DTC    B1411/11    Room Temperature Sensor Circuit

for Preparation Click here


DESCRIPTION

The cooler thermistor (front room temperature sensor) is installed in the instrument panel to detect the room temperature and control the heater and air conditioner "AUTO" mode. The resistance of the cooler thermistor (front room temperature sensor) changes in accordance with the room temperature. As the temperature decreases, the resistance increases. As the temperature increases, the resistance decreases.
The air conditioning amplifier assembly applies voltage (5 V) to the cooler thermistor (front room temperature sensor) and reads voltage changes as the resistance of the cooler thermistor (front room temperature sensor) changes. This sensor also sends the appropriate signals to the air conditioning amplifier assembly.

DTC Code
DTC Detection Condition
Trouble Area
B1411/11
An open or short in room temperature sensor circuit.
  1. Cooler thermistor (front room temperature sensor)
  2. Harness or connector between cooler thermistor and air conditioning amplifier assembly
  3. Air conditioning amplifier assembly

WIRING DIAGRAM


E147166E09


INSPECTION PROCEDURE

1.READ VALUE USING INTELLIGENT TESTER (FRONT ROOM TEMPERATURE SENSOR)
  1. Use the Data List to check if the cooler thermistor (room temperature sensor) is functioning properly.

    Air Conditioner 
    Tester Display
    Measurement Item/Range
    Normal Condition
    Diagnostic Note
    Room Temperature Sensor
    Front room temperature sensor /
    Min.: -6.5°C (20.3°F)
    Max.: 57.25°C (135.05°F)
    Actual room temperature is displayed
    Open in the circuit: -6.5°C (20.3°F)
    Short in the circuit: 57.25°C (135.05°F)

    OK:
    The display is as specified in the normal condition.

    Result 
    Result
    Proceed to
    NG
    A
    OK (When troubleshooting according to Problem Symptoms Table)
    B
    OK (When troubleshooting according to the DTC output)
    C



B
PROCEED TO NEXT SUSPECTED AREA SHOWN IN PROBLEM SYMPTOMS TABLE (Click here)

C
REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY (Click here)
A


2.INSPECT COOLER THERMISTOR (FRONT ROOM TEMPERATURE SENSOR)


    E117004E24
  1. Remove the front room temperature sensor (Click here).

  1. Measure the resistance according to the value(s) in the table below.

    Standard Resistance:
    Tester Connection
    Condition
    Specified Condition
    1 - 2
    10°C (50°F)
    3.00 to 3.73 kΩ
    15°C (59°F)
    2.45 to 2.88 kΩ
    20°C (68°F)
    1.95 to 2.30 kΩ
    25°C (77°F)
    1.60 to 1.80 kΩ
    30°C (86°F)
    1.28 to 1.47 kΩ
    35°C (95°F)
    1.00 to 1.22 kΩ
    40°C (104°F)
    0.80 to 1.00 kΩ
    45°C (113°F)
    0.65 to 0.85 kΩ
    50°C (122°F)
    0.50 to 0.70 kΩ
    55°C (131°F)
    0.44 to 0.60 kΩ
    60°C (140°F)
    0.36 to 0.50 kΩ

    HINT:
    As the temperature increases, the resistance decreases (See the graph).

    NOTICE:
    1. Even slightly touching the sensor may change the resistance value. Be sure to hold the connector of the sensor.
    2. When measuring, the sensor temperature must be the same as the ambient temperature.



NG
REPLACE COOLER THERMISTOR (FRONT ROOM TEMPERATURE SENSOR) (Click here)
OK


3.CHECK HARNESS AND CONNECTOR (ROOM TEMPERATURE SENSOR - AIR CONDITIONING AMPLIFIER)


    E127562E04
  1. Disconnect the H16 sensor connector.

  1. Disconnect the H24 amplifier connector.

  1. Measure the resistance according to the value(s) in the table below.

    Standard Resistance:
    Tester Connection
    Condition
    Specified Condition
    H16-1 - H24-29 (TR)
    Always
    Below 1 Ω
    H16-2 - H24-34 (SG-1)
    Always
    Below 1 Ω
    H16-1 or H24-29 (TR) - Body ground
    Always
    10 kΩ or higher
    H16-2 or H24-34 (SG-1) - Body ground
    Always
    10 kΩ or higher



NG
REPAIR OR REPLACE HARNESS OR CONNECTOR
OK

REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY (Click here)