INSTALLATION
Removal / installation · Vehicles built from Aug 2005
| 1. ADJUST COMPRESSOR OIL |
![]() ![]() |
When replacing the compressor with a new one, gradually discharge the refrigerant gas from the service valve. Then drain the following amount of oil from the new compressor before installation, so that the amount of oil contained in it is the same as that in the compressor to be replaced.
- HINT:
- New compressors are filled with sufficient oil for the whole cycle. Therefore, it is necessary to drain residual oil from the condenser and cooling unit.
- Standard:
- (The amount of oil inside a new compressor: 60 (+15) cc (2.0 (+0.51) fl.oz.)) - (The amount of oil remaining in the removed compressor) = The amount of oil to be removed when replacing the compressor
- NOTICE:
- When checking the compressor oil level, observe the precautions for cooler removal/installation.
- If a new compressor is installed without removing the amount of oil remaining in the pipes of the vehicle, the amount of oil becomes too large. This prevents heat exchange in the refrigerant cycle and causes refrigeration failure.
- If the amount of oil remaining in the removed compressor is too small, check for oil leakage.
- Use ND-OIL8 compressor oil.
- When checking the compressor oil level, observe the precautions for cooler removal/installation.
| 2. INSTALL COMPRESSOR AND PULLEY |
![]() ![]() |
Provisionally tighten the compressor with the bolt.
Tighten the compressor with the 4 bolts.

- Torque:
- 25 N*m{ 255 kgf*cm , 18 ft.*lbf }
- NOTICE:
- Tighten the bolts in the sequence order shown in the illustration to install the compressor.
Connect the connector and clamp.
| 3. INSTALL NO. 1 COOLER REFRIGERANT DISCHARGE HOSE |
![]() ![]() |
Remove the attached vinyl tape from the hose.
Apply sufficient compressor oil (ND-OIL8) to a new O-ring and the fitting surface of the compressor.
- Compressor oil:
- ND-OIL8 or the equivalent
Install the O-ring onto the discharge hose.
Install the discharge hose onto the compressor with the bolt.
- Torque:
- 9.8 N*m{ 100 kgf*cm , 87 in.*lbf }
| 4. INSTALL NO. 1 COOLER REFRIGERANT SUCTION HOSE |
![]() ![]() |
Remove the attached vinyl tape from the hose.
Apply sufficient compressor oil (ND-OIL8) to a new O-ring and the fitting surface of the compressor.
- Compressor oil:
- ND-OIL8 or the equivalent
Install the O-ring onto the suction hose.
Install the suction hose onto the compressor with the bolt.
- Torque:
- 9.8 N*m{ 100 kgf*cm , 87 in.*lbf }
| 5. INSTALL FAN AND GENERATOR V BELT |
![]() ![]() |
Install the fan and generator V belt.
Gently tighten bolt B until there is no measurable clearance.
Turn bolt C to adjust the tension of the fan and generator V belt.
Inspect the fan and generator V belt.
Tighten bolt B.
- Torque:
- 34 N*m{ 347 kgf*cm , 25 ft.*lbf }
Tighten bolt A.
- Torque:
- 54 N*m{ 551 kgf*cm , 40 ft.*lbf }
Visually check the generator wiring and listen for abnormal noise.
Check that the wiring is in good condition.
Check that there is no abnormal noise from the generator while the engine is running.
Inspect the discharge warning light circuit.

Turn the ignition switch to the ON position. Check that the discharge warning light illuminates.
Start the engine. Check that the light goes off.
| 6. INSPECT DRIVE BELT DEFLECTION AND TENSION |
![]() ![]() |
Check the belt deflection by pressing on the belt at the points indicated by the arrow marks in the illustration.
- Deflection:
Item
Specified Condition
New belt
7 to 8 mm (0.28 to 0.31 in.)
Used belt
9 to 11 mm (0.35 to 0.43 in.)
- HINT:
- The most appropriate force for the adjustment above is 98 N (10 kgf, 22 lbf).
- New belt refers to a belt which has been used on a running engine for less than 5 minutes.
- Used belt refers to a belt which has been used on a running engine for 5 minutes or more.
- After installing a belt, check that it fits properly in the ribbed grooves.
- Check with your hand to confirm that the belt has not slipped out of the groove on the bottom of the pulley.
- After installing a new belt, run the engine for about 5 minutes and recheck the belt tension.
- The most appropriate force for the adjustment above is 98 N (10 kgf, 22 lbf).
Adjust fan and generator V belt tension.

Loosen bolt A.
Loosen bolt B.
Gently tighten bolt B until there is no measurable clearance.
Turn bolt C to adjust the tension of the fan and generator V belt.
Tighten bolt B.
- Torque:
- 34 N*m{ 347 kgf*cm , 25 ft.*lbf }
Tighten bolt A.
- Torque:
- 54 N*m{ 551 kgf*cm , 40 ft.*lbf }
Visually check the generator wiring and listen for abnormal noises.
Check that the wiring is in good condition.
Check that there is no abnormal noise from the generator while the engine is running.
Inspect the discharge warning light circuit.

Turn the ignition switch to the ON position. Check that the discharge warning light illuminates.
Start the engine. Check that the light goes off.
| 7. INSTALL ENGINE UNDER COVER RH |
| 8. CONNECT CABLE TO NEGATIVE BATTERY TERMINAL |
- Torque:
- 5.4 N*m{ 55 kgf*cm , 48 in.*lbf }
| 9. CHARGE REFRIGERANT |
- SST
- 07110-58060
(07117-58060, 07117-58070, 07117-58080, 07117-58090, 09985-02100, 09985-02120, 07117-78050, 07117-88060, 07117-88070, 07117-88080)


- NOTICE:
- Charge refrigerant in accordance with the equipment manual.
Perform vacuum purging using a vacuum pump.
Charge refrigerant HFC-134a (R134a).
- Standard:
- 330 to 390 g (11.64 to 13.76 oz.) w/o Fan Shroud Ventilation Duct
- 350 to 410 g (12.35 to 14.46 oz.) w/ Fan Shroud Ventilation Duct
- NOTICE:
- Do not start the engine before charging it with refrigerant as the cooler compressor doesn't work properly without sufficient refrigerant. This could cause the compressor to overheat.
- HINT:
- The relationship between the refrigerant charge amount and the pressure is as follows.


- High Charge Range:
If the refrigerant is overcharged, the pressure rises on the high-pressure side. High-pressure cut off frequently occurs. This causes insufficient cooling performance and also insufficient compressor lubrication.
- Low Charge Range:
Shortage of refrigerant causes insufficient cooling performance and low circulation of refrigerant oil, which shortens the compressor life. Operation with insufficient coolant raises the refrigerant temperature and causes heat deterioration of the rubber seals and hoses. Cracking and thus refrigerant leakage may occur.
- The relationship between the refrigerant charge amount and the pressure is as follows.
Install the caps onto the service valves on the refrigerant line.
| 10. WARM UP ENGINE |
- NOTICE:
- Warm up the engine at less than 2000 rpm for 1 minute or more after charging it with refrigerant.
| 11. CHECK FOR REFRIGERANT LEAK |
After recharging the refrigerant gas, check for refrigerant gas leakage using a halogen leak detector.
Perform the operation as follows:
- Stop the engine.
- Secure good ventilation (the halogen leak detector may react to volatile gases other than refrigerant, such as evaporated gasoline or exhaust gas).
- Repeat the test 2 or 3 times.
- Make sure that some refrigerant remains in the refrigeration system.
When the compressor is off: approximately 392 to 588 kPa (4 to 6 kgf*cm2, 57 to 85 psi)
- HINT:
- It is impossible for the above pressure to be maintained if there is leakage.
- Stop the engine.
Using the halogen leak detector, check the refrigerant line, especially at the connection points, for leakage.

Bring the halogen leak detector close to the drain hose before performing the test.

- HINT:
- After the blower motor has stopped, leave the cooling unit for at least 15 minutes.
- Place the halogen leak detector sensor under the drain hose.
- When bringing the halogen leak detector close to the drain hose, make sure that the halogen leak detector does not react to the volatile gases.
- After the blower motor has stopped, leave the cooling unit for at least 15 minutes.
If no gas leakage is detected from the drain hose, remove the blower motor from the cooling unit. Insert the halogen leak detector sensor into the unit and perform the test.
Disconnect the pressure switch connector and leave it for approximately 20 minutes. Bring the halogen leak detector close to the pressure switch and perform the test.