HEATING / AIR CONDITIONING  REFRIGERANT(for HFO-1234yf(R1234yf))  ON-VEHICLE INSPECTION  


PROCEDURE

Hide 1.INSPECT REFRIGERANT VOLUME

a.
E198800E04
1.25,0.396 1.438,0.396 1.438,0.396 1.625,0.969 true 1.031,0.313 1.25,0.5 0.219,0.188 10 true *1

w/ Sight Glass:

Check the sight glass on the air conditioning tube assembly.

Text in Illustration
*1 Sight Glass

Test conditions:

·

Temperature at the air inlet is 30 to 35°C (86 to 95°F).

·

Engine is running at 1500 rpm.

·

Blower speed control switch is at HI.

·

A/C switch is on.

·

Temperature control switch is at the MAX. COOL position.


·

Doors are fully open.


Item Symptom Amount of Refrigerant Corrective Procedures
1 Bubbles visible Insufficient* (1) Check for gas leakage and repair if necessary
(2) Add refrigerant until bubbles disappear
2 No bubbles visible Empty, insufficient or too much Refer to items 3 and 4
3 No temperature difference between compressor inlet and outlet Empty or nearly empty (1) Check for gas leakage with halogen leak detector and repair if necessary
(2) Add refrigerant until bubbles disappear
4 Considerable temperature difference between compressor inlet and outlet Correct or too much Refer to items 5 and 6
5 Immediately after A/C is off, refrigerant becomes clear Too much (1) Drain or discharge refrigerant
(2) Bleed air and supply proper amount of purified refrigerant
6 Immediately after A/C is off, refrigerant foams and then becomes clear Correct -

HINT:

*: If the ambient temperature is higher than usual but cooling is sufficient, bubbles in the sight glass are permissible.



Hide 2.INSPECT REFRIGERANT PRESSURE

a.

This method uses a refrigerant recovery unit set to locate problem areas. Read the refrigerant pressure when the test conditions are established.

Test conditions:

·

Temperature at the air inlet with the air recirculation switch set at RECIRC is 30 to 35°C (86 to 95°F).

·

Engine is running at 1500 rpm.

·

All doors are fully open.

·

Blower speed control switch is set to HI.

·

A/C switch is on.


Gauge readings (Reference):

E225088E11
4.771,2.688 5.052,2.969 5.052,2.969 5.198,2.969 false 4.479,2.094 4.156,1.771 4.156,1.771 4.063,1.771 false 3.219,2.958 3.219,2.406 3.219,2.406 3.073,2.406 false 3.5,3.292 3.5,3.094 3.5,3.094 3.333,3.094 false 1.146,0.323 1.375,0.531 0.229,0.208 10 false *a 6.438,3.99 6.635,4.177 0.198,0.188 10 false *d 0.594,0.656 1.833,0.865 1.24,0.208 10 false MPa (kgf/cm2, psi) 5.906,4.438 7.125,4.646 1.219,0.208 10 false MPa (kgf/cm2, psi) 0.438,1.406 1.542,1.573 1.104,0.167 8 false 0.5 (5.0, 72) 0.438,2.063 1.24,2.26 0.802,0.198 8 false 0.4 (4.0, 58) 0.438,2.708 1.208,2.906 0.771,0.198 8 false 0.3 (3.0, 43) 0.448,3.365 1.219,3.563 0.771,0.198 8 false 0.2 (2.0, 29) 1.167,3.281 1.917,3.448 0.75,0.167 8 false 0.2 (2.0, 29) 1.406,4.448 2.083,4.646 0.677,0.198 8 false 0.5 (5.0, 72) 2.563,4.458 3.354,4.656 0.792,0.198 8 false 1.0 (10.1, 145) 1.167,2.802 1.969,3 0.802,0.198 8 false 0.27 (2.7, 39) 1.167,3.135 1.948,3.302 0.781,0.167 8 false 0.22 (2.2, 31) 1.302,3.896 2.438,4.094 1.135,0.198 8 false 0.14 (1.4, 20) 3.615,3.906 5,4.104 1.385,0.198 8 false 1.32 (13.4, 191) 2.844,3.521 3.698,3.688 0.854,0.167 8 true 1.25 (12.7, 181) 2.552,3.021 3.344,3.198 0.792,0.177 8 false 1.2 (12.2, 174) 2.219,2.333 3.208,2.531 0.99,0.198 8 false 1.06 (10.8, 153) 3.792,4.458 4.583,4.656 0.792,0.198 8 false 1.5 (15.2, 217) 5.031,4.458 5.802,4.656 0.771,0.198 8 false 2.0 (20.3, 290) 3.854,1.677 4.063,1.885 0.208,0.208 10 false *b 5.208,2.875 5.406,3.073 0.198,0.198 10 false *c

Text in Illustration
*a Pressure on low-pressure side *b Blower HI Zone
*c Blower LO Zone *d Pressure on high-pressure side

i.
E247052E01
0.203,0.105 0.402,0.315 0.199,0.210 10 *a 1.944,0.105 2.142,0.315 0.199,0.210 10 *b

Normally functioning refrigeration system.

Gauge Reading:
Pressure Side Refrigerant Volume
Low 0.15 to 0.25 MPa (1.5 to 2.5 kgf/cm2)
High 1.37 to 1.57 MPa (14 to 16 kgf/cm2)



ii.

The A/C system periodically changes between normal and improper function due to moisture in the refrigerant system.

E247053E01
1.372,0.043 1.625,0.269 0.253,0.225 10 *a 3.908,0.043 4.161,0.269 0.253,0.225 10 *b

Text in Illustration
*a Low Pressure Side *b High Pressure Side

Symptom Probable Cause Diagnosis Corrective Action
During operation, pressure on low pressure side cycles between normal and vacuum Moisture in refrigeration system freezes at expansion valve orifice, causing temporary stop of cycle. However, when melted, normal state is restored.
·

Dryer is overly saturated


·

Moisture in refrigeration system freezes at expansion valve orifice and blocks refrigerant circulation


1.

Replace cooler dryer

2.

Remove moisture from cycle by repeatedly evacuating air

3.

Supply appropriate volume of new refrigerant




iii.

The A/C system does not function effectively due to insufficient refrigerant.

E247054E01
1.372,0.043 1.625,0.269 0.253,0.225 10 *a 3.908,0.043 4.161,0.269 0.253,0.225 10 *b

Text in Illustration
*a Low Pressure Side *b High Pressure Side

Symptom Probable Cause Diagnosis Corrective Action
·

Pressure low on both low and high pressure sides

·

Cooling performance insufficient


Gas leakage from refrigeration system
·

Insufficient refrigerant

·

Refrigerant leakage


1.

Check for gas leakage and repair if necessary

2.

Supply appropriate volume of new refrigerant

3.

If indicated pressure value close to 0 with gauge connected, create vacuum after inspecting and repairing location of leakage




iv.

The A/C system does not function effectively due to poor circulation of the refrigerant.

E247055E01
1.372,0.043 1.625,0.269 0.253,0.225 10 *a 3.908,0.043 4.161,0.269 0.253,0.225 10 *b

Text in Illustration
*a Low Pressure Side *b High Pressure Side

Symptom Probable Cause Diagnosis Corrective Action
·

Pressure low on both low and high pressure sides

·

Frost exists on piping from condenser to A/C unit


Refrigerant flow obstructed by dirt in condenser Condenser clogged Replace condenser


v.

The A/C system does not function or functions intermittently because the refrigerant does not circulate.

E247055E01
1.372,0.043 1.625,0.269 0.253,0.225 10 *a 3.908,0.043 4.161,0.269 0.253,0.225 10 *b

Text in Illustration
*a Low Pressure Side *b High Pressure Side

Symptom Probable Cause Diagnosis Corrective Action
·

Vacuum indicated on low pressure side, and extremely low pressure indicated on high pressure side

·

Frost or condensation seen on piping on both sides of condenser or expansion valve


·

Refrigerant flow obstructed by moisture or dirt in refrigeration system

·

Refrigerant flow obstructed by gas leakage from expansion valve


Refrigerant does not circulate
1.

Check expansion valve refrigerant

2.

Clean expansion valve using compressed air

3.

Replace condenser

4.

Evacuate air and charge system with appropriate volume of new refrigerant

5.

For gas leakage from expansion valve, replace expansion valve




vi.

The A/C system does not function effectively due to the system being overcharged with refrigerant or insufficient cooling of the condenser.

E247056E01
1.372,0.043 1.625,0.269 0.253,0.225 10 *a 3.908,0.043 4.161,0.269 0.253,0.225 10 *b

Text in Illustration
*a Low Pressure Side *b High Pressure Side

Symptom Probable Cause Diagnosis Corrective Action
Pressure extremely high on both low and high-pressure sides
·

Excessive refrigerant

·

Cooling performance of condenser insufficient


·

Condenser is dirty

·

Condenser fan motor is malfunctioning

·

Excessive refrigerant


1.

Clean condenser

2.

Check condenser fan motor operation

3.

If actions taken in 1 and 2 do not solve problem, check amount of refrigerant and adjust amount of refrigerant to appropriate amount




vii.

The A/C system does not function due to air in the refrigeration system.

CAUTION:

The low-pressure piping may be very hot and cause serious burns.


NOTICE:

These gauge indications occur when the refrigeration system opens and the system is charged with refrigerant without vacuum purging.


E247057E01
1.372,0.043 1.625,0.269 0.253,0.225 10 *a 3.908,0.043 4.161,0.269 0.253,0.225 10 *b

Text in Illustration
*a Low Pressure Side *b High Pressure Side

Symptom Probable Cause Diagnosis Corrective Action
·

Pressure extremely high on both low and high-pressure sides

·

Low-pressure piping is too hot to touch


Air in refrigeration system
·

Air in refrigeration system

·

Vacuum purging insufficient


1.

Check if compressor oil is dirty or insufficient

2.

Evacuate air and charge system with new refrigerant




viii.

The A/C system does not function effectively due to an expansion valve malfunction.

E247057E01
1.372,0.043 1.625,0.269 0.253,0.225 10 *a 3.908,0.043 4.161,0.269 0.253,0.225 10 *b

Text in Illustration
*a Low Pressure Side *b High Pressure Side

Symptom Probable Cause Diagnosis Corrective Action
·

Pressure extremely high on both low and high-pressure sides

·

Frost or condensation on piping on low-pressure side


Problem with expansion valve
·

Excessive refrigerant in low pressure piping

·

Expansion valve open too widely


Replace expansion valve


ix.

The A/C system does not function due to a defective compressor.

E247058E01
1.372,0.043 1.625,0.269 0.253,0.225 10 *a 3.908,0.043 4.161,0.269 0.253,0.225 10 *b

Text in Illustration
*a Low Pressure Side *b High Pressure Side

Symptom Probable Cause Diagnosis Corrective Action
·

Pressure extremely high on both low and high-pressure sides

·

Pressure extremely low on high pressure side


Internal leakage in compressor
·

Compression failure

·

Leakage from damaged valve or broken sliding parts


Repair or replace compressor