Home › HEATER & AIR CONDITIONING SYSTEM › AIR CONDITIONING › AMBIENT TEMPERATURE SENSOR (for Automatic Air Conditioning System)

AMBIENT TEMPERATURE SENSOR (for Automatic Air Conditioning System) > INSPECTION

for Preparation Click here



1. INSPECT AMBIENT TEMPERATURE SENSOR


E106870E07
  1. Measure the resistance of the sensor.

    Standard resistance:
    Tester Connection
    Condition
    Specified Condition
    1 - 2
    10°C (50°F)
    3.00 to 3.73 kΩ
    1 - 2
    15°C (59°F)
    2.45 to 2.88 kΩ
    1 - 2
    20°C (68°F)
    1.95 to 2.30 kΩ
    1 - 2
    25°C (77°F)
    1.60 to 1.80 kΩ
    1 - 2
    30°C (86°F)
    1.28 to 1.47 kΩ
    1 - 2
    35°C (95°F)
    1.00 to 1.22 kΩ
    1 - 2
    40°C (104°F)
    0.80 to 1.00 kΩ
    1 - 2
    45°C (113°F)
    0.65 to 0.85 kΩ
    1 - 2
    50°C (122°F)
    0.50 to 0.70 kΩ
    1 - 2
    55°C (131°F)
    0.44 to 0.60 kΩ
    1 - 2
    60°C (140°F)
    0.36 to 0.50 kΩ

    NOTICE:
    1. Touching the sensor even slightly may change the resistance value. Hold the connector of the sensor.
    1. When measuring the resistance, the sensor temperature must be the same as the ambient temperature.

    HINT:
    As the temperature increases, the resistance decreases (see the graph).
    If the result is not as specified, replace the ambient temperature sensor.