REFRIGERANT > ON-VEHICLE INSPECTION

for Preparation Click here



1. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET

HINT:
The following examples show the readings of a manifold gauge set and the corresponding air conditioning system problems.



  1. Read the manifold gauge pressure when the following conditions are met:

    1. Doors are fully open.
    2. The power switch is ON (READY).
    3. The A/C switch is on.
    4. The temperature is set to max cool.
    5. The blower speed is set to high.
    6. Temperature at the air inlet with recirculate selected is 30 to 35°C (86 to 95°F).



      E050573
    1. Normally functioning air conditioning system
      Gauge Reading 
      Pressure Side
      Refrigerant Volume
      Low
      0.15 to 0.25 MPa (1.5 to 2.5 kgf/cm2, 21 to 36 psi)
      High
      1.37 to 1.57 MPa (14 to 16 kgf/cm2, 199 to 228 psi)

    2. Abnormally functioning air conditioning system


      1. E225742E01
        During operation, pressure on low pressure side cycles between normal and vacuum
        Symptom
        Air conditioning system periodically cools and then fails to cool.
        Probable Cause
        Moisture in air conditioning system freezes at expansion valve orifice, causing refrigerant to temporarily stop circulating
        After system stops, and warms up again, ice melts and normal operation is temporarily restored
        Diagnosis
        Cooler dryer (integrated into condenser tank) saturated with moisture
        Moisture in air conditioning system freezes at expansion valve orifice and blocks circulation of refrigerant
        Corrective Actions
        Replace cooler dryer
        Remove moisture by repeatedly evacuating air from air conditioning system
        Recharge air conditioning system with proper amount of new or purified refrigerant
        Text in Illustration 
        *a
        LO
        *b
        HI

        HINT:
        For the example above, moisture is present in the air conditioning system.


      2. E225743E01
        Pressure is low on both low and high pressure sides
        Symptom
        Air conditioning system does not cool effectively.
        Insufficient cooling performance
        Probable Cause
        Refrigerant leaks from air conditioning system
        Diagnosis
        Insufficient refrigerant
        Refrigerant leaking
        Corrective Actions
        Check for refrigerant leaks and repair if necessary
        Recharge air conditioning system with proper amount of new or purified refrigerant
        If gauges indicate pressure of close to 0, then it is necessary to evacuate air conditioning system after repairing leak
        Text in Illustration 
        *a
        LO
        *b
        HI

        HINT:
        For the example above, there is insufficient refrigerant.


      3. E225744E01
        Pressure is low on both low and high pressure sides
        Symptom
        Air conditioning system does not cool effectively.
        Frost exists on pipe from condenser to evaporator unit
        Probable Cause
        Refrigerant flow is obstructed by dirt inside pipes of condenser core
        Diagnosis
        Condenser is clogged
        Corrective Actions
        Replace condenser
        Text in Illustration 
        *a
        LO
        *b
        HI

        HINT:
        For the example above, there is poor circulation of refrigerant.


      4. E225745E01
        Vacuum is indicated on low pressure side and very low pressure is indicated on high pressure side
        Symptom
        Air conditioning system does not cool effectively. (System may cool occasionally)
        Frost or condensation is seen on piping on both sides of receiver/ dryer or expansion valve
        Probable Cause
        Refrigerant flow is obstructed by moisture or dirt in air conditioning system
        Expansion valve is stuck closed
        Diagnosis
        Refrigerant does not circulate
        Corrective Actions
        Replace expansion valve
        Replace condenser
        Evacuate air conditioning system and supply proper amount of new or purified refrigerant
        Text in Illustration 
        *a
        LO
        *b
        HI

        HINT:
        For the example above, the refrigerant does not circulate.


      5. E225746E01
        Pressure is too high on both low and high pressure sides
        Symptom
        Air conditioning system does not cool effectively.
        Probable Cause
        Unable to develop sufficient performance due to excessive amount of refrigerant
        Cooling effectiveness of condenser is insufficient
        Diagnosis
        Excessive amount of refrigerant in air conditioning system because excessive refrigerant was added during recharging
        Cooling effectiveness of condenser is insufficient because condenser fins are clogged or cooling fan is faulty
        Corrective Actions
        Clean condenser
        Check operation of condenser cooling fan
        If above two corrective actions are normal, check amount of refrigerant and recharge air conditioning system with proper amount of new or purified refrigerant
        Text in Illustration 
        *a
        LO
        *b
        HI

        HINT:
        For the example above, the air conditioning system is overcharged or cooling effectiveness of condenser is insufficient.


      6. E225747E01
        Pressure is too high on both low and high pressure sides
        Symptom
        Air conditioning system does not cool.
        The low pressure piping is too hot to touch
        Probable Cause
        Air in air conditioning system
        Diagnosis
        Air present in air conditioning system
        Insufficient vacuum purging when evacuating air conditioning system
        Corrective Actions
        Replace cooler dryer
        Check compressor oil to see if it is dirty or insufficient
        Evacuate air conditioning system and recharge it with new or purified refrigerant
        Text in Illustration 
        *a
        LO
        *b
        HI

        NOTICE:
        These gauge indications occur when the air conditioning system has been left open and then recharged without evacuating the system.

        HINT:
        For the example above, air is present in the air conditioning system.


      7. E225748E01
        Pressure is too high on both low and high pressure sides
        Symptom
        Air conditioning system does not cool effectively.
        Frost or a large amount of condensation on piping on low pressure side
        Probable Cause
        Expansion valve may be stuck open or metering refrigerant incorrectly
        Diagnosis
        Excessive refrigerant in low pressure piping
        Expansion valve open too wide
        Corrective Actions
        Replace expansion valve
        Text in Illustration 
        *a
        LO
        *b
        HI

        HINT:
        For the above example, there is an expansion valve malfunction.


      8. E225749E01
        Pressure is too high on both low and high pressure sides or pressure is too low on high pressure side
        Symptom
        Air conditioning system does not cool effectively.
        Probable Cause
        Internal leak in compressor
        Diagnosis
        Low compression
        Leak from a damaged valve or other compressor component
        Corrective Actions
        Replace compressor
        Text in Illustration 
        *a
        LO
        *b
        HI

        HINT:
        For the above example, there is insufficient compressor compression.



    3. Gauge readings (Reference)


      I030081E45


      Text in Illustration 
      *a
      Pressure on low pressure side MPa ( kgf/cm2, psi)
      *b
      Pressure on high pressure side MPa ( kgf/cm2, psi)
      *c
      Blower high zone
      *d
      Blower low zone