| 1. |
Measure the pressure of high pressure line by
measuring voltage output between NO.1 and NO.2
terminals.

|
| 2. |
Inspection the voltage value whether it is
sufficient to be regular value or not.
Voltage = 0.00878835 * Pressure (psig) +
0.5
| |
| 3. |
If the measured voltage value is not
specification, replace the A/C pressure
transducer. |
| 1. |
Disconnect negative (-) battery
terminal. |
| 2. |
Disconnect A/C pressure transducer
connector(A) (3P) from wiring harness.

|
| 3. |
Remove the A/C pressure
transducer.
|
Take care that liquid suction pipe is
not bent. | |
| 4. |
Installation is the reverse order of
removal.
Tightening
torques : 10~12 N.m (1.02~1.22 kgf.m,
7.4~8.8 lb-ft)
| | |