Home › Heating,Ventilation, Air Condioning › Controller

Controller: Troubleshooting

DIAGNOSIS SYSTEM
OPERATION METHOD (SELF-DIAGNOSIS)
The Full Automatic Control air conditioning module self test feature will detect electrical malfunction and provide error codes for system components with suspected failures.

DIAGNOSTIC TROUBLE CODE DESCRIPTION
1.
A/C system is turned OFF during self diagnosis. The result of self diagnosis is displayed using 2 digits of the temperature display.
2.
Diagnostic trouble codes are displayed during self diagnosis. However, after diagnosis is complete, relevant data is not stored in memory.
3.
Self diagnosis of photo sensor is performed using a light bulb over 60W placed within 40cm with sun load applied.
Without sun load, photo sensor error code displays.
DTC CHART
If a malfunction code is displayed during the DTC check, check the circuit listed for that code in the table below.
DTC code
Detection item
Trouble area
00
Normal
•
Incar sensor
•
Harness or connector between incar sensor and A/C control assembly
•
A/C control assembly
11
Open INCAR Sensor circuit
12
Shorted INCAR Sensor circuit
13
Open Ambient sensor circuit
•
Ambient sensor
•
Harness or connector between ambient sensor and A/C control assembly
•
A/C control assembly
14
Shorted Ambient sensor circuit
15
Open water temp. sensor
•
Water temp. sensor
•
Harness or connector between water temp. sensor and A/C control assembly
•
A/C control assembly
16
Shorted water temp. sensor
17
Open evap. sensor
•
Evap. sensor
•
Harness or connector between evap. sensor and A/C control assembly
•
A/C control assembly
18
Shorted evap. sensor
19
Open or shorted temp. door potentiometer
•
Harness or connector between temp. door potentiometer and A/C control assembly
20
Defective temp. door potentiometer
•
Temp. door potentiometer

FAILURE SAFE FUNCTION
NO.
Item
Description
Fail-safe
1
INCAR SENSOR
Short/open circuit of IN CAR SENSOR
Once diagnosis is occurs, system is regarded as 25°C constant.
2
AMBIENT SENSOR
Short/open circuit of AMBIENT SENSOR
Once diagnosis is occurs, system is regarded as 20°C constant.
3
EVAPORATOR TEMP. SENSOR
Short/open circuit of EVAPORATOR TEMP. SENSOR
Once diagnosis is occurs, system is regarded as -2°C constant.
4
WATER TEMP. SENSOR
Short/open circuit of WATER TEMP. SENSOR
•
DEF mode
•
After 10 minutes at ignition ON condition, the water temp. sensor will be failed.
5
TEMP. DOOR POTENTIOMETER
Short/open circuit of TEMP. DOOR POTENTIOMETER
•
17°C constant → when 24.5°C : MAX COOL
•
25°C constant → when 32°C : MAX HOT