HEATING / AIR CONDITIONING  AIR CONDITIONING SYSTEM(for Automatic Air Conditioning System)  DATA LIST / ACTIVE TEST  


DATA LIST


HINT:

Using the GTS to read the Data List allows the values or states of switches, sensors, actuators and other items to be read without removing any parts. This non-intrusive inspection can be very useful because intermittent conditions or signals may be discovered before parts or wiring is disturbed. Reading the Data List information early in troubleshooting is one way to save diagnostic time.


NOTICE:

In the table below, the values listed under "Normal Condition" are reference values. Do not depend solely on these reference values when deciding whether a part is faulty or not.


a.

Connect the GTS to the DLC3.


b.

Turn the ignition switch to ON.


c.

Turn the GTS on.


d.

Enter the following menus: Body Electrical / Air Conditioner / Data List.


e.

According to the display on the GTS, read the Data List.

Air Conditioner
Tester Display Measurement Item/Range Normal Condition Diagnostic Note
Room Temperature Sensor Room temperature sensor /
Min.: -6.5°C (20.3°F)
Max.: 57.25°C (135.1°F)
Actual room temperature is displayed -
Ambient Temp Sensor Ambient temperature sensor /
Min.: -23.3°C (-9.94°F)
Max.: 65.95°C (150.71°F)
Actual ambient temperature is displayed -
Adjusted Ambient Temp Adjusted ambient temperature /
Min.: -30.8°C (-23.44°F)
Max.: 50.8°C (123.44°F)
- -
Evaporator Fin Thermistor Evaporator temperature sensor /
Min.: -29.7°C (-21.46°F)
Max.: 59.55°C (139.19°F)
Actual evaporator temperature displayed Open in the circuit: -29.7°C (-21.46°F).
Short in the circuit: 59.55°C (139.19°F).
Evaporator Target Temp Target evaporator temperature /
Min.: -327.68°C (-557.82°F)
Max.: 327.67°C (621.81°F)
Target evaporator temperature displayed -
Solar Sensor (D side) Driver side solar sensor /
Min.: 0
Max.: 255
Driver side solar sensor value increases as brightness increases -
Engine Coolant Temp Engine coolant temperature /
Min.: 1.3°C (34.34°F)
Max.: 90.55°C (194.99°F)
Actual engine coolant temperature is displayed after engine warmed up -
Set Temperature (D side) Driver side set temperature /
Min.: MAX COLD
Max.: MAX HOT
Driver side actual set temperature is displayed -
Blower Motor Speed Level Blower motor speed level /
Min.: 0
Max.: 31
Increases from 0 to 31 as blower motor speed increases -
Regulator Pressure Sensor Regulator pressure sensor /
Min.: -0.4566 MPaG
Max.: 3.2943 MPaG
Actual regulator pressure is displayed -
Regulator Control Current Regulator control current /
Min.: 0 A
Max.: 0.997 A
Value changes between 0.12 A and 0.997 A in accordance with compressor operation -
Air Mix Servo Targ Pulse (D) Air mix servo motor target pulse /
Min.: 0
Max.: 255
·

MAX COOL: 4 (pulse)

·

MAX HOT: 93 (pulse)


-
Air Mix Servo Actual Pulse (D) Air mix servo motor actual pulse /
Min.: 0
Max.: 255
Follows the target pulse -
Air Outlet Servo Pulse (D) Air outlet servo motor target pulse /
Min.: 0
Max.: 255
·

FACE: 101 (pulse)

·

B/L: 74 (pulse)

·

FOOT: 53 or 62 (pulse)

·

FOOT / DEF: 35 (pulse)

·

DEF: 9 (pulse)


-
Air Outlet Servo Actu Pulse (D) Air outlet servo motor actual pulse /
Min.: 0
Max.: 255
Follows the target pulse -
Air Inlet Damper Targ Pulse Air inlet servo motor target pulse /
Min.: 0
Max.: 255
·

Recirculation: 6 (pulse)

·

Fresh: 22 (pulse)


-
Air Inlet Damper Actual Pulse Air inlet servo motor actual pulse /
Min.: 0
Max.: 255
Follows the target pulse -
Shift Set Temperature Set temperature shift /
2C decr, 1C decr, Normal, 1C incr or 2C incr
Customized value displayed -
Air Inlet Mode Air inlet mode /
Auto or Manual
Customized value displayed -
Evaporator Control Evaporator Control /
Auto or Manual
Customized value displayed -
Refrigerant Shortage Check Refrigerant shortage check function /
ON or OFF
Customized value displayed -
Fan Speed Increment Control Not available /
Fast, Normal or Slow
- -
Foot/DEF Auto Mode Foot / DEF auto mode /
ON or OFF
Customized value displayed -
Foot/DEF Auto Blow Up Foot / DEF automatic blow up function /
ON or OFF
Customized value displayed -
A/C Cutoff Signal A/C control cutoff signal /
ON or OFF
- -
Refrigerant Gas Type Refrigerant gas type /
R134a or 1234yf
Refrigerant gas type displayed -
Number of Trouble Codes Number of trouble codes /
Min.: 0
Max.: 255
Number of DTCs displayed -



ACTIVE TEST


HINT:

Using the GTS to perform Active Tests allows relays, VSVs, actuators and other items to be operated without removing any parts. This non-intrusive functional inspection can be very useful because intermittent operation may be discovered before parts or wiring is disturbed. Performing Active Tests early in troubleshooting is one way to save diagnostic time. Data List information can be displayed while performing Active Tests.


a.

Connect the GTS to the DLC3.


b.

Turn the ignition switch to ON.


c.

Turn the GTS on.


d.

Enter the following menus: Body Electrical / Air Conditioner / Active Test.


e.

According to the display on the GTS, perform the Active Test.

Air Conditioner
Tester Display Test Part Control Range Diagnostic Note
Blower Motor Blower motor Min.: 0, Max.: 31 -
Magnetic Clutch Relay A/C Compressor OFF or ON -
Defogger Relay (Rear) Defogger relay (Rear) OFF or ON -
Air Mix Servo Targ Pulse (D) Air mix servo motor pulse Min.: 0, Max.: 255 Perform Active Test when value between 4 and 93 displayed
Air Outlet Servo Pulse (D) Air outlet servo motor pulse Min.: 0, Max.: 255 Perform Active Test when value between 9 and 101 displayed
Air Inlet Damper Targ Pulse Air inlet damper target pulse Min.: 0, Max.: 255 Perform Active Test when value between 6 and 22 displayed