GAUGE READINGS
|
OTHER SYMPTOMS
|
DIAGNOSIS
|
CORRECTION
|
|

|
| •
|
Discharge air : slightly
cool. |
| •
|
Thermostatic switch (with thermistor) :
Low side gauge doesn't fluctuate with "ON" and
"OFF". | |
Some air and
moisture in system.
|
| •
|
Discharge refrigerant from
system. |
| •
|
Repair leaks as
located. |
| •
|
Evacuate the system for at least 30
minutes. |
| •
|
Charge system with
refrigerant. |
| •
|
Operate system and check
performance. | |
|

|
| •
|
Discharge air : Becomes warm all the
time during hot part of
day. | |
Some air and
moisture in system.
|
| •
|
Evacuate system with a vacuum
pump. |
| •
|
Recharge system to proper
capacity. |
| •
|
Operate system and check
performance. | |
|

|
| •
|
Compressor : Cycles on and off too
fast. | |
Defective
thermostatic switch.
|
| •
|
Replace thermostatic
switch. |
| •
|
Operate system and check
performance. | |
|

|
| •
|
Compressor : Low side pressure builds
too high before compressor turns on (cycle "ON" point too
high). | |
Faulty
thermostatic switch.
|
| •
|
Replace the thermostatic
switch. |
| •
|
Operate system and check
performance. | |
|

|
| •
|
Discharge air : Slightly
cool. | |
System slightly
low on refrigerant.
|
| •
|
Evacuate system using a vacuum
pump. |
| •
|
Charge system with
refrigerant. |
| •
|
Operate system and check
performance. | |
|

|
|
| •
|
System very low on
refrigerant. |
| •
|
Possible leak in
system. | |
| •
|
Evaporate system using a vacuum
pump. |
| •
|
Charge system with
refrigerant. |
| •
|
Operate system and check
performance. | |
|

|
| •
|
Discharge air : Slightly
cool. |
| •
|
Expansion valve : Frost build
up. | |
| •
|
Sensing bulb
malfunction. | |
| •
|
Disconnect inlet line at expansion valve
and remove and inspect
screen. |
| •
|
Replace screen and reconnect inlet
line. |
| •
|
Evacuate system using a vacuum
pump. |
| •
|
Charge system with
refrigerant. | |
|

|
| •
|
Discharge air : Slightly
cool. |
| •
|
High side pipe : Cool and also shows
moisture or frost. | |
Restriction in
high side of system
|
| •
|
Evacuate system using a vacuum
pump. |
| •
|
Charge system with
refrigerant. |
| •
|
Operate system and check
performance. | |
|

|
|
Compressor
malfunction
|
| •
|
Disassemble
compressor. |
| •
|
Check compressor oil
level. |
| •
|
Operate system and check
performance. | |
|

|
| •
|
High side pipe : Very
hot | |
|
| •
|
Check for loose or worn fan
belt. |
| •
|
Inspect condenser for clogged air
passage. |
| •
|
Check for refrigerant
overcharge. |
| •
|
Operate system and check
performance. | |
|

|
| •
|
Discharge air : Slightly
cool. | |
Large amount of
air and moisture.
|
| •
|
Discharge refrigerant from
system. |
| •
|
Evacuate system using vacuum
pump. |
| •
|
Charge system with
refrigerant. |
| •
|
Operate system and check
performance. | |
|

|
| •
|
Evaporator : Moisture or
frost. | |
Expansion valve
stuck.
|
| •
|
Replace expansion
valve. |
| •
|
Evacuate system using vacuum pump, then
recharge system with
refrigerant. |
| •
|
Operate system and check
performance. | |