REFRIGERANT > ON-VEHICLE INSPECTION |
| 1. INSPECT REFRIGERANT VOLUME |
![]() |
Check the sight glass.
Prepare the vehicle according to the chart below.
| Item | Condition |
| Vehicle doors | Fully open |
| Temperature setting | Max cool |
| Ignition switch | ON (READY) |
| Blower speed | High |
| A/C switch | On |
Compare the sight glass to the following chart.
| Item | Symptom | Amount of Refrigerant | Corrective Action |
| 1 | Bubbles exist | Insufficient* |
|
| 2 | No bubbles exist | Empty, insufficient or excessive | Refer to 3 and 4 |
| 3 | No temperature difference between compressor inlet and outlet | Empty or nearly empty |
|
| 4 | Considerable temperature difference between compressor inlet and outlet | Proper or excessive | Refer to 5 and 6 |
| 5 | Immediately after air conditioning is turned off, refrigerant in sight glass remains clear | Excessive |
|
| 6 | Immediately after air conditioning is turned off, refrigerant in sight glass foams and then becomes clear | Proper | - |
| 2. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET |
Read the manifold gauge pressure when the following conditions are met:
![]() |
Normally functioning air conditioning system
| Pressure Side | Refrigerant Volume |
| Low | 150 to 250 kPa (1.5 to 2.5 kgf/cm2, 22 to 36 psi) |
| High | 1370 to 1570 kPa (14.0 to 16.0 kgf/cm2, 199 to 228 psi) |
Abnormally functioning air conditioning system
![]() |
| Symptom | Air conditioning system periodically cools and then fails to cool. |
| Probable Cause | Moisture in air conditioning system freezes at expansion valve orifice, causing refrigerant to temporarily stop circulating |
| After system stops, and warms up again, ice melts and normal operation is temporarily restored | |
| Diagnosis | Cooler dryer (integrated into condenser tank) saturated with moisture |
| Moisture in air conditioning system freezes at expansion valve orifice and blocks circulation of refrigerant | |
| Corrective Actions | Replace cooler dryer |
| Remove moisture by repeatedly evacuating air from air conditioning system | |
| Recharge air conditioning system with proper amount of new or purified refrigerant |
| *a | LO |
| *b | HI |
![]() |
| Symptom | Air conditioning system does not cool effectively. |
| Insufficient cooling performance | |
| Probable Cause | Refrigerant leaks from air conditioning system |
| Diagnosis | Insufficient refrigerant |
| Refrigerant leaking | |
| Corrective Actions | Check for refrigerant leaks and repair if necessary |
| Recharge air conditioning system with proper amount of new or purified refrigerant | |
| If gauges indicate pressure of close to 0, then it is necessary to evacuate air conditioning system after repairing leak |
| *a | LO |
| *b | HI |
![]() |
| Symptom | Air conditioning system does not cool effectively. |
| Frost exists on pipe from condenser to evaporator unit | |
| Probable Cause | Refrigerant flow is obstructed by dirt inside pipes of condenser core |
| Diagnosis | Condenser is clogged |
| Corrective Actions | Replace condenser |
| *a | LO |
| *b | HI |
![]() |
| Symptom | Air conditioning system does not cool effectively. (System may cool occasionally) |
| Frost or condensation is seen on piping on both sides of receiver/ dryer or expansion valve | |
| Probable Cause | Refrigerant flow is obstructed by moisture or dirt in air conditioning system |
| Expansion valve is stuck closed | |
| Diagnosis | Refrigerant does not circulate |
| Corrective Actions | Replace expansion valve |
| Replace condenser | |
| Evacuate air conditioning system and supply proper amount of new or purified refrigerant |
| *a | LO |
| *b | HI |
![]() |
| Symptom | Air conditioning system does not cool effectively. |
| Probable Cause | Unable to develop sufficient performance due to excessive amount of refrigerant |
| Cooling effectiveness of condenser is insufficient | |
| Diagnosis | Excessive amount of refrigerant in air conditioning system because excessive refrigerant was added during recharging |
| Cooling effectiveness of condenser is insufficient because condenser fins are clogged or cooling fan is faulty | |
| Corrective Actions | Clean condenser |
| Check operation of condenser cooling fan | |
| If above two corrective actions are normal, check amount of refrigerant and recharge air conditioning system with proper amount of new or purified refrigerant |
| *a | LO |
| *b | HI |
![]() |
| Symptom | Air conditioning system does not cool. |
| The low pressure piping is too hot to touch | |
| Probable Cause | Air in air conditioning system |
| Diagnosis | Air present in air conditioning system |
| Insufficient vacuum purging when evacuating air conditioning system | |
| Corrective Actions | Replace cooler dryer |
| Check compressor oil to see if it is dirty or insufficient | |
| Evacuate air conditioning system and recharge it with new or purified refrigerant |
| *a | LO |
| *b | HI |
![]() |
| Symptom | Air conditioning system does not cool effectively. |
| Frost or a large amount of condensation on piping on low pressure side | |
| Probable Cause | Expansion valve may be stuck open or metering refrigerant incorrectly |
| Diagnosis | Excessive refrigerant in low pressure piping |
| Expansion valve open too wide | |
| Corrective Actions | Replace expansion valve |
| *a | LO |
| *b | HI |
![]() |
| Symptom | Air conditioning system does not cool effectively. |
| Probable Cause | Internal leak in compressor |
| Diagnosis | Low compression |
| Leak from a damaged valve or other compressor component | |
| Corrective Actions | Replace compressor |
| *a | LO |
| *b | HI |
Gauge readings (Reference)

| *a | Pressure on low pressure side kPa (kgf/cm2, psi) | *b | Pressure on high pressure side kPa (kgf/cm2, psi) |
| *c | Blower high zone | *d | Blower low zone |