DTC    B1412    Ambient Temperature Sensor Circuit

for Preparation Click here


DESCRIPTION

The ambient temperature sensor is installed in the front part of the condenser to detect the ambient temperature and control the heater and air conditioner "AUTO" function. The sensor connected to the ECM detects fluctuation in the ambient temperature that is used for controlling the room temperature. The sensor sends a signal to the air conditioning amplifier via the ECM. The resistance of the ambient temperature sensor changes in accordance with the ambient temperature. As the temperature decreases, the resistance increases. As the temperature increases, the resistance decreases.
The ECM applies voltage (5 V) to the ambient temperature sensor and reads voltage changes as the resistance of the ambient temperature sensor changes. The ECM sends the read signal to the air conditioning amplifier via CAN and body multiplex communications.

DTC No.
Detection Condition
Trouble Area
B1412
Open or short in ambient temperature sensor circuit
  1. Ambient temperature sensor
  2. Wire harness between ambient temperature sensor and ECM
  3. ECM
  4. Multiplex communication circuit
  5. Air conditioning amplifier

WIRING DIAGRAM


E125206E01


INSPECTION PROCEDURE

1.READ VALUE OF TECHSTREAM
  1. Connect Techstream to DLC3.

  1. Turn the power switch ON (IG) and turn Techstream ON.

  1. Select the item below in the Data List, and read the display on Techstream.

    Air conditioning amplifier 
    Item
    Measurement Item / Display (Range)
    Normal Condition
    Diagnostic Note
    Ambient Temp Sensor
    Ambient temperature sensor /
    min.: -23.3°C (-9.94°F)
    max.: 65.95°C (150.71°F)
    Actual ambient temperature is displayed
    Open in the circuit: -23.3°C (-9.94°F)
    Short: in the circuit: 65.95°C (150.71°F)

    OK:
    The display is as specified in the normal condition.


    Result 
    Result
    Proceed to
    NG
    A
    OK (Checking from the PROBLEM SYMPTOMS TABLE)
    B
    OK (Checking from the DTC)
    C



B
PROCEED TO NEXT CIRCUIT INSPECTION SHOWN IN PROBLEM SYMPTOMS TABLE

C
REPLACE AIR CONDITIONING AMPLIFIER
A


2.CHECK ECM (TAM VOLTAGE)

I036365E01

  1. Remove the ECM with connectors still connected.

  1. Measure the voltage of the wire harness side connectors.

    Standard voltage:
    Tester Connection
    Condition
    Specified Condition
    E7-21 (TAM) - E4-28 (E2)
    Power switch ON (IG) at 25°C (77°F)
    1.8 to 2.2 V
    E7-21 (TAM) - E4-28 (E2)
    Power switch ON (IG) at 40°C (104°F)
    1.2 to 1.6 V

    HINT:
    As the temperature increases, the voltage decreases.

    Result 
    Result
    Proceed to
    NG
    A
    OK (Checking from the PROBLEM SYMPTOMS TABLE)
    B
    OK (Checking from the DTC)
    C



B
PROCEED TO NEXT CIRCUIT INSPECTION SHOWN IN PROBLEM SYMPTOMS TABLE

C
REPLACE AIR CONDITIONING AMPLIFIER
A


3.INSPECT AMBIENT TEMPERATURE SENSOR
E114516E12
  1. Remove the ambient temperature sensor.

  1. Measure the resistance of the sensor.

    Standard resistance:
    Tester Connection
    Condition
    Specified Condition
    1 - 2
    10°C (50°F)
    3.00 to 3.73 kΩ
    1 - 2
    15°C (59°F)
    2.45 to 2.88 kΩ
    1 - 2
    20°C (68°F)
    1.95 to 2.30 kΩ
    1 - 2
    25°C (77°F)
    1.60 to 1.80 kΩ
    1 - 2
    30°C (86°F)
    1.28 to 1.47 kΩ
    1 - 2
    35°C (95°F)
    1.00 to 1.22 kΩ
    1 - 2
    40°C (104°F)
    0.80 to 1.00 kΩ
    1 - 2
    45°C (113°F)
    0.65 to 0.85 kΩ
    1 - 2
    50°C (122°F)
    0.50 to 0.70 kΩ
    1 - 2
    55°C (131°F)
    0.44 to 0.60 kΩ
    1 - 2
    60°C (140°F)
    0.36 to 0.50 kΩ

    NOTICE:
    1. Even slightly touching the sensor may change the resistance value. Be sure to hold the connector of the sensor.
    2. When measuring, the sensor temperature must be the same as the ambient temperature.

    HINT:
    As the temperature increases, the resistance decreases (see the graph).



NG
REPLACE AMBIENT TEMPERATURE SENSOR
OK


4.CHECK WIRE HARNESS (AMBIENT TEMPERATURE SENSOR - ECM)


    I036366E01
  1. Disconnect the A6 sensor connector.

  1. Disconnect the E4 and E7 ECM connectors.

  1. Measure the resistance of the wire harness side connectors.

    Standard resistance:
    Tester Connection
    Specified Condition
    E7-21 (TAM) - A6-2
    Below 1 Ω
    E4-28 (E2) - A6-1
    Below 1 Ω
    E7-21 (TAM) - Body ground
    10 kΩ or higher
    E4-28 (E2) - Body ground
    10 kΩ or higher



NG
REPAIR OR REPLACE HARNESS AND CONNECTOR
OK

REPLACE AIR CONDITIONING AMPLIFIER