Home › HEATER & AIR CONDITIONING SYSTEM › AIR CONDITIONING › AIR CONDITIONING SYSTEM

AIR CONDITIONING SYSTEM > Warm Air does not Flow Immediately after Engine Start with Temperature Control Dial at Max. Hot

for Preparation Click here

HINT:
This trouble shooting flowchart is used only for 2KD-FTV engine models.


INSPECTION PROCEDURE

1.INSPECT FUSE (PTC1, PTC2)


NG
REPLACE FUSE
OK


2.INSPECT RELAY
(Click here)


NG
REPLACE RELAY
OK


3.INSPECT AIR MIX DAMPER CONTROL SWITCH
(Click here)


NG
REPLACE AIR MIX DAMPER CONTROL SWITCH
OK


4.INSPECT AMBIENT TEMPERATURE SENSOR
(Click here)


NG
REPAIR OR REPLACE AMBIENT TEMPERATURE SENSOR
OK


5.INSPECT HEATER RADIATOR ASSEMBLY
(Click here)


NG
REPLACE HEATER RADIATOR ASSEMBLY
OK


6.CHECK HARNESS OR CONNECTOR
  1. Disconnect the connector from A/C amplifier.



    E113139E01
  1. Measure the resistance according to the value(s) in the table below.

    Standard Resistance:
    Tester Connection
    Condition
    Specified Conditioin
    PTC (H18-2) - Body ground
    Always
    Below 1 Ω
    PTCL (H18-3) - Body ground
    Always
    Below 1 Ω



NG
REPAIR OR REPLACE HARNESS OR CONNECTOR
OK

REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY