REFRIGERANT > ON-VEHICLE INSPECTION |
| 1. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET |
This is a method to specify trouble areas by using a manifold gauge set. Read the manifold gauge pressure when the following conditions are established.
Test conditions:

![]() |
When the refrigerant volume is proper:
When there is moisture in the refrigeration system:

| Symptoms | Probable Cause | Diagnosis | Corrective Actions |
| During operation, pressure on low pressure side cycles between normal and vacuum | Moisture in refrigeration system freezes at expansion valve orifice, causing temporary stop of cycle. However, when melted, normal state restored |
|
|
When cooling is insufficient:

| Symptoms | Probable Cause | Diagnosis | Corrective Actions |
| Gas leakage from refrigeration system |
|
|
When the circulation of the refrigerant is poor:

| Symptoms | Probable Cause | Diagnosis | Corrective Action |
| Refrigerant flow obstructed by dirt in condenser | Condenser clogged | Replace condenser |
When the refrigerant does not circulate:

| Symptoms | Probable Causes | Diagnosis | Corrective Actions |
|
| Refrigerant does not circulate |
|
When the refrigerant is overcharged or cooling of condenser is insufficient:

| Symptoms | Probable Causes | Diagnosis | Corrective Actions |
| Pressure extremely high on both low and high pressure sides |
|
|
|
When there is air in the refrigeration system:

| Symptoms | Probable Cause | Diagnosis | Corrective Actions |
| Air in refrigeration system |
|
|
When the expansion valve malfunctions:

| Symptoms | Probable Cause | Diagnosis | Corrective Action |
| Trouble in expansion valve |
| Replace expansion valve |
When the compressor is defective:

| Symptoms | Probable Cause | Diagnosis | Corrective Action |
| Internal leakage in compressor |
| Repair or replace compressor |