CONSTRUCTION
In the sub-cool cycle, after the refrigerant passes through the condensing portion of the condenser assembly, both the liquid refrigerant and the gaseous refrigerant that could not be liquefied are cooled again in the super-cooling portion. Thus, the refrigerant is sent to the No. 1 cooler evaporator sub-assembly in an almost completely liquefied state.
| *1 | Condensing Portion | *2 | Super-cooling Portion |
| *3 | Modulator | - | - |
|
Gaseous Refrigerant |
|
Liquid Refrigerant |
The point at which the air bubbles disappear in the refrigerant of the sub-cool cycle is lower than the proper amount of refrigerant with which the system must be filled. Therefore, if the system is refilled with refrigerant based on the point at which the air bubbles disappear, the amount of refrigerant would be insufficient. As a result, the cooling performance of the system will be affected. If the system is overfilled with refrigerant, this will also lead to reduced performance. For the proper method of verifying the amount of the refrigerant and to refill the system with refrigerant, refer to the corresponding Repair Manual for this model.