HEATING / AIR CONDITIONING  SOLAR SENSOR  INSPECTION  


PROCEDURE

Hide 89120A 1.INSPECT AUTOMATIC LIGHT CONTROL SENSOR

a.
B157083C49
1.521,0.333 1.896,0.552 0.375,0.219 1,1.75 1.406,1.188 true 1.906,1.75 1.656,1.167 true 0.135,0.104 0.344,0.26 0.208,0.156 10 false *a 1.646,0.375 1.854,0.531 0.208,0.156 10 false K1 0.573,1.646 0.979,1.813 0.406,0.167 10 false CLTB 2.01,1.667 2.417,1.833 0.406,0.167 10 false CLTE
*a Front view of wire harness connector
(Automatic Light Control Sensor)


Disconnect the automatic light control sensor connector.


b.

Measure the voltage according to the value(s) in the table below.

Standard Voltage:
Tester Connection Condition Specified Condition
K1-1 (CLTB) - K1-2 (CLTE) Ignition switch on (IG) 11 to 14 V



c.

Measure the resistance according to the value(s) in the table below.

Standard Resistance:
Tester Connection Condition Specified Condition
K1-2 (CLTE) - Body ground Always Below 1 Ω



d.
E259758C33
1.531,0.271 1.927,0.49 0.396,0.219 1.833,1.177 2.385,0.885 true 1.458,1.167 0.896,0.896 true 0.188,0.135 0.438,0.313 0.25,0.177 10 false *a 1.667,0.313 1.896,0.552 0.229,0.24 10 false K1 0.542,0.771 0.958,0.948 0.417,0.177 10 false CLTS 2.438,0.792 2.833,0.958 0.396,0.167 10 false CLTE
*a Component with harness connected
(Automatic Light Control Sensor)


Connect the automatic light control sensor connector.


e.

Connect an oscilloscope to the automatic light control sensor connector.


f.
E276298N04
2.844,1.667 3.302,1.865 0.458,0.198 10 false GND

Check the waveform.

OK:
Tester Connection Tool Setting Condition Specified Condition
K1-4 (CLTS) - K1-2 (CLTE) 2 V/DIV., 10 ms./DIV. Ignition switch on (IG), light control switch in AUTO position Correct waveform is as shown


HINT:

The communication waveform changes according to the surrounding brightness.


If the result is not as specified, replace the automatic light control sensor.


Hide 88625H 2.INSPECT COOLER (SOLAR SENSOR) THERMISTOR

a.

Check the resistance.

i.
E182278C02
0.896,1.813 1.49,1.479 true 2,1.5 2.531,1.802 true 0.104,0.115 0.417,0.313 0.313,0.198 10 false *a 2.625,1.76 3.083,1.958 0.458,0.198 10 false SS+ 0.583,1.771 1.042,1.969 0.458,0.198 10 false SS-
*a Component without harness connected
(Cooler (Solar Sensor) Thermistor)


Measure the resistance according to the value(s) in the table below.

Standard Voltage:
Tester Connection Condition Specified Condition
1 (SS+) - 2 (SS-) Without direct light exposure (Sensor covered) ∞ Ω
1 (SS+) - 2 (SS-) When exposed to sunlight or an inspection light Except ∞ Ω


NOTICE:

The connection procedure for using a digital tester such as an electrical tester is shown above. When using an analog tester, connect the positive (+) lead to terminal 2 (SS-) and the negative (-) lead to terminal 1 (SS+) of the cooler (solar sensor) thermistor.


HINT:
·

As the inspection light is moved away from the cooler (solar sensor) thermistor, the voltage decreases.


·

Use an incandescent light for the inspection. Position it about 30 cm (11.8 in.) from the cooler (solar sensor) thermistor.



If the result is not as specified, replace the cooler (solar sensor) thermistor.