| BUTTON CONTROL AND OPERATION
LOGIC |
| a. |
All buttons should be
back-up. |
| b. |
Push the button, then the operation sound is
made for 0.1 sec. (When a S/W is selected, and operation sound is
made as well). |
|
NO |
BUTTON |
BUTTON FUNCTION |
DISPLAY |
SYSTEM OPERATION |
|
1 |
TEMP |
TEMP
UP/DOWN |
Set temperature : Display |
| a. |
Control the discharge air temperature by
adjusting the mixture ratio of cold amp; hot air with the TEMP
DOOR. |
| b. |
Whenever press the SWITCH, temperature
is changed 0.5°C up/down each time. (Each time the operation
sound is made of 0.1 sec.) |
| c. |
Set 17°C (62°F) as MAX COOL, 32°C (90°F)
as MAX HOT. |
| d. |
When the switch is turned ON from OFF,
the set temperature is displayed as the same before
OFF. |
| e. |
When changing the set temperature from
17.5°C to 17°C or from 31.5°C to 32°C, the operation sound is
made. |
| f. |
At 17°C, if the temperature is set below
than 17°C or at 32°C , if it is a above than 32°C , the
operation sound is made 5 times at an interval of 0.15
sec. |
| g. |
When pushing the TEMP button several
times, the set temperature is shifted to another step at an
interval of 0.7sec., When engaging the button continuously
(keep pushing), only the first shift takes 0.7 sec. but the
next shifts take 0.3
sec. | |
|
OFF SW AND SYSTEM OPERATION
| b. |
TEMP : SET TEMPERATURE
UP/DOWN | |
|
2 |
AUTO |
AUTO CONTROL |
“AUTO” : Display |
| a. |
Automatically control the following
items corresponding to the set
temperature. |
| b. |
When the AUTO mode is off, the word AUTO
should not appear. |
| c. |
After off the AUTO mode, the system is
automatically controlled except for the manually selected
SW. | |
|
OFF SW AND SYSTEM OPERATION
| b. |
FAN UP/DOWN : BLOWER FAN SPEED MANUAL
CONTROL |
| c. |
MODE : DISCHARGE MODE MANUAL
CONTROL |
| d. |
A/C : A/C ON/OFF MANUAL
CONTROL |
| e. |
FRE. : FRE. MODE MANUAL
CONTROL |
| f. |
REC. : REC. MODE MANUAL
CONTROL |
| g. |
DEF. : DEF. MODE MANUAL CONTROL, A/C ON,
FRE. | |
|
3 |
AMB |
Ambient temperature display |
| b. |
Ambient temperature :
Display |
| c. |
The other signals :
OFF | |
| a. |
System is operated as the same before
the AMB SW turned on. |
| b. |
When the AMB SW is pushed, the other
signals are not appeared but the word AMB and the ambient
temperature are displayed for 5 sec., and then the display
become the same as the AMB SW is not
pushed. | |
|
OFF SW AND SYSTEM OPERATION
| a. |
AMB : If the AMB SW is pushed once more
when the ambient temperature is displayed, the ambient
temperature is not appeared and the display become the same as
the AMB SW is not pushed. |
| b. |
OTHER SWITCHES : If the other switch is
pushed except for REAR DEF and in-car amp; ambient /AQS,
ambient temperature is not appeared and the pushed switch is
displayed. | |
|
4 |
A/C |
A/C ON/OFF CONTROL |
|
|
|
OFF SW AND SYSTEM OPERATION
| a. |
A/C : A/C ON/OFF MANUAL
CONTROL |
| c. |
AUTO : AUTO MODE AUTOMATIC
CONTROL | |
|
5 |
MODE |
MODE DOOR CONTROL
|
|
| a. |
Fix the MODE DOOR to one among VENT,
B/L, FLOOR and MIX. |
| b. |
MODE SW MANUAL CONTROL ORDER : VENT →
B/L → FLOOR → MIX → VENT →
... |
| c. |
At MIX MODE : MIX LOGIC (MIX, FRE., A.C
ON) | |
|
OFF SW AND SYSTEM OPERATION
| a. |
DEF : DEF MODE MANUAL
CONTROL |
| b. |
MODE : VENT, B/L, FLOOR amp; MIX (repeat
the order) |
| c. |
AUTO : AUTO MODE AUTOMATIC
CONTROL | |
|
6 |
DEF |
DEF MODE |
|
| a. |
MODE DOOR : Fix to
“DEF” |
| b. |
INTAKE DOOR : Fix to “FRE.” (REC. can be
selected) |
| 1) |
A/C OUTPUT ON/OFF control :
Corresponding to the detected temperature by EVAP
SENSOR. |
| 2) |
A/C output should be cut off at 3.5°C or
below (ambient temperature).
(DISPLAY OFF, A/C SELECT SIGNAL
OFF) |
| d. |
DEF is prior to “MAX HOT/COOL”
function. |
| e. |
DEF is prior to “MIX MODE”
control. | |
|
OFF SW AND SYSTEM OPERATION
| a. |
AUTO : ALL SYSTEM AUTOMATIC
CONTROL |
| b. |
MODE : DISCHARGE MODE MANUAL CONTROL
(DEF Function off) |
| c. |
A/C : A/C ON/OFF MANUAL
CONTROL |
| d. |
DEF : Return to the mode before the DEF
S/W selection | |
|
7 |
OFF |
SYSTEM OFF |
LCD : ON |
| c. |
TEMP. DOOR : Fix to the mode before
OFF |
| d. |
MODE DOOR : Fix to the mode before
OFF |
| e. |
INTAKE CONTROL : Fix to the mode before
OFF |
| a. |
After “OFF”, at REC, REC. S/W ON
(NON-AQS type) |
| b. |
After “OFF”, at FRE, FRE. S/W ON
(NON-AQS type) |
| c. |
After “OFF”, at AQS, AQS/REC. S/W ON
(AQS type) |
| d. |
After “OFF”, AQS ON→AQS
LOGIC |
| e. |
After “OFF”, AMB S/W
ON |
| 1) |
OFF : The word “AMB” amp; ambient
temperature display for 5 sec. and then
off. | |
|
OFF SW AND SYSTEM OPERATION
| a. |
AUTO : AUTO MODE AUTOMATIC
CONTROL |
| 1) |
SPEED : Return to MANUAL
LOW |
| 2) |
OTHERS : Return to the mode before
OFF |
| 2) |
OTHERS : Return to the mode before
OFF |
| 1) |
MODE : The mode before
OFF |
| 2) |
OTHERS : Return to the mode before
OFF |
| 4) |
OTHERS : Return to the mode before
OFF |
| 1) |
TEMP : The mode before
OFF |
| 2) |
OTHERS : Return to the mode before
OFF | |
|
8 |
REC. (NON-AQS type) |
REC. MODE |
|
| a. |
When operating the REC. S/W from FRE.
MODE, fix the INTAKE DOOR to REC. MODE or when operating the
REC. S/W from REC. fix the INTAKE DOOR to FRE.
MODE. | |
|
FRE. MODE |
|
OFF SW AND SYSTEM OPERATION
| a. |
REC. : FRE./REC. MODE
CONTROL |
| b. |
OFF SW : ALL MODES (POSSIBLE TO MANUALLY
SELECT) |
| c. |
AUTO : AUTOMATIC CONTROL (FRE. or
REC.) | |
|
9 |
FAN UP/DOWN |
BLOWER FAN SPEED UP/DOWN |
FAN IND ON/OFF |
| a. |
BLOWER MOTOR's rotation speed is
controlled by the current variation of the POWER
TRANSISTOR. |
| b. |
At AUTO MODE, if FAN is operated
UP/DOWN, the FAN SPEED is UP/DOWN on the basis of the present
FAN LEVEL. |
| c. |
At OFF, if the other SW except for “FAN”
is turned ON, the FAN SPEED is gradually increased from LOW to
TARGET SPEED. |
| d. |
Fan speed level and
voltage |
| 1) |
AUTO AIR CONDITIONER : No level (4.5V -
B+) |
| 2) |
AUTO HEATER : No level (4.5V -
B+) |
| 3) |
MANUAL FAN SPEED : 7th level (3.8V -
B+) |
| e. |
The first shift to another step takes
0.7 sec. If the button is continually engaged, the first shift
takes 0.7 sec. And then the next ones take 0.3 sec per each.
The operation sound is made for 0.1
sec. |
| f. |
At MANUAL 7th level when the UP SW is
pushed or at MANUAL 1st level when the DOWN SW is pushed, the
operation sound is made 5 times at an interval of 0.15
sec. |
| g. |
When shifting 6 to 7 level, or 2 to 1
level, the operation sound is intervally made each 0.15
sec. | |
|
OFF SW AND SYSTEM OPERATION
| a. |
AUTO : AUTO MODE AUTOMATIC
CONTROL |
| c. |
FAN UP/DOWN : BLOWER FAN SPEED MANUAL
CONTROL | |
|
10 |
DEFOG |
Rear glass defogger |
DEFOG IND ON/OFF |
| a. |
If the DEFOG SW is pushed, the rear
glass defogger operation signal is output to the ETACS and the
ETACS turns the DEFOG IND on by the HTD
input. |
| b. |
While operating the rear glass defogger,
if DEFOG SW is pushed, ETACS stops operating the rear glass
defogger and turns the DEFOG IND
off. |
| c. |
After operating the rear glass defogger
for 15 minutes by EATCS, DEFOG function is automatically
off. | |
|
OFF SW AND SYSTEM OPERATION
| a. |
DEFOG : Push the second DEFOG SW, DEFOG
function is
off. | |
SYSTEM CONTROL FEATURES
Signal I/O for each control
feature
|
Control item |
Input |
Output |
Remarks |
|
Required discharge temperature
control |
Auto SW, A/C SW, TEMP SW, INCAR sensor, AMB
sensor, Photo sensor, Water temperature sensor, thermo sensor, TEMP
actuator. |
TEMP actuator |
|
|
Mode control |
AUTO SW, MODE SW, TEMP SW, DEF SW, Blower SW,
OFF SW, INCAR sensor, AMB sensor, Photo sensor, Water temperature
sensor, thermo sensor, Power TR. |
Blower motor
Power TR
HI-blower relay |
Blower Switch
Manual selection
Control in priority |
|
Mode door control |
AUTO SW, MODE SW, DEF SW, Blower SW, OFF SW,
TEMP SW, INCAR sensor, AMB sensor, Photo sensor. |
Mode actuator |
|
|
Intake control |
AUTO SW, A/C SW, DEF SW, TEMP SW, OFF SW,
Intake SW, INCAR sensor, AMB sensor, Photo sensor, Power
TR. |
Mode actuator |
|
|
Compressor control |
AUTO SW, A/C SW, DEF SW, TEMP SW, OFF SW,
IN-CAR sensor, AMB sensor, Photo sensor |
Compressor relay |
|
| a. |
During mode control, the A/C may operate
during DEF or MIX mode. In order to enable dehumidification, the
driver may select A/C OFF during the A/C on
condition. |
Control specification
|
Control item |
Control features |
Remarks |
|
Required discharge temperature |
Required temperature determined by the set
temperature and the inputted sensor value. |
|
|
Auto control |
Required discharge temperature is determined
by the set temperature and the inputted sensor value. The feature
will use the required discharge temperature to perform the auto
control of temp. actuator, mode actuator, intake actuator, blower
motor and compressor, and maintain the set temperature
stably. |
|
|
IN-CAR temperature correction |
Upon detecting rapid changes of temperature
from the INCAR sensor, it will gradually correct the incar
temperature value. |
|
|
AMB temperature correction |
Upon detecting rapid changes of temperature
from the AMB sensor, it will gradually correct the ambient
temperature value. |
|
|
Photo correction |
Upon detecting rapid changes of photo
intensity from the PHOTO sensor, it will gradually correct the photo
intensity value. |
| a. |
350→1000(W/m²)/1min
delay |
| b. |
350→1000(W/m²)/5min
delay | |
|
TEMP door control |
It does the automatic control to maintain the
optimum TEMP door opening (0%-100%). It will be computed by the
temperature set and the input signal from each
sensor. |
The set temperature range 17°C→32°C, 0.5°C
step (62°F→90°F, 1°F step) |
|
Blower speed |
Automatic control of the blower speed. The
target value will be computed by the set temperature and the input
signal from each sensor. (7 levels may be selected in case of manual
selection.) |
| a. |
Auto mode blower low voltage (Manual low
voltage: 3.8) |
| b. |
Auto mode heater blower HI speed:
10.6V | |
|
Electro-motive mode control |
During auto control, it will raise the
permitted voltage of blower motor gradually in order to improve
comfortability. |
6 seconds for shifting LO→MAX
HI |
|
Photo compensation |
During auto control, it will compensate the
blower level and the discharge temperature according to the photo
intensity detected from the PHOTO sensor at VENT or B/L mode. PHOTO
compensation will begin after 5 seconds when ignition
on. |
|
|
Mode door control |
Automatic control of air discharge based on
the required discharge temperature. It will be computed by the
temperature setting and the input signal from each
sensor.
(VENT→B/L→FLOOR→VENT)
In case of manual selection
(VENT→B/L→FLOOR→MIX→VENT) |
| a. |
At OFF in AUTO mode, MODE door will
maintain the AUTO control
condition. |
| b. |
At OFF in manual mode, MODE door will
maintain the manual control
condition. | |
|
MIX mode control (in auto
control) |
If the ambient temperature is -13°C or less in
AUTO mode, discharge mode will be controlled at MIX. (When front
window glass is defogged.) |
Entering MIX mode, A/C will
operate. |
|
INTAKE door control |
Auto control of intake mode based on the
required discharge temperature that will be computed by the
temperature setting and the input signal from each
sensor. |
| a. |
Shift to REC when selecting REC button
at FRE condition (LED on). |
| b. |
Shift to FRE when selecting FRE button
at REC condition (LED
off). | |
|
INTAKE control at OFF |
The intake door will shift to the REC position
when switching the system off in auto-condition, and maintain the
previous condition at OFF at manual condition. |
| a. |
FRE./REC. manual selection will be
enabled at OFF |
| b. |
REC indicator will come on at OFF at
AUTO mode. | |
|
Compressor auto control |
Control automatically the compressor on/off
state corresponding to the set temperature and the input signal from
each sensor. |
| a. |
When selection the AUTO SW, the
compressor is controlled to
ON/OFF. |
| b. |
When selection the DEF SW, the
compressor is controlled to
“ON”. | |
|
Compressor clutch on/off control based on
refrigerant temperature |
If EVAP sensor temperature is below than
0.5°C, the compressor will be ON and the temperature is 3°C, or
higher, with the compressor OFF. |
|
|
MAX HOT |
When selecting the set temperature 32°C at
AUTO mode, MAX HOT will be performed. It will prevail over MIX mode
control. |
| e. |
Blower speed: AUTO
HI(10.6V) | |
|
MAX COOL |
When selecting the set temperature 17°C at
AUTO mode, MAX COOL will be performed. |
|
|
Electromotive heating control |
If the set temperature > the in-car
temperature by 3°C at B/L or FLOOR in AUTO mode, and the water
temperature sensor input is 58°C or less, it will effect the
electromotive heating control to prevent outside cold air from
flowing toward the feet of passengers. |
| a. |
Blower speed: Controlled at AUTO LOW
(0.5V) | |
|
As the coolant temperature rises, the MODE
door will shift to DEF→MIX→AUTO. |
Operation release
| a. |
10 minutes after ignition on(In case of
temperature sensor fail, it will apply the substitute value,
20°C). |
| b. |
After pressing blower switch when water
temperature sensor detection is 58°C or
higher. |
| c. |
In pressing MODE
switch. |
| d. |
In Upon pressing DEF
switch. | |
|
MODE: Manual selection is
enabled.
INTAKE door: At AUTO control or at manual
selection mode. |
|
Blower speed: Manual selection is enabled (No
re-entry). |
|
Electromotive cooling control |
In order to prevent hot air from the VENT or
B/L in AUTO mode (A/C on mode), the blower speed will be operated at
LOW for approx. 9 seconds before entering the AUTO control if the
EVAP sensor detection is temperature 30°C or higher. |
|
|
MAX HOT |
If the above condition is satisfied,
electromotive cooling control will operate at any
time. |
|
|
Air Quality System (AQS) |
The AQS system will detect the hazardous
elements and odors contained in the air. If the harmful element
concentration is higher than standard, the system will output a LOW
signal (0V) to the FATC. |
| a. |
When the initial battery connection and
ignition is ON, it will operate at AUTO mode. (AQS will not
operate.) | |
|
If the concentration is within the standard
value, the system will output a HI signal (3V) the
FATC. |
| a. |
When IGN 2 ON, the AQS assembly will be
preheated for 34.5±5seconds. During the preheating, AQS will
output 0V (ground). (REC
mode) | |
|
Corresponding to the signal from the AQS, it
will control the INTAKE door as follows to prevent the inflow of
harmful gas in FATC: |
| a. |
IGN2 ON: It will check circuit break on
the AQS assembly's signal line for approx. 7 seconds during
the preheating, irrespective to the AQS switch
condition. | |
|
Condition |
INTAKE door position |
| a. |
When AQS is selected prior to IGN2 OFF
and IGN2 is turned OFF→ON: AQS indicator will come on, and the
system will operate at AQS mode. (Store the previous condition
before IGN 2 OFF) | |
|
LOW |
REC |
|
HI |
FRE |
|
Initialization Upon battery-on |
When supplying the initial power, it will
operate in the initial condition. |
| a. |
When the initial ignition ON after
battery connection, the system will operate at the set
temperature 25°C and at AUTO
mode. | |
|
Memory |
When removing ignition key, it will store
FATC's operating condition |
| a. |
When IGN ON after IGN OFF during FATC
operation, the system will operate at the previous before the
ignition
off. | | |