88719A
1.INSPECT AIR CONDITIONING PRESSURE SENSOR
Check the wire harness.
Disconnect the A31 air conditioning pressure sensor connector.
Disconnect the L17 air conditioning amplifier assembly connector.
Measure the resistance according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| A31-1 (-) - L17-13 (SG-2) | Always | Below 1 Ω |
| A31-2 (PR) - L17-9 (PRE) | Always | Below 1 Ω |
| A31-3 (+) - L17-10 (S5-3) | Always | Below 1 Ω |
| A31-1 (-) - Body ground | Always | 10 kΩ or higher |
| A31-2 (PR) - Body ground | Always | 10 kΩ or higher |
| A31-3 (+) - Body ground | Always | 10 kΩ or higher |
Measure the voltage according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| A31-3 (+) - Body ground | Power switch ON | 4.75 to 5.25 V |
| *a | Front view of wire harness connector
(to Air Conditioning Pressure Sensor) |
Check the air conditioning pressure sensor.
Install a manifold gauge set.
Connect the air conditioning pressure sensor connector.
Turn the power switch on (READY).
A/C switch on.
Measure the voltage according to the value(s) in the table below.
Check from the rear of the connector while it is connected to the air conditioning amplifier assembly.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| L17-9 (PRE) - L17-13 (SG-2) | Refrigerant pressure:
3.025 MPa (30.8 kgf/cm2, 439 psi) to 0.167 MPa (1.7 kgf/cm2, 24 psi) |
0.70 to 4.69 V |
| *a | Component with harness connected
(Air Conditioning Amplifier Assembly) |