DATA LIST
Using the GTS to read the Data List allows the values or states of switches, sensors, actuators and other items to be read without removing any parts. This non-intrusive inspection can be very useful because intermittent conditions or signals may be discovered before parts or wiring is disturbed. Reading the Data List information early in troubleshooting is one way to save diagnostic time.
In the table below, the values listed under "Normal Condition" are reference values. Do not depend solely on these reference values when deciding whether a part is faulty or not.
Connect the GTS to the DLC3.
Turn the ignition switch to ON.
Turn the GTS on.
Enter the following menus: Body Electrical / Air Conditioner / Data List.
Check the value(s) by referring to the table below.
| Tester Display | Measurement Item | Range | Normal Condition | Diagnostic Note |
|---|---|---|---|---|
| Room Temperature Sensor | Cooler thermistor (room temperature sensor) | Min.: -6.50°C (-20.30°F)
Max.: 57.25°C (135.05°F) |
Actual ambient temperature displayed | Cooler thermistor (room temperature sensor) system malfunction:
·
When open circuit: -6.50°C (-20.30°F) ·
When short circuit: 57.25°C (135.05°F) |
| Ambient Temp Sensor | Thermistor assembly (ambient temperature sensor) | Min.: -23.30°C (-9.94°F)
Max.: 65.95°C (150.71°F) |
Actual ambient temperature displayed | Thermistor assembly (ambient temperature sensor) system malfunction:
·
When open circuit: -23.30°C (-9.94°F) ·
When short circuit: 65.95°C (150.71°F) |
| Adjusted Ambient Temp | Adjusted ambient temperature | Min.: -30.80°C (-23.44°F)
Max.: 50.80°C (123.44°F) |
- | Air conditioning amplifier assembly malfunction |
| Evaporator Fin Thermistor | No. 1 cooler thermistor (evaporator temperature sensor) | Min.: -29.70°C (-21.46°F)
Max.: 59.55°C (139.19°F) |
Actual evaporator temperature displayed | No. 1 cooler thermistor (evaporator temperature sensor) system malfunction:
·
When open circuit: -29.70°C (-21.46°F) ·
When short circuit: 59.55°C (139.19°F) |
| Evaporator Target Temp | Evaporator target temperature | Min.: -327.68°C (-557.82°F)
Max.: 327.67°C (621.81°F) |
Evaporator target temperature displayed | No. 1 cooler thermistor (evaporator temperature sensor) system malfunction:
·
When open circuit: -327.68°C (-557.82°F) ·
When short circuit: 327.67°C (621.81°F) |
| Solar Sensor (D Side) | Cooler thermistor (solar sensor) | 0 to 255 | Cooler thermistor (solar sensor) value increases as brightness increases | Cooler thermistor (solar sensor) malfunction:
·
When open circuit: 0 ·
When short circuit: 255 |
| Engine Coolant Temp | Engine coolant temperature sensor | Min.: 1.30°C (34.34°F)
Max.: 90.55°C (194.99°F) |
Actual engine coolant temperature displayed | ·
ECD system malfunction ·
SFI system malfunction ·
CAN communication system malfunction |
| Blower Motor Speed Level | Blower motor speed level | Min.: 0
Max.: 31 |
Displayed speed level increases in range between 0 and 31 as blower motor speed increases | Blower with fan motor sub-assembly system malfunction |
| Air Mix Servo Targ Pulse(D) | No. 1 air conditioning radiator damper servo sub-assembly (front side air mix) target pulse | Min.: 128
Max.: 383 |
for LHD:
MAX. COLD: 257 (pulse) MAX. HOT: 165 (pulse) for RHD:
MAX. COLD: 255 (pulse) MAX. HOT: 347 (pulse) |
·
Displayed between 165 and 257 pulse (for LHD) ·
Displayed between 255 and 347 pulse (for RHD) ·
No. 1 air conditioning radiator damper servo sub-assembly (front side air mix) system malfunction |
| Air Mix Servo Actual Pulse(D) | No. 1 air conditioning radiator damper servo sub-assembly (front side air mix) actual pulse | Min.: 128
Max.: 383 |
for LHD:
MAX. COLD: 257 (pulse) MAX. HOT: 165 (pulse) for RHD:
MAX. COLD: 255 (pulse) MAX. HOT: 347 (pulse) |
·
Displayed between 165 and 257 pulse (for LHD) ·
Displayed between 255 and 347 pulse (for RHD) ·
No. 1 air conditioning radiator damper servo sub-assembly (front side air mix) system malfunction |
| Air Outlet Servo Pulse (D) | No. 1 air conditioning radiator damper servo sub-assembly (front mode) target pulse | Min.: 128
Max.: 383 |
for LHD:
FACE: 257 (pulse) FACE1: 257 (pulse) FACE2: 257 (pulse) B/L: 223 (pulse) B/L2: 223 (pulse) FOOT-R: 195 (pulse) FOOT-M: 195 (pulse) FOOT: 195 (pulse) FOOT-D: 189 (pulse) FOOT-0: 195 (pulse) FOOT F: 195 (pulse) F/D: 175 (pulse) DEF: 143 (pulse) for RHD:
FACE: 255 (pulse) FACE1: 255 (pulse) FACE2: 255 (pulse) B/L: 271 (pulse) B/L2: 271 (pulse) FOOT-R: 299 (pulse) FOOT-M: 299 (pulse) FOOT: 299 (pulse) FOOT-D: 307 (pulse) FOOT-0: 299 (pulse) FOOT F: 317 (pulse) F/D: 337 (pulse) DEF: 369 (pulse) |
·
Displayed between 143 and 257 pulse (for LHD) ·
Displayed between 255 and 369 pulse (for RHD) ·
No. 1 air conditioning radiator damper servo sub-assembly (front mode) system malfunction |
| Air Outlet Servo Actu Pulse(D) | No. 1 air conditioning radiator damper servo sub-assembly (front mode) actual pulse | Min.: 128
Max.: 383 |
for LHD:
FACE: 257 (pulse) FACE1: 257 (pulse) FACE2: 257 (pulse) B/L: 223 (pulse) B/L2: 223 (pulse) FOOT-R: 195 (pulse) FOOT-M: 195 (pulse) FOOT: 195 (pulse) FOOT-D: 189 (pulse) FOOT-0: 195 (pulse) FOOT F: 195 (pulse) F/D: 175 (pulse) DEF: 143 (pulse) for RHD:
FACE: 255 (pulse) FACE1: 255 (pulse) FACE2: 255 (pulse) B/L: 271 (pulse) B/L2: 271 (pulse) FOOT-R: 299 (pulse) FOOT-M: 299 (pulse) FOOT: 299 (pulse) FOOT-D: 307 (pulse) FOOT-0: 299 (pulse) FOOT F: 317 (pulse) F/D: 337 (pulse) DEF: 369 (pulse) |
·
Displayed between 143 and 257 pulse (for LHD) ·
Displayed between 255 and 369 pulse (for RHD) ·
No. 1 air conditioning radiator damper servo sub-assembly (front mode) system malfunction |
| Air Inlet Damper Targ Pulse | No. 1 blower damper servo sub-assembly (recirculation) target pulse | Min.: 128
Max.: 383 |
Recirculation: 258 (pulse)
Fresh: 235 (pulse) |
No. 1 blower damper servo sub-assembly (recirculation) system malfunction |
| Air Inlet Damper Actual Pulse | No. 1 blower damper servo sub-assembly (recirculation) actual pulse | Min.: 128
Max.: 383 |
Recirculation: 274 (pulse)
Fresh: 306 (pulse) |
No. 1 blower damper servo sub-assembly (recirculation) system malfunction |
| Electric Heater Count | Maximum PTC heater operation level | Min.: 0
Max.: 3 |
Maximum possible operation of PTC heater displayed | w/ PTC Heater |
| Electric Heater Active Level | Number of electric heaters operating | Min.: 0
Max.: 3 |
Actual operation level of PTC heater displayed | w/ PTC Heater |
| Shift Set Temperature | Shift set temperature | 2C decr, 1C decr, Normal, 1C incr, 2C incr | Customized value displayed | - |
| Air Inlet Mode | Air inlet mode | Auto or Manual | Customized value displayed | - |
| Evaporator Control | Evaporator control | Auto or Manual | Customized value displayed | - |
| Fan speed increment control | Fan speed increment control | Slow, Normal, Fast | Customized value displayed | - |
| Foot/DEF Auto Mode | Foot/DEF Auto Mode | ON or OFF | Customized value displayed | - |
| Foot/DEF Auto Blow Up | Foot/DEF Auto blower speed increase | ON or OFF | Customized value displayed | - |
| IDLE UP/PWR HEAT Switch | Idle up switch | ON or OFF | ON: Idle up switch on
OFF: Idle up switch off |
w/ PTC Heater |
| Refrigerant Gas Type | Refrigerant gas type | R134a or 1234yf | Refrigerant gas type displayed | - |
| Set Temperature (D Side) | Front side set temperature | Min.: MAX COLD
Max.: MAX HOT |
Front side set temperature displayed | ·
LIN communication system malfunction ·
Air conditioning control assembly system malfunction |
| Outside Air Mode Auto Switch Function | Switches ON/OFF the function to switch the suction opening to the outside air mode automatically when the ignition switch is turned off | OFF or ON | Customized value displayed | - |
| Number of Trouble Codes | Number of trouble codes | Min.: 0
Max.: 255 |
Number of DTCs displayed | - |
Enter the following menus: Powertrain / Engine and ECT / Data List.
Check the value(s) by referring to the table below.
| Tester Display | Measurement Item | Range | Normal Condition | Diagnostic Note |
|---|---|---|---|---|
| A/C Signal | Magnet clutch ON request signal | ON or OFF | ON: "A/C" switch on
OFF: "A/C" switch off |
Operate with the engine idling and the blower switch on (LO level). |
ACTIVE TEST
Using the GTS to perform Active Tests allows relays, VSVs, actuators and other items to be operated without removing any parts. This non-intrusive functional inspection can be very useful because intermittent operation may be discovered before parts or wiring is disturbed. Performing Active Tests early in troubleshooting is one way to save diagnostic time. Data List information can be displayed while performing Active Tests.
Connect the GTS to the DLC3.
Turn the ignition switch to ON.
Turn the GTS on.
Enter the following menus: Body Electrical / Air Conditioner / Active Test.
Check the operation by referring to the table below.
| Tester Display | Measurement Item | Control Range | Diagnostic Note |
|---|---|---|---|
| Blower Motor | Blower with fan motor sub-assembly | Min.: 0
Max.: 31 |
- |
| Magnetic Clutch Relay | Magnet clutch relay | OFF/ON | Operates with the engine started and the vehicle stopped |
| Air Mix Servo Targ Pulse(D) | No. 1 air conditioning radiator damper servo sub-assembly (front side air mix) target pulse | Min.: 128
Max.: 383 |
·
Operates between 165 and 257 pulses (for LHD) ·
Operates between 255 and 347 pulses (for RHD) |
| Air Outlet Servo Pulse (D) | No. 1 air conditioning radiator damper servo sub-assembly (front mode) pulse | Min.: 128
Max.: 383 |
·
Operates between 143 and 257 pulses (for LHD) ·
Operates between 255 to 369 pulses (for RHD) |
| Air Inlet Damper Targ Pulse | No. 1 blower damper servo sub-assembly (recirculation) target pulse | Min.: 128
Max.: 383 |
Operates between 235 and 258 pulses |