Home › Vehicle Interior › HEATING / AIR CONDITIONING › AIR CONDITIONING SYSTEM › from 2020.08
NM2070E _58 Vehicle Interior _061892 HEATING / AIR CONDITIONING _0301438 AIR CONDITIONING SYSTEM UN GENERAL/CONTROL/DETAILS F

HEATING / AIR CONDITIONING  AIR CONDITIONING SYSTEM  GENERAL/CONTROL/DETAILS  DETAILS  


SYSTEM CONTROL


a.

Control List

i.

The air conditioning system uses the following types of control.

Control Outline
Neural Network Control This control is capable of effecting complex control by artificially simulating the information processing method of the nervous system of living organisms in order to establish a complex input/output relationship that is similar to a human brain.
Outlet Air Temperature Control In compliance with the temperature set at the temperature control switch, the neural network control calculates the outlet temperature based on the input signals from various sensors. In addition, corrections in accordance with the signals from the evaporative temperature sensor and E.F.I. engine coolant temperature sensor are added to control the outlet air temperature.
Blower Control Controls the blower with fan motor sub-assembly in accordance with the airflow volume that has been calculated by the neural network control based on the input signals from various sensors.
Air Outlet Control Automatically switches the outlets in accordance with the outlet mode ratio that has been calculated by the neural network control based on the input signals from various sensors.
Micro Dust and Pollen Filter Mode Control Activated by the micro dust and pollen filter mode switch operation. Switches the air vent to the FACE mode. Sends air which has passed through the clean air filter (air refiner element) to the area around the upper part of the bodies of the driver and front passenger. This air is filtered by the clean air filter (air refiner element) in order to remove pollen.
Air Inlet Control Automatically controls the blower damper servo sub-assembly (recirculation/refresh) in accordance with the outlet temperature that has been calculated by the neural network control.
Compressor Speed Control The air conditioning amplifier assembly calculates the target speed of the compressor based on the target evaporator temperature (which is calculated by the temperature control switch, cooler (room temperature sensor) thermistor, outside temperature sensor (thermistor assembly), and solar sensor (automatic light control sensor)) and the actual evaporator temperature that is detected by the evaporator temperature sensor (cooler thermistor No. 1) in order to control the compressor speed.
The air conditioning amplifier assembly calculates the target evaporator temperature, which includes corrections based on the temperature control switch, cooler (room temperature sensor) thermistor, outside temperature sensor (thermistor assembly), solar sensor (automatic light control sensor), and evaporator temperature sensor (cooler thermistor No. 1). Accordingly, the air conditioning amplifier assembly controls the compressor speed to an extent that would not inhibit the proper cooling performance or defogging performance.
Engine Water Pump Assembly Control The air conditioning amplifier assembly calculates the flow rate value required for the electric engine water pump assembly in accordance with the engine coolant temperature and air mix control damper opening degree and sends it to the ECM.
Eco Drive Mode Control When the ECO mode switch is turned on, the air conditioning amplifier assembly limits the air conditioning system performance.
Rear Window Defogger & Mirror Heater Control When the power switch is turned on (IG), and the rear window defogger switch is pushed, this system is activated to keep the defogger heater on for approximately 15 minutes.



b.

Neural Network Control

i.

Previously, in automatic air conditioning systems without neural network control, the air conditioning amplifier assembly determined the required outlet air temperature and blower air volume in accordance with the calculation formula that was obtained based on information received from the sensors. However, because the senses of a person are rather complex, a given temperature is sensed differently, depending on the environment in which the person is situated. For example, a given amount of solar radiation can feel comfortably warm in a cold climate, or extremely uncomfortable in a hot climate. Therefore, as a technique for performing a higher level of control, a neural network has been adopted in the automatic air conditioning system. With this technique, the data that has been collected under varying environmental conditions is stored in the air conditioning amplifier assembly. The air conditioning amplifier assembly can then perform control in a way that provides enhanced air conditioning comfort.


ii.

The neural network control consists of neurons in the input layer, intermediate layer and output layer. The input layer neurons process the input data of the outside temperature, the amount of sunlight, and the room temperature based on the outputs of the switches and sensors, and output them to the intermediate layer neurons. Based on this data, the intermediate layer neurons adjust the strength of the links among the neurons. The sum of these is then calculated by the output layer neurons in the form of the required outlet temperature, solar correction, target airflow volume and outlet mode control volume. Accordingly, the air conditioning amplifier assembly controls the servo motors and blower motor in accordance with the control volumes that have been calculated by neural network control.

Y109700E04
2.302,4.052 3.302,4.281 1,0.229 10 false Neural Network 0.271,4.563 1.344,4.792 1.073,0.229 10 false Input Processing 0.25,5.729 1.063,6.094 0.813,0.365 10 false Temperature Setting 0.302,7.01 1.156,7.25 0.854,0.24 10 false Sensor Input 0.271,8.094 1.135,8.323 0.865,0.229 10 false Switch Input 1.01,8.99 3.219,9.208 2.208,0.219 10 false : Neural Network Operation Range 2.292,5.438 3.5,5.781 1.208,0.344 10 false Amount of Sunlight Correction 3.906,4.281 5.208,4.635 1.302,0.354 10 false Temperature Control Correction 5.729,2.063 6.906,2.26 1.177,0.198 10 false Output Processing 5.792,2.698 6.823,3.51 1.031,0.813 10 false Air Conditioning Damper Servo Sub-assembly No. 1 (Air Mix) 5.771,8.781 6.854,9.177 1.083,0.396 10 false Compressor with Motor Assembly 5.917,4.271 6.792,4.51 0.875,0.24 10 false Blower Motor 3.833,5.5 5.344,5.875 1.51,0.375 10 false Various Types of Airflow Volume Corrections 3.865,6.906 5.323,7.292 1.458,0.385 10 false Various Types of Mode Corrections 3.896,7.688 5,8.073 1.104,0.385 10 false Various Types of Corrections 2.323,6.229 3.208,6.573 0.885,0.344 10 false Target Airflow Volume 2.354,7.052 3.198,7.24 0.844,0.188 10 false Outlet Mode 2.365,7.802 3.104,8 0.74,0.198 10 false Inlet Mode 2.354,8.333 3.208,8.542 0.854,0.208 10 false Compressor 2.323,4.635 3.188,5.01 0.865,0.375 10 false Target Outlet Temperature 2.365,3.646 2.917,3.854 0.552,0.208 10 false Control 2.958,0.229 4.177,0.594 1.219,0.365 10 false Intermediate Layer 2.052,0.604 2.854,0.969 0.802,0.365 10 false Input Layer 4.333,0.604 5.323,0.969 0.99,0.365 10 false Output Layer 1.063,1.083 2.479,1.427 1.417,0.344 10 false Ambient Temperature 1.167,1.802 2.427,2.135 1.26,0.333 10 false Amount of Sunlight 1.167,2.5 2.427,2.833 1.26,0.333 10 false Cabin Temperature 4.708,1.094 6.615,1.479 1.906,0.385 10 false Target Output Temperature 5.823,4.917 6.813,5.76 0.99,0.844 10 false Air Conditioning Damper Servo Sub-assembly No. 2 (Mode) 5.802,6.49 6.833,7.594 1.031,1.104 10 false Blower Damper Servo Sub-assembly No. 1 (Recirculation / Refresh)



c.

Compressor Speed Control

i.

The air conditioning amplifier assembly calculates the target compressor speed based on the target evaporator temperature (calculated from the temperature control switch, cooler (room temperature sensor) thermistor, outside temperature sensor (thermistor assembly), and solar sensor (automatic light control sensor)) and the actual evaporator temperature detected by the evaporator temperature sensor (cooler thermistor No. 1). Then, the air conditioning amplifier assembly transmits the target speed to the hybrid vehicle control ECU. The hybrid vehicle control ECU controls the air conditioning inverter based on the target speed data in order to control the compressor with motor assembly to a speed that suits the operating condition of the air conditioning system.


ii.

The air conditioning amplifier assembly calculates the target evaporator temperature, which includes corrections based on the temperature control switch, cooler (room temperature sensor) thermistor, outside temperature sensor (thermistor assembly), solar sensor (automatic light control sensor), and evaporator temperature sensor (cooler thermistor No. 1). Accordingly, the air conditioning amplifier assembly controls the compressor speed to an extent that does not inhibit the proper cooling performance or defogging performance. As a result, comfort and low fuel consumption can be realized.


iii.

The compressor with motor assembly is supplied with high-voltage direct current, and it uses high-voltage alternating current internally. If an open or short circuit occurs in the compressor with motor assembly, the hybrid vehicle control ECU will cut off the air conditioning inverter circuit.

Y110464E05
0.354,4.833 1.813,5.417 1.458,0.583 10 false Compressor with Motor Assembly 0.583,5.552 1.594,6.125 1.01,0.573 10 false Air Conditioning Inverter 2.292,1.927 4.26,2.313 1.969,0.385 10 false Evaporator Temperature Sensor (Cooler Thermistor No. 1) 2.302,2.813 4.208,3.208 1.906,0.396 10 false Solar Sensor (Automatic Light Control Sensor) 2.427,1.01 4.115,1.396 1.688,0.385 10 false Cooler (Room Temperature Sensor) Thermistor 2.344,3.635 4.156,4.052 1.813,0.417 10 false Outside Temperature Sensor (Thermistor Assembly) 4.333,4.917 5.208,5.125 0.875,0.208 10 false CAN (V Bus) 2.74,4.854 3.906,5.417 1.167,0.563 10 false Hybrid Vehicle Control ECU Assembly 2.385,0.406 4.198,0.76 1.813,0.354 10 false Temperature Control Switch 5.646,0.573 6.688,1.25 1.042,0.677 10 false Air Conditioning Amplifier Assembly 4.104,5.5 5.292,6.167 1.188,0.667 10 false Target Compressor Speed 5.448,2.271 6.771,3.719 1.323,1.448 10 false Calculates the target compressor speed in accordance with various input conditions. 2.052,5.427 2.552,5.885 0.5,0.458 10 false Inverter Control



d.

Micro Dust and Pollen Filter Mode Control

i.

When the micro dust and pollen filter switch is pressed, the micro dust and pollen filter mode control is activated. Then, the air vent is switched to the FACE mode and recirculated pollen free air flows in the area around the upper part of the bodies of the driver and front passenger.


ii.

When the micro dust and pollen filter switch signal is received by the air conditioning amplifier assembly, the air conditioning amplifier assembly controls the compressor with motor assembly, blower damper servo sub-assembly (recirculation/refresh), air conditioning radiator damper servo sub-assembly No. 2 (mode) and blower motor as shown in the timing chart below.


iii.

This control usually operates for approximately 3 minutes. However, when the outside temperature is low, it will operate for approximately 1 minute.


iv.

After this control stops operating, the air conditioning amplifier assembly controls the air conditioning system using AUTO mode.

Y103418E26
3.583,1.167 3.583,0.396 3.583,0.396 3.74,0.396 true 5.563,1.156 5.563,0.448 5.563,0.448 5.729,0.448 true 3.781,0.26 5.208,0.667 1.427,0.406 10 false Micro Dust and Pollen Filter Mode 5.781,0.323 6.573,0.531 0.792,0.208 10 false Auto Mode 1.313,1.354 2.146,1.635 0.833,0.281 10 false Recirculation 0.208,1.563 0.75,1.781 0.542,0.219 10 false Air Inlet 0.208,2.458 0.813,2.708 0.604,0.25 10 false Air Vent 0.208,3.563 0.76,3.823 0.552,0.26 10 false Blower 0.208,4.719 1.083,4.958 0.875,0.24 10 false Compressor 0.167,0.302 2.042,0.604 1.875,0.302 12 false Timing Chart (Sample): 1.615,3.635 2.135,3.958 0.521,0.323 10 false Medium 5.979,5.469 6.76,5.688 0.781,0.219 10 false Time (min.) 2.833,5.427 3.229,5.688 0.396,0.26 10 false Start 3.646,5.417 3.813,5.604 0.167,0.188 10 false 1 4.344,5.417 4.521,5.604 0.177,0.188 10 false 2 5,5.427 5.177,5.615 0.177,0.188 10 false 3 1.75,1.708 2.135,2.031 0.385,0.323 10 false Fresh 1.771,2.271 2.135,2.583 0.365,0.313 10 false Face 1.823,2.698 2.146,3 0.323,0.302 10 false Foot 1.969,3.177 2.135,3.469 0.167,0.292 10 false Hi 1.906,4.083 2.135,4.406 0.229,0.323 10 false Off 1.885,4.563 2.146,4.792 0.26,0.229 10 false On* 1.906,4.906 2.135,5.167 0.229,0.26 10 false Off 0.208,5.917 6.76,6.427 6.552,0.51 10 false *: The compressor with motor assembly turns on only when the outside temperature is low. The compressor with motor assembly remains on after micro dust and pollen mode is canceled.



e.

Eco Drive Mode Control

i.

During eco drive mode control, the air conditioning amplifier assembly restricts the air conditioning system performance under specified conditions, thus improving fuel economy.


ii.

Eco drive mode control is activated when the ECO mode switch is pressed, and then restricts the air conditioning system performance as described below.

Control Outline
Inside/Outside Air Switch Control Automatically switches the air inlet port to recirculation mode when the outside air temperature is equal to or higher than a predetermined temperature and reduces the power consumption.
Blower Level Control Sets the blower level in AUTO mode lower than normal, and suppresses the power consumption.
Heating Restriction Control Changes the air outlet temperature by entering eco drive mode during heating and increases the amount of engine-off time when the drive mode is in ECO, thus improving fuel economy.
Compressor Speed Restriction Control Restricts the maximum compressor speed during cooling and reduces the power consumption.




CONSTRUCTION


a.

Air Conditioning Control Assembly

i.

The push button and dial type air conditioning control assembly makes it possible to easily operate 3 functions using a single dial: air outlet mode control, temperature setting adjustment and fan speed adjustment.


ii.

The function currently selected (mode, temperature or fan speed) can be changed to a different function by sliding the dial to either side. The selected function can then be controlled by turning the dial.

Y120460E01
1.134,4.072 1.290,4.254 0.156,0.181 10 *a 3.465,4.072 3.621,4.254 0.156,0.181 10 *b 5.759,4.072 5.914,4.254 0.156,0.181 10 *c 0.397,2.769 0.553,2.950 0.156,0.181 10 *1

Text in Illustration
*1 Air Conditioning Control Assembly - -
*a Air Outlet Mode Control *b Temperature Setting Adjustment
*c Fan Speed Adjustment - -



b.

Air Conditioning Radiator Assembly

i.

A semi-center location air conditioning radiator assembly is used, in which the cooler evaporator sub-assembly No. 1 and heater radiator unit sub-assembly are mounted horizontally.

Y107191E03
2.979,1.146 2.469,0.25 2.469,0.25 2.25,0.25 true 2.854,2.5 1.792,2.5 true 2.063,0.156 2.26,0.365 0.198,0.208 10 false *1 1.563,2.396 1.76,2.604 0.198,0.208 10 false *2

Text in Illustration
*1 Heater Radiator Unit Sub-assembly *2 Cooler Evaporator Sub-assembly No. 1


ii.

A partial recirculation system is used. This system has an air inlet control door (sub) in the cabin side of the air inlet duct. Thus, it is able to cycle a small volume of recirculated air even in the FRESH mode, thus ensuring heating and air conditioning performance. When the blower switch is on, the suction force of the blower fan opens this air inlet control door (sub).

Y107192E04
5.708,0.313 5.438,0.313 5.438,0.313 5.438,1.01 true 6.417,1.417 6.156,1.417 6.156,1.417 6.156,2.104 true 3.583,0.427 3.313,0.427 3.313,0.427 3.313,1.365 true 5.729,0.188 5.948,0.375 0.219,0.188 10 false *1 6.448,1.302 6.719,1.552 0.271,0.25 10 false *2 4.844,0.792 5.063,0.979 0.219,0.188 10 false *a 6.083,0.99 6.302,1.177 0.219,0.188 10 false *b 6.667,2.021 6.885,2.208 0.219,0.188 10 false *b 5.479,3.167 5.698,3.354 0.219,0.188 10 false *c 3.604,0.313 3.823,0.5 0.219,0.188 10 false *1

Text in Illustration
*1 Air Inlet Control Door *2 Air Inlet Control Door (Sub)
*a Fresh Air *b Recirculated Air
*c To Blower Fan - -



c.

Cooler Evaporator Sub-assembly No. 1

i.

The Ejector Cycle System (ECS) type cooler evaporator sub-assembly No. 1 is used.


ii.

By placing the tanks at the top and the bottom of the evaporator unit and adopting a micropore tube construction, the following effects have been realized:

·

The heat exchanging efficiency has been improved.

·

The temperature distribution has been made more uniform.

·

The evaporator has been made thinner.



iii.

The ejector is provided in the top tank of the cooler evaporator sub-assembly No. 1.

Y110465E03
2.542,1.885 2.063,1.885 true 2.896,2.177 2.063,2.177 true 3.031,1.063 2.833,0.552 2.833,0.552 2.365,0.552 true 4.208,2.865 4.208,3.219 true 2.146,0.448 2.385,0.667 0.24,0.219 10 false *1 4.146,3.229 4.49,3.479 0.344,0.25 10 false *2 1.875,1.771 2.135,1.969 0.26,0.198 10 false *3 1.875,2.073 2.135,2.25 0.26,0.177 10 false *4

Text in Illustration
*1 Top Tank (Built-in Ejector) *2 Bottom Tank
*3 Upwind Side *4 Downwind Side



d.

Evaporator Temperature Sensor (Cooler Thermistor No. 1)

i.

The evaporator temperature sensor (cooler thermistor No. 1) detects the temperature of the cooled air immediately past the evaporator in the form of resistance changes, and outputs this data to the air conditioning amplifier assembly.



e.

Blower with Fan Motor Sub-assembly

i.

The blower with fan motor sub-assembly has a built-in blower controller, and is controlled using duty control from the air conditioning amplifier assembly.



f.

Heater Radiator Unit Sub-assembly

i.

The compact, lightweight and highly efficient Straight Flow Aluminum (SFA)-II type heater radiator unit sub-assembly is used for the air conditioning system.



g.

Bus Connector

i.

A bus connector is used in the wire harness connection that connects the servo motor from the air conditioning amplifier assembly.

Y120484E02
1.854,0.854 2.073,0.854 2.073,0.854 2.396,1.177 true 0.896,2.01 0.896,1.813 true 0.906,4.188 0.906,3.99 true 3.5,4.396 3.5,4.198 true 0.823,5.354 0.823,5.156 true 3.573,1.021 3.573,0.823 true 6.135,1.031 6.135,0.833 true 1.823,4.281 1.948,4.281 1.948,4.281 2.208,4.604 true 0.146,0.083 0.313,0.26 0.167,0.177 10 false *A 0.146,3.354 0.313,3.531 0.167,0.177 10 false *B 0.813,2.031 1.01,2.208 0.198,0.177 10 false *1 1.948,2.958 2.104,3.135 0.156,0.177 10 false *b 6.135,1.896 6.354,2.115 0.219,0.219 10 false *a 1.625,0.74 1.865,0.938 0.24,0.198 10 false *2 1.948,6.396 2.167,6.594 0.219,0.198 10 false *b 6.135,5.333 6.396,5.521 0.26,0.188 10 false *a 1.625,4.156 1.781,4.333 0.156,0.177 10 false *2 0.823,4.219 1.031,4.417 0.208,0.198 10 false *1 3.427,4.406 3.656,4.604 0.229,0.198 10 false *1 0.74,5.365 0.948,5.573 0.208,0.208 10 false *1 3.49,1.031 3.698,1.229 0.208,0.198 10 false *1 6.063,1.052 6.281,1.24 0.219,0.188 10 false *1

Text in Illustration
*A LHD Models *B RHD Models
*1 Bus Connector *2 Air Conditioning Harness Assembly
*a To Air Conditioning Amplifier Assembly *b To Evaporator Temperature Sensor (Cooler Thermistor No. 1)


ii.

The bus connector has a built-in driver IC with a position detection function that communicates with each servo motor connector and actuates the servo motor. This enables bus communication for the servo motor wire harness with a more lightweight construction and a reduced number of wires.

Y103434E27
4.427,1.073 4.427,0.635 4.427,0.635 4.26,0.635 true 4.521,1.208 4.521,0.646 4.521,0.646 4.75,0.646 true 0.51,0.469 0.802,0.75 0.292,0.281 10 false *A 1.635,0.844 1.927,1.01 0.292,0.167 10 false *1 1.635,1.292 1.885,1.5 0.25,0.208 10 false *5 1.635,1.792 1.865,1.969 0.229,0.177 10 false *6 4.083,0.531 4.375,0.813 0.292,0.281 10 false *2 4.76,0.531 5.052,0.813 0.292,0.281 10 false *3 5.958,1.76 6.167,1.948 0.208,0.188 10 false *4 0.521,3.042 0.813,3.323 0.292,0.281 10 false *B 1.604,3.396 1.823,3.594 0.219,0.198 10 false *1 2.042,3.875 2.302,4.083 0.26,0.208 10 false *7 2.042,4.813 2.271,5.021 0.229,0.208 10 false *7 1.083,4.333 1.313,4.542 0.229,0.208 10 false *6 5.823,4.323 6.042,4.521 0.219,0.198 10 false *4

Text in Illustration
*A Models with Bus Connector *B Models without Bus Connector
*1 Air Conditioning Amplifier Assembly *2 Bus Connector
*3 Communication Driver IC *4 Servo Motor
*5 Communication IC *6 CPU
*7 Driver IC - -



h.

Servo Motor

i.

In contrast to the previous type that detects the position by way of a potentiometer voltage, the pulse pattern type servomotor detects the relative position by way of the 2-bit on/off signals.


ii.

The forward and reverse revolutions of this motor are detected by way of 2 phases, A and B, which output 4 types of patterns. The air conditioning amplifier assembly counts the number of pulse patterns in order to determine the stopped position.

Y100716E34
3.99,2.375 3.719,2.375 3.719,2.375 3.5,2.771 true 3.094,1.896 2.792,1.896 2.792,1.896 2.875,2.875 false 3.938,2.875 4.396,2.875 true 4.104,3.135 4.271,3.344 4.271,3.344 4.417,3.344 true 3.271,4.604 3.417,4.365 3.417,4.365 3.542,4.365 true 2.208,0.542 2.042,0.542 2.042,0.542 1.781,1.125 true 0.156,0.802 0.74,1.052 0.583,0.25 10 false Phase B 0.156,1.156 0.729,1.406 0.573,0.25 10 false Phase A 0.156,1.479 0.792,1.729 0.635,0.25 10 false Common 2.26,0.417 3.625,0.635 1.365,0.219 10 false Printed Circuit Board 2.26,1.406 3.219,1.604 0.958,0.198 10 false Pattern Width 4.927,0.927 5.677,1.104 0.75,0.177 10 false Phase A: + 4.677,1.344 5.677,1.521 1,0.177 10 false Common: GND 4.938,1.76 5.677,1.938 0.74,0.177 10 false Phase B: + 4.021,2.26 6.75,2.479 2.729,0.219 10 false Rotation Direction of Printed Circuit Board 3.125,1.813 4.406,2.031 1.281,0.219 10 false Fixed Contact Point 4.427,2.792 5.729,2.99 1.302,0.198 10 false Printed Circuit Board 4.438,3.24 4.948,3.427 0.51,0.188 10 false Pattern 3.594,4.25 4.948,4.479 1.354,0.229 10 false Pattern Width 2.81° 2.177,4.073 2.781,4.271 0.604,0.198 10 false Phase B 2.01,3.271 2.781,3.469 0.771,0.198 10 false Pattern No. 2.177,3.594 2.781,3.792 0.604,0.198 10 false Phase A 2.854,3.229 2.99,3.458 0.135,0.229 10 false 1 3.01,3.229 3.146,3.458 0.135,0.229 10 false 2 3.198,3.229 3.333,3.458 0.135,0.229 10 false 3 3.375,3.229 3.51,3.458 0.135,0.229 10 false 4 3.552,3.229 3.688,3.458 0.135,0.229 10 false 1 3.729,3.229 3.865,3.458 0.135,0.229 10 false 2 3.906,3.229 4.042,3.458 0.135,0.229 10 false 3 4.083,3.229 4.219,3.458 0.135,0.229 10 false 4 2.833,3.646 2.969,3.875 0.135,0.229 10 false 1 3.01,3.646 3.146,3.875 0.135,0.229 10 false 1 3.198,3.635 3.333,3.865 0.135,0.229 10 false 0 3.375,3.635 3.51,3.865 0.135,0.229 10 false 0 3.542,3.646 3.677,3.875 0.135,0.229 10 false 1 3.719,3.646 3.854,3.875 0.135,0.229 10 false 1 3.906,3.635 4.042,3.865 0.135,0.229 10 false 0 4.083,3.635 4.219,3.865 0.135,0.229 10 false 0 2.854,3.958 2.99,4.188 0.135,0.229 10 false 0 3.01,3.979 3.146,4.208 0.135,0.229 10 false 1 3.188,3.979 3.323,4.208 0.135,0.229 10 false 1 3.375,3.958 3.51,4.188 0.135,0.229 10 false 0 3.552,3.958 3.688,4.188 0.135,0.229 10 false 0 3.708,3.979 3.844,4.208 0.135,0.229 10 false 1 3.896,3.979 4.031,4.208 0.135,0.229 10 false 1 4.083,3.958 4.219,4.188 0.135,0.229 10 false 0 0.958,2.583 1.708,2.76 0.75,0.177 10 false Phase A: + 0.708,2.979 1.708,3.156 1,0.177 10 false Common: GND 0.979,3.354 1.719,3.531 0.74,0.177 10 false Phase B: +



i.

Clean Air Filter (Air Refiner Element)

i.

A pollen removal type filter is used. This filter is made of polyester and excels in the removal of dust and pollen. Because the filter is made of polyester it can be disposed of easily as a non-hazardous combustible material, a feature provided out of consideration for the environment.

Y122933E02
0.948,0.979 0.875,0.583 0.875,0.583 0.76,0.583 false 0.885,1.583 0.885,2.042 false

Text in Illustration
*1 Clean Air Filter (Air Refiner Element) *2 Large Foreign Object Filter Layer
*3 Electret Layer *4 Air Flow



j.

Condenser with Receiver Assembly

i.

A Multi-Flow (MF) type condenser is used. The condenser with receiver assembly consists of 2 cooling portions: a condensing portion and a super-cooling portion. These portions are integrated with a gas-liquid separator (modulator). This condenser with receiver assembly uses a sub-cool cycle that offers excellent heat-exchange performance.


ii.

In the sub-cool cycle, after the refrigerant passes through the condensing portion of the condenser, both the liquid refrigerant and the gaseous refrigerant that could not be liquefied are cooled again in the super-cooling portion. Thus, the refrigerant is sent to the evaporator in an almost completely liquefied state.

Y103456E05
2.938,1.906 3.198,1.135 3.198,1.135 3.469,1.135 true 3.094,2.729 3.354,3.24 3.354,3.24 3.625,3.24 true 4.802,1.729 5.167,1.01 5.167,1.01 5.542,1.01 true 6,1.646 6.365,1.646 true 5.885,2 6.375,2 true 0.948,2.396 1.156,2.604 0.208,0.208 10 false *1 3.49,1.031 3.698,1.24 0.208,0.208 10 false *2 0.938,2.677 1.146,2.885 0.208,0.208 10 false *7 3.656,3.135 3.865,3.344 0.208,0.208 10 false *6 5.563,0.906 5.771,1.115 0.208,0.208 10 false *3 6.385,1.531 6.594,1.74 0.208,0.208 10 false *4 6.396,1.896 6.604,2.104 0.208,0.208 10 false *5

Text in Illustration
*1 Gaseous Refrigerant *2 Condensing Portion
*3 Modulator *4 Desiccant
*5 Filter *6 Super-cooling Portion
*7 Liquid Refrigerant - -

HINT:

The point at which the air bubbles disappear in the refrigerant of the sub-cool cycle is lower than the proper amount of refrigerant with which the system must be filled. Therefore, if the system is recharged with refrigerant based on the point at which the air bubbles disappear, the amount of refrigerant would be insufficient. As a result, the cooling performance of the system would be affected. Overcharging the system with refrigerant will also lead to reduced performance. For the proper method of verifying the amount of refrigerant and for instructions on how to recharge the system with refrigerant. For details, refer to the Repair Manual.


Y100135E34
2.865,2.01 3.302,2.01 true 2.792,0.927 4.281,1.167 1.49,0.24 10 false Proper Charge Amount 5.073,2.24 6.51,2.469 1.438,0.229 10 false Amount of Refrigerant 1.021,1.292 1.969,1.531 0.948,0.24 10 false High Pressure 3.333,1.906 5.479,2.125 2.146,0.219 10 false Point at which Bubbles Disappear



k.

Compressor with Motor Assembly

i.

Along with the installation of the hybrid system, an ES27 type compressor with motor assembly that is driven by a motor is used. The basic construction and operation of this compressor is the same as an ordinary scroll compressor, except that it is driven by an electric motor.


ii.

The air conditioning inverter is integrated with the compressor with motor assembly.


iii.

The electric motor is actuated by 3-phase alternating current created from the direct current (201.6 V) supplied to the air conditioning inverter. As a result, the air conditioning system is actuated without depending on the operation of the engine, thus realizing a comfortable air conditioning system and low fuel consumption.


iv.

Due to the use of a compressor with motor assembly, the compressor speed can be controlled at the required speed calculated by the air conditioning amplifier assembly. Thus, the cooling and dehumidification performance and power consumption have been optimized.


v.

Low-moisture permeation hoses are used for the suction and discharge hoses at the compressor in order to minimize the entry of moisture into the refrigeration cycle.


vi.

The compressor with motor assembly is supplied with high-voltage direct current, and it uses high-voltage alternating current internally. If an open or short circuit occurs in the compressor with motor assembly, the hybrid vehicle control ECU will cut off the air conditioning inverter circuit.

Y109133E05
4.385,1.021 5.333,1.021 true 4.531,3.51 5.333,3.51 true 2.531,3.021 2.302,2.469 2.302,2.469 2.073,2.469 true 5.365,0.906 5.635,1.094 0.271,0.188 10 false *1 5.365,3.406 5.635,3.594 0.271,0.188 10 false *3 1.854,2.375 2.083,2.573 0.229,0.198 10 false *2

Text in Illustration
*1 Air Conditioning Inverter *2 Discharge Hose Port
*3 Suction Hose Port - -


vii.

The compressor with motor assembly consists of a spirally wound fixed scroll and rotating scroll that form a pair, a brushless motor, an oil separator, a motor shaft and air conditioning inverter.


viii.

The fixed scroll is integrated with the housing. Because the rotation of the shaft causes the rotating scroll to revolve while maintaining the same posture, the volume of the space that is partitioned by both scrolls varies to perform the suction, compression, and the discharge of the refrigerant gas.


ix.

Locating the suction port directly above the scrolls enables direct suction, thus realizing improved suction efficiency.


x.

Containing a built-in oil separator, this compressor is able to separate the compressor oil that is intermixed with the refrigerant and circulates in the refrigeration cycle, thus realizing a reduction in the oil circulation rate.


xi.

This inverter converts the HV battery nominal voltage of DC 201.6 V into AC and supplies power to operate the compressor.

Y109321E06
4.333,0.708 4.458,0.354 4.458,0.354 4.75,0.354 true 4.177,1.698 4.99,1.698 true 4.177,1.906 4.99,1.906 true 3.01,1.208 2.708,0.344 2.708,0.344 2.323,0.344 true 2.708,1.344 2.448,0.583 2.448,0.583 2.281,0.583 true 1.406,1.521 2.198,1.521 true 1.406,1.708 2.688,1.708 true 4.781,0.24 5.031,0.469 0.25,0.229 10 false *1 1.208,1.615 1.458,1.844 0.25,0.229 10 false *2 5.042,1.573 5.292,1.802 0.25,0.229 10 false *3 2.125,0.229 2.375,0.458 0.25,0.229 10 false *4 2.125,0.479 2.375,0.708 0.25,0.229 10 false *5 1.208,1.417 1.458,1.604 0.25,0.188 10 false *6 5.052,1.802 5.302,2.031 0.25,0.229 10 false *7 6.49,3.313 6.74,3.542 0.25,0.229 10 false *8 5.75,3.531 6,3.76 0.25,0.229 10 false *1 5.448,3.854 5.698,4.083 0.25,0.229 10 false *10 2.167,4.75 2.417,4.979 0.25,0.229 10 false *11 0.583,5.938 0.833,6.167 0.25,0.229 10 false *15 4.698,5.01 4.948,5.24 0.25,0.229 10 false *14 5.125,5 5.375,5.229 0.25,0.229 10 false *13 3.438,4.75 3.688,4.979 0.25,0.229 10 false *12 0.458,4.083 0.708,4.313 0.25,0.229 10 false *9 2.281,5.938 2.531,6.167 0.25,0.229 10 false *16 3.427,5.802 3.677,6.031 0.25,0.229 10 false *17 5.052,5.781 5.302,6.01 0.25,0.229 10 false *18 0.958,5.125 1.208,5.354 0.25,0.229 10 false *a

Text in Illustration
*1 Air Conditioning Inverter *2 Discharge Port
*3 Motor Shaft *4 Rotating Scroll
*5 Fixed Scroll *6 Oil Separator
*7 Brushless Motor *8 Compressor with Motor Assembly
*9 HV Battery *10 Current Sensor
*11 Power Supply Circuit *12 Gate Drive Circuit
*13 Temperature Sensor *14 Voltage Sensor
*15 Hybrid Vehicle Control ECU *16 Input/Output Interface
*17 CPU *18 System Protection Control Circuit
*a From Battery - -

NOTICE:

In order to ensure proper insulation of the internal high-voltage portion of the compressor with motor assembly and the compressor housing, this model has adopted compressor oil (ND11) with a high level of insulation performance. Therefore, never use compressor oil other than the ND11 type compressor oil or its equivalent.




l.

Cooler (Room Temperature Sensor) Thermistor

i.

The cooler (room temperature sensor) thermistor detects the room temperature based on changes in the resistance of its built-in thermistor. This signal is used by the air conditioning amplifier assembly.



m.

Outside Temperature Sensor (Thermistor Assembly)

i.

The outside temperature sensor (thermistor assembly) detects the outside temperature based on changes in the resistance of its built-in thermistor. This signal is used by the air conditioning amplifier assembly.



n.

Solar Sensor (Automatic Light Control Sensor)

i.

The solar sensor (automatic light control sensor) consists of a photo diode, amplifier circuit and frequency conversion circuit.


ii.

The solar sensor (automatic light control sensor) detects (in the form of changes in the current that flows through the built-in photo diode) the changes in the amount of sunlight and outputs these sunlight strength signals to the air conditioning amplifier assembly for the automatic air conditioning control.

Y110475E03
1.552,1.563 1.26,2.021 1.26,2.021 0.781,2.021 true 0.271,1.906 0.771,2.333 0.5,0.427 10 false Sensor Portion 2.896,0.24 5.896,0.458 3,0.219 10 false Solar Sensor (Automatic Light Control Sensor) 4.188,0.656 5.177,0.844 0.99,0.188 10 false Photo Diode 3.24,1.24 4.688,1.615 1.448,0.375 10 false Frequency Conversion Circuit 5.313,1.292 6.333,1.552 1.021,0.26 10 false Amplifier Circuit 5.438,3.01 6.656,3.448 1.219,0.438 10 false To Air Conditioning Amplifier Assembly 3.271,3.021 5.125,3.438 1.854,0.417 10 false To Main Body ECU (Multiplex Network Body ECU)



o.

Air Conditioner Pressure Sensor

i.

The air conditioner pressure sensor detects the refrigerant pressure and outputs it to the air conditioning amplifier assembly in the form of voltage changes.




OPERATION


a.

Mode Position and Door Operation

Y110468E04
3.146,2.26 2.99,1.156 2.99,1.156 2.771,1.156 true 2.458,3.219 2.458,3.552 true 1.146,3.125 1.146,4.104 true 0.906,1.708 1.125,1.927 0.219,0.219 10 false B 1.49,1.688 1.708,1.865 0.219,0.177 10 false A 2.719,2.365 2.938,2.583 0.219,0.219 10 false C 3.177,3.063 3.396,3.281 0.219,0.219 10 false D 3.542,3.104 3.708,3.302 0.167,0.198 10 false G 4.542,2.521 4.708,2.719 0.167,0.198 10 false G 4.74,2.823 4.906,3.01 0.167,0.188 10 false F 5.063,2.719 5.229,2.906 0.167,0.188 10 false E 3.594,3.302 3.75,3.5 0.156,0.198 10 false H 4.698,2.406 4.854,2.594 0.156,0.188 10 false H 3.719,3.479 3.844,3.667 0.125,0.188 10 false I 4.802,2.25 4.927,2.438 0.125,0.188 10 false I 3.823,3.573 3.948,3.76 0.125,0.188 10 false J 4.698,1.99 4.854,2.198 0.156,0.208 10 false J 0.656,1.5 1.083,1.688 0.427,0.188 10 false Fresh 1.49,1.5 2.427,1.708 0.938,0.208 10 false Recirculation 1.375,3.542 2.823,3.917 1.448,0.375 10 false Cooler Evaporator Sub-assembly No. 1 3.615,4.125 4.615,4.479 1,0.354 10 false Center Register 2.646,4.115 3.552,4.479 0.906,0.365 10 false Side Register 0.26,4.115 2.479,4.313 2.219,0.198 10 false Blower with Fan Motor Assembly 3.875,0.49 5.021,0.719 1.146,0.229 10 false Center Defroster 5.531,0.688 6.521,0.979 0.99,0.292 10 false Side Defroster 1.49,1.052 2.781,1.417 1.292,0.365 10 false Heater Radiator Unit Sub-assembly 2.406,0.708 3.333,0.927 0.927,0.219 10 false Side Defroster 4.76,4.125 5.667,4.49 0.906,0.365 10 false Side Register 5.323,1.865 6.25,2.26 0.927,0.396 10 false Front Footwell Register Duct 6,2.531 6.896,2.948 0.896,0.417 10 false Rear Footwell Register Duct 5.323,3.073 6.25,3.479 0.927,0.406 10 false Front Footwell Register Duct

Control Damper Operation Position Damper Position Operation
Air Inlet Control Damper FRESH A Brings in fresh air.
RECIRCULATION B Recirculates internal air.
Air Mix Control Damper MAX COLD-MAX HOT C, D Varies the mixture ratio of warm air and cool air in order to regulate the temperature continuously from HOT to COLD.
Mode Control Damper
Y129010

FACE E, J Air blows out of the center registers and side registers.
Y129009

BI-LEVEL F, J Air blows out of the center registers, side registers, and front and rear footwell register ducts.
Y129008

FOOT F, I Air blows out of the front and rear footwell registers ducts and side registers. In addition, air blows out slightly from the front defroster and side defrosters.
Y129007

FOOT/DEF F, H Defrosts the windshield through the center defroster, side defrosters and side registers, while air is also blown out from the front and rear footwell register ducts.
Y129006

DEF E, G Defrosts the windshield through the center defroster, side defrosters and side registers.


b.

Air Outlets and Airflow Volume

Y122175E02
2.625,0.125 2.833,0.333 0.208,0.208 10 false D 1.719,1.229 1.875,1.406 0.156,0.177 10 false E 2.365,1.417 2.521,1.594 0.156,0.177 10 false B 2.448,2.344 2.604,2.521 0.156,0.177 10 false C 3.969,2 4.125,2.177 0.156,0.177 10 false C 4.688,0.385 4.844,0.563 0.156,0.177 10 false E 4.896,1.031 5.052,1.208 0.156,0.177 10 false B 3.979,1.115 4.135,1.292 0.156,0.177 10 false A 4.115,0.875 4.271,1.052 0.156,0.177 10 false A 3.531,1.229 3.688,1.406 0.156,0.177 10 false A 3.792,3.542 3.948,3.719 0.156,0.177 10 false C 5.323,3.104 5.479,3.281 0.156,0.177 10 false C

Indication Mode Face Footwell Defroster
Center Side Front Rear Center Side
A B C C D E
Y129010

FACE
Y129016

Y129016

- - - -
Y129009

BI-LEVEL
Y129013

Y129013

Y129013

Y129013

- -
Y129008

FOOT -
Y129014

Y129016

Y129016

Y129014

Y129014

Y129007

FOOT AND DEFROSTER -
Y129014

Y129013

Y129013

Y129013

Y129013

Y129006

DEFROSTER -
Y129014

- -
Y129016

Y129016


The size of the circle ○ indicates the proportion of airflow volume.


c.

Compressor Operation

i.

Suction Operation

As the capacity of the compression chamber, which is created between the rotating scroll and the fixed scroll increases in accordance with the revolution of the rotating scroll, refrigerant gas is drawn in from the intake port.


ii.

Compression Operation

From the state at which the suction process has been completed, as the revolution of the rotating scroll advances further, the capacity of the compression chamber decreases gradually. Consequently, the refrigerant gas that has been drawn in becomes compressed gradually and is sent to the center of the fixed scroll. The compression of the refrigerant gas is completed when the rotating scroll completes approximately 2 revolutions.


iii.

Discharge Operation

When the compression of the refrigerant gas is completed and the refrigerant pressure becomes high, the refrigerant gas discharges through the discharge port located in the center of the fixed scroll by pushing the discharge valve.

Y101263E14
2.063,0.896 2.292,0.615 2.292,0.615 2.396,0.615 true 1.188,0.625 1.271,0.625 1.271,0.625 1.74,1.208 true 1.177,1.573 1.271,1.573 1.271,1.573 1.542,1.396 true 2.427,1.573 2.344,1.573 2.344,1.573 2.031,1.281 true 5.906,2.802 6.104,3 0.198,0.198 10 false *b 2.208,0.313 2.406,0.51 0.198,0.198 10 false *a 1.021,3.604 1.219,3.802 0.198,0.198 10 false *c 2.448,0.542 2.646,0.74 0.198,0.198 10 false *1 2.448,1.479 2.646,1.677 0.198,0.198 10 false *2 1.01,1.49 1.208,1.688 0.198,0.198 10 false *3 1.021,0.521 1.219,0.719 0.198,0.198 10 false *4

Text in Illustration
*1 Intake Port *2 Fixed Scroll
*3 Rotating Scroll *4 Discharge Port
*a Suction *b Compression
*c Discharge - -



d.

Ejector Cycle System Operation

i.

In the conventional refrigerant cycle, liquid refrigerant gas is sent into the cooler evaporator sub-assembly No. 1 using the cooler expansion valve, generating cold air. However, a rapid decrease in the refrigerant pressure forms swirls, causing energy loss. In this ejector cycle, the energy loss caused by the cooler expansion valve is utilized by the operation of the ejector that injects and expands a high-pressure refrigerant, thus improving energy consumption efficiency.

Y110470E03
1.146,2.469 1.167,2.354 1.167,2.354 1.406,2.354 true 0.167,0.625 1.802,0.823 1.635,0.198 10 false Cooler Expansion Valve 0.375,3.802 1.281,4.01 0.906,0.208 10 false Low-pressure 0.375,1.052 1.406,1.25 1.031,0.198 10 false High-pressure 1.448,2.25 2.729,2.635 1.281,0.385 10 false Energy loss caused by swirls 3.854,3.99 6.292,4.177 2.438,0.188 10 false Cooler Evaporator Sub-assembly No. 1 4.521,2.229 5.979,2.594 1.458,0.365 10 false Compressor with Motor Assembly 3.948,1.344 6.177,1.542 2.229,0.198 10 false Condenser with Receiver Assembly 0.125,0.094 2.635,0.344 2.51,0.25 12 false Conventional Refrigerant Cycle:

Y110471E03
4.042,1.573 4.083,1.906 4.083,1.906 4.219,1.906 true 4.031,1.198 4.073,0.688 4.073,0.688 4.24,0.688 true 0.833,0.583 1.51,0.823 0.677,0.24 12 false Ejector: 1.042,1.156 2.281,1.729 1.24,0.573 10 false Refrigerant from the condenser with receiver assembly 1.635,2.396 5.198,2.76 3.563,0.365 10 false Refrigerant from the cooler evaporator sub-assembly No. 1 at the downwind side 4.26,1.792 6.469,2.125 2.208,0.333 10 false Suction flow generated by decrease in the pressure 4.281,0.542 6.49,0.938 2.208,0.396 10 false Suction flow generated by decrease in the pressure 3.813,3.438 6.021,3.656 2.208,0.219 10 false Condenser with Receiver Assembly 3.323,6.469 6.49,6.688 3.167,0.219 10 false ECS Type Cooler Evaporator Sub-assembly No. 1 3.406,5.656 5.51,6.021 2.104,0.365 10 false Capillary Tube (valve to reduce the refrigerant pressure) 4.365,5.115 5.417,5.333 1.052,0.219 10 false Downwind Side 4.521,4.563 5.406,4.75 0.885,0.188 10 false Upwind Side 0.583,3.552 2.167,3.76 1.583,0.208 10 false Cooler Expansion Valve 0.104,0.115 2.073,0.354 1.969,0.24 12 false Ejector Cycle (EJECS II): 3.865,3.74 6,3.958 2.135,0.219 10 false Compressor with Motor Assembly


ii.

The ejector includes nozzle, mixing and diffuser portions.


iii.

The high temperature and pressure liquid refrigerant from the condenser with receiver assembly is introduced into the mixing section through the nozzle at high speeds because the nozzle is inwardly tapered. This decreases the refrigerant pressure in the vicinity of the nozzle, drawing low temperature and pressure gaseous refrigerant into the nozzle from the cooler evaporator sub-assembly No. 1. Thus, both refrigerants mix in the mixing section and pass into the diffuser section.


iv.

As the diffuser section is outwardly flared, the refrigerant flow rate in the diffuser decreases and the refrigerant pressure rises.


v.

Through these operations, the refrigerant pressure in the cooler evaporator sub-assembly No. 1 on the downwind side can be constantly kept lower than that on the upwind side, creating the lower temperature conditions. Therefore, air cooled by the cooler evaporator sub-assembly on the upwind side can be further cooled by the downwind side, thus improving the efficiency of the cooler evaporator sub-assembly No. 1.

Y110472E03
3.229,2.469 3.052,2.469 3.052,2.469 2.969,3.333 true 5.354,2.417 5.188,2.417 5.188,2.417 5.021,3.177 true 0.146,0.417 1.688,0.833 1.542,0.417 10 false From the condenser with receiver assembly 0.396,1.729 2.083,2.26 1.688,0.531 10 false From the cooler evaporator sub-assembly at the downwind side 1.302,2.656 1.938,3 0.635,0.344 10 false Pressure 1.26,3.802 1.969,4.094 0.708,0.292 10 false Flow Rate 0.219,4.979 4.26,5.313 4.042,0.333 10 false a: Refrigerant flow from the condenser with receiver assembly 2.563,2.833 2.792,3.052 0.229,0.219 10 false a 2.479,4.479 2.708,4.698 0.229,0.219 10 false a 3.667,3.365 3.917,3.531 0.25,0.167 10 false b 3.115,4.49 3.344,4.708 0.229,0.219 10 false b 2.5,1.656 2.979,1.896 0.479,0.24 10 false Nozzle 3.01,1.344 3.979,1.719 0.969,0.375 10 false Mixing Section 3.99,1.656 5,2.01 1.01,0.354 10 false Diffuser Section 3.26,2.323 4.781,2.688 1.521,0.365 10 true Suction due to decrease in pressure 5.083,0.802 6.906,1.365 1.823,0.563 10 false To the cooler evaporator sub-assembly No. 1 at the upwind side 5.406,2.302 6.688,2.719 1.281,0.417 10 false Pressure rise due to decrease in speed 0.219,5.344 5.76,5.635 5.542,0.292 10 false b: Refrigerant flow from the cooler evaporator sub-assembly No. 1 at the downwind side




DIAGNOSIS


a.

The air conditioning amplifier assembly has a diagnosis function. It stores a record of any air conditioning system failures in memory in the form of Diagnostic Trouble Codes (DTCs).


b.

There are 2 methods for reading DTCs. One is to use the Global TechStream (GTS) and the other is to read the DTCs using the air conditioning control assembly. For details, refer to the Repair Manual.