88601
1.INSPECT COOLER CONTROL SWITCH SUB-ASSEMBLY
Measure the resistance according to the value(s) in the table below.
| Tester Connection | Switch Condition | Specified Condition |
|---|---|---|
| 1 - 2 | On | Below 1 Ω |
| 1 - 2 | Off | 10 kΩ or higher |
Apply battery voltage to the cooler control switch connector and check that the indicator illuminates.
| Measurement Condition | Specified Condition |
|---|---|
| Battery positive (+) → Terminal 3
Battery negative (-) → Terminal 4 |
indicator illuminates |
If the result is not as specified, replace the cooler control switch.
88306
2.INSPECT NO. 1 COOLER BLOWER MOTOR SUB-ASSEMBLY
Apply battery voltage to the blower motor connector and check the operation of the blower motor.
| Measurement Condition | Specified Condition |
|---|---|
| Battery positive (+) → Terminal 1
Battery negative (-) → Terminal 2 |
Motor operates smoothly |
If the result is not as specified, replace the blower motor.
88625B
3.INSPECT NO. 3 COOLER THERMISTOR
Measure the resistance according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| 1 - 2 | -10°C (14°F) | 7.40 to 9.20 kΩ |
| 1 - 2 | -5°C (23°F) | 5.65 to 7.00 kΩ |
| 1 - 2 | 0°C (32°F) | 4.35 to 5.40 kΩ |
| 1 - 2 | 5°C (41°F) | 3.40 to 4.20 kΩ |
| 1 - 2 | 10°C (50°F) | 2.68 to 3.30 kΩ |
| 1 - 2 | 15°C (59°F) | 2.10 to 2.60 kΩ |
| 1 - 2 | 20°C (68°F) | 1.66 to 2.10 kΩ |
| 1 - 2 | 25°C (77°F) | 1.32 to 1.66 kΩ |
| 1 - 2 | 30°C (86°F) | 1.05 to 1.35 kΩ |
Even slightly touching the sensor may change the resistance value. Be sure to hold the connector of the sensor.
When measuring, the sensor temperature must be the same as the ambient temperature.
As the temperature increases, the resistance decreases (see the graph).
If the result is not as specified, replace the cooler thermistor.