range | Diagnostic Note |
|---|---|---|---|
| Blower Motor | Blower motor with fan sub-assembly | Min.: 0
Max.: 31 |
- |
| Tester Display |
|---|
| Blower Motor |
| Result | Proceed to |
|---|---|
| Blower motor with fan sub-assembly does not operate | A |
| Blower motor with fan sub-assembly operates but does not change speed | B |
A
B
| *a | Rear view of wire harness connector
(to Blower Motor with Fan Sub-assembly) |
Disconnect the A25 blower motor with fan sub-assembly connector.
Measure the resistance according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| A25-1 (GND) - Body ground | Always | Below 1 Ω |
Measure the voltage according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| A25-3 (+B) - Body ground | Ignition switch off | 11 to 14 V |
| Proceed to |
|---|
| OK |
| NG |
OK
NG
Disconnect the H62 air conditioning amplifier assembly connector.
Disconnect the A25 blower motor with fan sub-assembly connector.
Measure the resistance according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| H62-21 (BLW) - A25-2 (SI) | Always | Below 1 Ω |
| H62-21 (BLW) or A25-2 (SI) - Other terminals and body ground | Always | 10 kΩ or higher |
| Proceed to |
|---|
| OK |
| NG |
OK
NG
Connect the A25 blower motor with fan sub-assembly connector.
| *a | Front view of wire harness connector
(to Air Conditioning Amplifier Assembly) |
Disconnect the H62 air conditioning amplifier assembly connector.
Measure the voltage according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| H62-21 (BLW) - Body ground | Always | 4.75 to 5.25 V |
| Proceed to |
|---|
| OK |
| NG |
OK
NG
Connect the H62 air conditioning amplifier assembly connector.
Using an oscilloscope, check the waveform.
| *a | Component with harness connected
(Air Conditioning Amplifier Assembly) |
- | - |
| Item | Content |
|---|---|
| Terminal No. | H62-21 (BLW) - H62-17 (GND) |
| Tool Setting | 2 V/DIV., 1 ms./DIV. |
| Condition | ·
Ignition switch ON ·
Blower speed: LO |
Waveform is similar to that shown in the illustration.
The waveform varies with the blower speed.
| Proceed to |
|---|
| OK |
| NG |
OK
NG