The No. 1 cooler thermistor (evaporator temperature sensor) is installed on the evaporator in the air conditioning unit to detect the temperature of the cooled air that has passed through the evaporator and to control the air conditioner. It sends signals to the air conditioning amplifier. The signals change in accordance with the resistance of the No. 1 cooler thermistor (evaporator temperature sensor). As the temperature decreases, the resistance increases. As the temperature increases, the resistance decreases. The air conditioning amplifier applies a voltage (5 V) to the No. 1 cooler thermistor (evaporator temperature sensor) and reads voltage changes as changes in the resistance of the No. 1 cooler thermistor (evaporator temperature sensor). This sensor is used for frost prevention.
| DTC No. | DTC Detection Condition | Trouble Area |
|---|---|---|
| B1413/13 | Open or short in evaporator temperature sensor circuit | ·
No. 1 cooler thermistor (evaporator temperature sensor) ·
Wire harness between No. 1 cooler thermistor (evaporator temperature sensor) and air conditioning amplifier ·
Air conditioning amplifier |
Connect the intelligent tester to the DLC3.
Turn the ignition switch on (IG) and turn the intelligent tester main switch ON.
Select the item below in the Data List, and read the value displayed on the intelligent tester.
| Item | Measurement Item / Display (Range) | Normal Condition | Diagnostic Note |
|---|---|---|---|
| Evap Fin Temp | Evaporator temperature sensor / Min.: -29.7°C (-21.46°F)
Max.: 59.6°C (139.28°F) |
Actual evaporator temperature is displayed | Open circuit: -29.7°C (-21.46°F)
Short circuit: 59.6°C (139.28°F) |
The display is as specified in the normal condition column.
| Result | Proceed to |
|---|---|
| NG | A |
| OK (Checking from PROBLEM SYMPTOMS TABLE) | B |
| OK (Checking from DTC) | C |
A
B
C
Remove the No. 1 cooler thermistor.
Measure the resistance of the thermistor.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| 1 - 2 | -10°C (14°F) | 7.30 to 9.10 kΩ |
| 1 - 2 | -5°C (23°F) | 5.65 to 6.95 kΩ |
| 1 - 2 | 0°C (32°F) | 4.40 to 5.35 kΩ |
| 1 - 2 | 5°C (41°F) | 3.40 to 4.15 kΩ |
| 1 - 2 | 10°C (50°F) | 2.70 to 3.25 kΩ |
| 1 - 2 | 15°C (59°F) | 2.14 to 2.58 kΩ |
| 1 - 2 | 20°C (68°F) | 1.71 to 2.05 kΩ |
| 1 - 2 | 25°C (77°F) | 1.38 to 1.64 kΩ |
| 1 - 2 | 30°C (86°F) | 1.11 to 1.32 kΩ |
Touching the thermistor even slightly may change the resistance value. Be sure to hold the connector of the thermistor.
When measuring, the thermistor temperature must be the same as the ambient temperature.
As the temperature increases, the resistance decreases (see the graph).
OK
NG