Home › HEATER & AIR CONDITIONING SYSTEM › AIR CONDITIONING › AIR CONDITIONING UNIT (for Sedan)

AIR CONDITIONING UNIT (for Sedan) > INSPECTION

for Preparation Click here



1. INSPECT NO. 1 COOLER THERMISTOR


E113141E02
  1. Measure the resistance.

    Standard resistance:
    Tester Connection
    Condition
    Specified Condition
    1 - 2
    -10°C (14°F)
    7.30 to 9.10 kΩ
    1 - 2
    -5°C (23°F)
    5.65 to 6.95 kΩ
    1 - 2
    0°C (32°F)
    4.40 to 5.35 kΩ
    1 - 2
    5°C (41°F)
    3.40 to 4.15 kΩ
    1 - 2
    10°C (50°F)
    2.70 to 3.25 kΩ
    1 - 2
    15°C (59°F)
    2.14 to 2.58 kΩ
    1 - 2
    20°C (68°F)
    1.71 to 2.05 kΩ
    1 - 2
    25°C (77°F)
    1.38 to 1.64 kΩ
    1 - 2
    30°C (86°F)
    1.11 to 1.32 kΩ

    NOTICE:
    1. Touching the sensor even slightly may change the resistance value. Hold the connector of the sensor.
    2. When measuring the resistance, the temperature of the sensor and the cooler thermistor must be the same.

    HINT:
    As the temperature increases, the resistance decreases (see the graph).

    If the operation is not as specified, replace the cooler thermistor.