HEATING / AIR CONDITIONING  AIR CONDITIONING SYSTEM(for Automatic Air Conditioning System)  CHECK MODE PROCEDURE  


REFRIGERANT SHORTAGE CHECK IN NORMAL OPERATION (CHECK A/C SWITCH INDICATOR AND DTC)


E226013

a.

Turn the ignition switch to ON.


b.

Check that A/C switch indicator is turned on when the following conditions are met.

Measurement Condition
Item Condition
A/C Switch ON
A/C driving time 15 minutes or more
Ambient temperature* 0 to 49°C (32 to 120°F)
Engine coolant temperature 45°C (113°F) or more

*: If the ambient temperature does not meet condition, do not perform this check.

HINT:

If the amount of refrigerant in the system is insufficient, air conditioning system operation stops after 11 minutes in order to prevent compressor burnout, and the A/C switch indicator light turns off.



c.

Connect the intelligent tester to the DLC3.


d.

Check for DTC B14B8.

Result
Result Amount of Refrigerant Corrective Action
DTC B14B8 is output Empty or nearly empty Check for gas leakage using halogen leak detector, and repair if necessary (See page (Click here))
DTC B14B8 is not output Correct or insufficient Perform the refrigerant shortage check using the intelligent tester



REFRIGERANT SHORTAGE CHECK USING THE INTELLIGENT TESTER


a.

Connect the intelligent tester to the DLC3.


b.

Turn the ignition switch to ON.


c.

Turn the intelligent tester on.


d.

Enter the following menus: Body / Air Conditioner / Utility / Refrigerant Gas Volume Check.


e.

According to the display on the intelligent tester, perform the refrigerant shortage check when the following conditions are met.

Measurement Condition
Item Condition
A/C Switch ON
Ambient temperature* 0 to 49°C (32 to 120°F)
R/F Switch Recirculation (Ambient temperature is 30°C (86°F) or less)
Fresh (Ambient temperature is 31°C (87°F) or more)
Blower Speed HI
Temperature Setting MAX HOT

*: If the ambient temperature does not meet condition, do not perform this check.

HINT:
·

Refer to the intelligent tester operator's manual for further details.

·

The message "The gas volume is insufficient" is shown on the intelligent tester screen and air conditioning system is stopped if the amount of refrigerant is insufficient in the cycle.

·

The refrigerant shortage check using the intelligent tester does not output a DTC.



Result
Result Amount of Refrigerant Corrective Action
The gas volume is insufficient Insufficient or leakage
1.

Check for gas leakage using halogen leak detector, and repair if necessary

2.

Evacuate air and then charge appropriate volume of new refrigerant


The gas volume is normal Correct -