WHEN
HANDLING REFRIGERANT
| 1. |
R-134a liquid refrigerant is highly
volatile. A drop on the skin of your hand could result in localized
frostbite. When handling the refrigerant, be sure to wear
gloves. |
| 2. |
It is standard practice to wear goggles or
glasses to protect your eyes, and gloves to protect your hands. If
the refrigerant splashes into your eyes, wash them with clean water
immediately. |
| 3. |
The R-134a container is highly pressurized.
Never leave it in a hot place, and check that the storage
temperature is below 52°C (126°F). |
| 4. |
A electronic leak detector should be used to
check the system for refrigerant leakage. Bear in mind that the
R-134a, upon coming into contact with flame, produces phosgene, a
highly toxic gas. |
| 5. |
Use only recommended the lubricant for
R-134a systems. If lubricants other than the recommended one used,
system failure may occur. |
| 6. |
PAG lubricant absorbs moisture from the
atmosphere at a rapid rate, therefore the following precautions must
be observed :
| A. |
When removing refrigerant components
from a vehicle, cap immediately the components to prevent from
the entry of moisture. |
| B. |
When installing refrigerant components
to a vehicle, do not remove the cap until just before
connecting the components. |
| C. |
Complete the connection of all
refrigerant tubes and hoses without delay to prevent the A/C
system from taking on
moisture. |
| D. |
Use the recommended lubricant from a
sealed container
only. | |
| 7. |
If an accidental discharge in the system
occurs, ventilate the work area before resuming
service.

|
WHEN
REPLACING PARTS ON A/C SYSTEM
| 1. |
Never open or loosen a connection before
discharging the system. |
| 2. |
Seal the open fittings of components with a
cap or plug immediately to prevent intrusion of moisture or
dust. |
| 3. |
Do not remove the sealing caps from a
replacement component until it is ready to be
installed. |
| 4. |
Before connecting an open fitting, always
install a new sealing ring. Coat the fitting and seal with
refrigerant oil before making the connection.

|
WHEN
INSTALLING CONNECTING PARTS
| 1. |
BOLT/NUT COUPLING TYPE
| (1) |
Lubricate each connecting parts with
compressor oil so as to tighten them easily, enough to prevent
refrigerant leaks. |
| (2) |
Use two wrenches not to twist the
tube. |
| (3) |
Tighten them to the specified
torque.

| |
| 2. |
FLANGE WITH GUIDE PIN TYPE
| (1) |
Check the O-ring for missing and
damage, then lubricate it with compressor
oil. |
| (2) |
Push the pipe as shown in the
illustration and tighten the nut by
hand. |
| (3) |
Tighten the nut to the specified
torque.

| |
COMPRESSOR
OIL
The oil used to
lubricate the compressor circulates in the system while the compressor is
operating. Whenever replacing any component of the system or when a large
amount of gas leakage occurs, add oil to maintain the original total
amount of oil.
| 1. |
HANDLING OF OIL
| (1) |
The oil should be free from moisture,
dust, metal filings, etc. |
| (3) |
The moisture content in the oil
increases when exposed to air for prolonged periods. After
use, seal the container
immediately. | |
| 2. |
OIL RETURN OPERATION
To check the oil level or add oil, idle
engine for 20~30 minutes and setting the heater control set to
maximum cooling and blower level, to return the lubricant to
compressor. |
| 3. |
CHECKING AND ADDING COMPRESSOR
OIL
In order to add oil to an operating
compressor, check the compressor oil using the following
procedure:
| (1) |
Perform the oil return operation, stop
the engine, discharge the refrigerant, and dismantle the
compressor from vehicle. |
| (2) |
Discharge oil from the system line
outlet.
|
If compressor is cold, sometimes
it can be hard to drain the oil. Warm up the compressor
(approx. 40~50°C) to drain the
oil. | |
| (3) |
Check the amount of the discharged
oil. If it is less than 70cc, it means there is a little leak
of oil. Perform the leakage test on each system connection,
and repair or replace faulty parts if
necessary. |
| (4) |
Check oil for contamination and set
the oil level in the following procedure:
WHEN OIL IS CLEAN
Discharge
|
Setting
|
Above 70cc
|
Oil level is normal, add equal amount of
discharged oil.
|
Below 70cc
|
Oil level is low, add 70cc of
oil.
|
| |
INSTALLATION
OF MANIFOLD GAUGE SET
|
When connecting the manifold gauge set, be
sure to observe all safety
precautions. |
| 1. |
Close both hand valves of the manifold gauge
fittings. |
| 2. |
Install the charging hoses of the gauge set
to the fittings. Connect the low-pressure hose to the low-pressure
service port, and the high-pressure hose to the high-pressure
service port. Tighten the hose nuts by hand.

|
When charging the refrigerant, do it
after removing the engine cover and the air intake
hose. | |
REFRIGERANT
DISCHARGING PROCEDURE
| 1. |
Connect the manifold gauge set to the
system.

|
| 2. |
Put a towel under the open end of the center
hose. |
| 3. |
Open the high pressure valve slowly to
discharge the refrigerant.
|
If discharging the refrigerant too
fast, compressor oil may drain from the
system. | |
| 4. |
Check if the towel is stained with oil. If
so, gently close the valve. |
| 5. |
If the manifold gauge reading drops below
3.5kg·cm², open the low pressure valve
slowly. |
| 6. |
Open the high and low pressure valves slowly
in order to drop the system pressure until the gauge indicates
0kg·cm².

|
EVACUATING
REFRIGERANT
|
It is necessary to evacuate the air
conditioning system any time the system has been opened. Evacuation
is necessary to rid the system of all air and moisture that may have
been allowed to enter the unit. After installation of a component,
the system should be evacuated for approximately 15 minutes. A
component in service that has been opened for repair should be
evacuated for 30 minutes.

|
| 2. |
Connect a manifold gauge set to the
compressor gauge fittings. Close both high and low pressure
valves. |
| 3. |
Make sure the refrigerant has been
discharged from the system. |
| 4. |
Connect the center hose of the gauge set to
the vacuum pump inlet. |
| 5. |
Start the vacuum pump and then open the high
and low manifold pressure valves. |
| 6. |
After about ten minutes, check that the low
pressure gauge reads more than 94,39 kPa (0.96 kg·cm², 13.7 psi) of
vacuum. If negative pressure can not be obtained, there is a leak in
the system. In this case, repair the leak as follows:
| (1) |
Close both manifold valves and stop
the vacuum pump. |
| (2) |
Charge the system with a can of
refrigerant [about 0.4 kg (0.9 lb)]. Refer to Charging
Refrigerant. |
| (3) |
Check for refrigerant leakage with a
leak detector. Repair any leakage found. Refer to Checking
Refrigerant Leak. |
| (4) |
Discharge refrigerant again, and then
evacuate the system. If no leaks are found, continue
evacuating the
system. | |
| 7. |
Start the vacuum
pump. |
| 8. |
Open both manifold pressure valves to obtain
94.39 kPa (0.96 kg·cm², 13.7 psi) of
vacuum. |
| 9. |
After the low pressure manifold gauge
indicates close to 94.39 kPa (0.96 kg·cm², 13.7 psi), continue
evacuating for 15 minutes. |
| 10. |
After evacuating for 15 minutes, close both
manifold pressure valves and stop the vacuum pump. Disconnect the
hose from the vacuum pump. The system is now ready for
charging.

|
HANDLING
THE REFRIGERANT SERVICE TAP VALVE
| 1. |
Before connecting the valve to the
refrigerant container, turn the handle fully
counterclockwise. |
| 2. |
Turn the disc counterclockwise until it
reaches its highest position. |
| 3. |
Connect the center hose to the valve
fitting. Turn the disc fully clockwise by
hand. |
| 4. |
Turn the handle clockwise to make a hole in
the sealed top. |
| 5. |
Loosen the center hose nut connected to the
center fitting of the manifold
gauge. |
| 6. |
Allow air to escape for a few seconds, and
then tighten the nut. |
CHARGING
REFRIGERANT SYSTEM (VAPOR)
|
This step is to charge the system through
the low pressure side with the refrigerant in a vapor state. When
the refrigerant container is placed upright, refrigerant will enter
the system as a vapor.

|
| 1. |
Install the refrigerant can tap valve as
described in Handling the Refrigerant Tap Valve
section. |
| 2. |
Open the low pressure valve. Adjust the
valve so that the low pressure gauge does not read over 412 kPa (4.2
kg·cm², 60 psi). |
| 3. |
Put the refrigerant in a pan of warm water
(about 40°C or 104°F) to keep vapor pressure in the container
slightly higher than vapor pressure in the
system. |
| 4. |
Run the engine at fast idle and operate the
air conditioning.

|
Be sure to keep the container upright
to prevent liquid refrigerant from being charged into the
system through the suction side, resulting in possible damage
to the
compressor. | |
| 5. |
Charge the system to the specified amount.
Then close the low pressure valve.
Specified amount :
550±25g
| |
| 6. |
When refrigerant charging speed is slow,
immerse the refrigerant can in heated water. (a temperature of
approx. 40°C (104°F)).
| • |
Under any circumstances, the
refrigerant must not be warmed in water heated to a
temperature of over 52°C
(126°F). |
| • |
A blow torch or stove must never
be used to warm up the
can. | | |
CHARGING
THE REFRIGERANT SYSTEM (LIQUID)
|
This step is to charge an empty system
through the high pressure side with refrigerant in a liquid state.
When the refrigerant container is held upside down, refrigerant will
enter the system as a liquid. |
|
Never run the engine when charging the
system through the high pressure side. Do not open the low pressure
valve when the system is being charged with liquid
refrigerant. |
| 1. |
Close both high and low pressure valves
completely after the system is
evacuated. |
| 2. |
Install the refrigerant can tap valve as
described in "Handling the Refrigerant Service Tap Valve"
section. |
| 3. |
Open the high pressure valve fully and keep
the container upside down. |
| 4. |
Charge the system to the specified amount by
weighing the refrigerant with a scale. Overcharging will cause
discharge pressure (high side) to rise. Then, close the high
pressure valve.
Specified amount :
550±25g
| |
| 5. |
After the specified amount of refrigerant
has been charged into the system, close the manifold gauge
valve. |
| 6. |
Confirm that there are no leaks in the
system by checking with a leak detector. Refer to Checking for
Refrigerant Leak.
|
Conducting a performance test prior to
removing the manifold gauge is good service
practice. | |
CHECKING
FOR REFRIGERANT LEAKS
Always conduct a leak
test with an electronic leak detector whenever leakage or refrigerant is
suspected and when conducting service operations which are accompanied by
disassembly or loosening or connection fittings.
| 1. |
Check the torque on the connection fittings
and, if too loose, tighten to the proper torque. Check for gas
leakage with a leak detector. |
| 2. |
If leakage continues even after the fitting
has been tightened, discharge the refrigerant from the system,
disconnect the fittings, and check their seating faces for damage.
Always replace, even if the damage is
slight. |
| 3. |
Check the compressor oil and add oil if
required. |
| 4. |
Charge the system and recheck for gas leaks.
If no leaks are found, evacuate and charge the system
again. |
AMOUNT
OF DEFLECTION OF BELT
Item
|
Deflection L
(mm)
|
New one
|
5~5.5
|
Used one
|
6~7
|
After driving
|
8
|

PERFORMANCE
TEST
| 1. |
Install the manifold gauge
set. |
| 2. |
Run the engine at 2,000 rpm and set the
controls for maximum cooling and high blower
speed. |
| 3. |
Keep all windows and doors
open. |
| 4. |
Place a dry-bulb thermometer in the cool air
outlet. |
| 5. |
Place a psychrometer close to the inlet of
the cooling unit. |
| 6. |
Check that the reading on the high pressure
gauge is 1,373-1,575 kPa (14-16kg·cm², 199-228 psi). If the reading
is too high, pour water on the condenser. If the reading to too low,
cover the front of the condenser.

|
| 7. |
Check that the reading on the dry-bulb
thermometer at the air inlet is 25~35°C
(77~95°F). |
| 8. |
Calculate the relative humidity from the
psychrometric graph by comparing the wet-and dry-bulb reading of the
psychrometer at the air inlet. |
| 9. |
Measure the dry-bulb temperature at the cool
air outlet, and calculate the difference between the inlet dry-bulb
and outlet dry-bulb temperatures. |
| 10. |
Check that the intersection of the relative
humidity and temperature difference is within the block hard line.
If the intersection is within the block hard line, cooling
performance is satisfactory.


| |