This DTC is stored if refrigerant pressure on the high pressure side is extremely low (176 kPa (1.8 kgf/cm2, 26 psi) or less) or extremely high (3025 kPa (30.8 kgf/cm2, 439 psi) or more). The air conditioner pressure sensor, which is installed on the pipe on the high pressure side to detect refrigerant pressure, sends a refrigerant pressure signal to the air conditioning amplifier assembly. The air conditioning amplifier assembly converts this signal to a pressure value according to the sensor characteristics and uses it to control the compressor.
| DTC No. | Detection Item | DTC Detection Condition | Trouble Area | Memory | Note |
|---|---|---|---|---|---|
| B1423/23 | Pressure Sensor Circuit | ·
Open or short in air conditioner pressure sensor circuit ·
Refrigerant pressure on high pressure side is extremely low (176 kPa (1.8 kgf/cm2, 26 psi) or less) or extremely high (3025 kPa (30.8 kgf/cm2, 439 psi) or more) |
·
Air conditioner pressure sensor ·
Harness or connector ·
Air conditioning amplifier assembly ·
Cooler expansion valve (blocked, stuck) ·
Condenser assembly (blocked, deterioration of cooling capacity due to dirt) ·
Cooler dryer (moisture in the refrigerant cycle cannot be absorbed) ·
Cooling fan system (condenser assembly cannot be cooled down) ·
Air conditioning system (leaks, blocked) |
- | - |
The air conditioning amplifier assembly stores the DTC of the respective malfunction if it has occurred for the period of time indicated in the brackets.
When the battery is disconnected or the air conditioning amplifier assembly is replaced, be sure to perform servo motor initialization.
If DTC B1423 and B14B8 are output at the same time, troubleshoot for DTC B1423 first.
| *a | Front view of wire harness connector
(to Air Conditioner Pressure Sensor) |
Disconnect the air conditioner pressure sensor connector.
Measure the voltage according to the value(s) in the table below.
| Tester Connection | Switch Condition | Specified Condition |
|---|---|---|
| A34-3 (+) - Body ground | Ignition switch ON | 4.75 to 5.25 V |
| Proceed to |
|---|
| OK |
| NG |
OK
NG
| *a | Front view of wire harness connector
(to Air Conditioner Pressure Sensor) |
Disconnect the A34 air conditioner pressure sensor connector.
Measure the resistance according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| A34-1 (-) - Body ground | Always | Below 1 Ω |
| Proceed to |
|---|
| OK |
| NG |
OK
NG
| *a | Component with harness connected
(Air Conditioning Amplifier Assembly) |
Remove the air conditioning amplifier assembly with the connectors still connected.
Click hereVehicle Interior>HEATING / AIR CONDITIONING>AIR CONDITIONING AMPLIFIER>REMOVAL
Measure the voltage according to the value(s) in the table below.
| Tester Connection | Switch Condition | Specified Condition |
|---|---|---|
| G81-9 (PRE) - Body ground | Ignition switch ON
A/C switch off |
0.62 to 4.73 V |
If the measured voltage is not within the normal range, there may be a malfunction in the air conditioning amplifier assembly, air conditioner pressure sensor, or wire harness. It is also possible that the amount of refrigerant may not be appropriate.
| Proceed to |
|---|
| OK |
| NG |
OK
NG
Measure the voltage when the following conditions are satisfied.
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Temperature Setting | MAX COLD |
| Blower Speed | Hi |
| A/C Switch | On |
| R/F Switch | Recirculation |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
| Engine Speed | 2000 rpm |
If refrigerant pressure on the high pressure side becomes extremely high during the inspection (if the voltage exceeds 4.8 V), the fail-safe function stops compressor operation. Therefore, measure the voltage before the fail-safe operation.
It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the problem symptom may recur after a while.
When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
| *a | Component with harness connected
(Air Conditioning Amplifier Assembly) |
Measure the voltage according to the value(s) in the table below.
| Tester Connection | Switch Condition | Specified Condition |
|---|---|---|
| G81-9 (PRE) - Body ground | Ignition switch ON
A/C switch on |
0.62 to 4.73 V |
| Result | Proceed to |
|---|---|
| OK (When troubleshooting according to the DTC) | A |
| OK (When troubleshooting according to Problem Symptoms Table) | B |
| NG | C |
A
B
C
Disconnect the G81 air conditioning amplifier assembly connector.
Disconnect the A34 air conditioner pressure sensor connector.
Measure the resistance according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| A34-3 (+) - G81-10 (S5-3) | Always | Below 1 Ω |
| G81-10 (S5-3) - Body ground | Always | 10 kΩ or higher |
| Proceed to |
|---|
| OK |
| NG |
OK
NG
Disconnect the G81 air conditioning amplifier assembly connector.
Disconnect the A34 air conditioner pressure sensor connector.
Measure the resistance according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| A34-1 (-) - G81-13 (SG-2) | Always | Below 1 Ω |
| G81-13 (SG-2) - Body ground | Always | 10 kΩ or higher |
| Proceed to |
|---|
| OK |
| NG |
OK
NG
Disconnect the G81 air conditioning amplifier assembly connector.
Disconnect the A34 air conditioner pressure sensor connector.
Measure the resistance according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| A34-2 (PR) - G81-9 (PRE) | Always | Below 1 Ω |
| G81-9 (PRE) - Body ground | Always | 10 kΩ or higher |
| Proceed to |
|---|
| OK |
| NG |
OK
NG
Install a manifold gauge set.
Recover the refrigerant from the air conditioning system using a refrigerant recovery unit.
Evacuate the air conditioning system and check that vacuum can be maintained in it.
If vacuum cannot be maintained in the air conditioning system, refrigerant may be leaking from it. In this case, it is necessary to repair or replace the leaking part of the air conditioning system.
Vacuum can be maintained in the air conditioning system.
| Proceed to |
|---|
| OK |
| NG |
OK
NG
Use a refrigerant recovery unit to recover refrigerant.
Evacuate the air conditioning system.
Add an appropriate amount of refrigerant.
Click hereVehicle Interior>HEATING / AIR CONDITIONING>REFRIGERANT>REPLACEMENT
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTC.
| Proceed to |
|---|
| NEXT |
NEXT
Check for DTCs when the following conditions are satisfied.
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Temperature Setting | MAX COLD |
| Blower Speed | Hi |
| A/C Switch | On |
| R/F Switch | Recirculation |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
| Engine Speed | 2000 rpm |
If refrigerant pressure on the high pressure side becomes high, the DTC will be set. It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the DTC may be set after the air conditioning operates for a while.
If the DTC was stored due to an insufficient or excessive amount of refrigerant, the problem may have been solved after performing the previous step. However, the root cause of insufficient refrigerant may be refrigerant leaks. The root cause of excessive refrigerant may be adding refrigerant when the level was insufficient. Therefore, identify and repair the area where refrigerant leaks from as necessary.
When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
DTC B1423/23 is not output.
| Proceed to |
|---|
| OK |
| NG |
OK
NG
Identify the area where refrigerant leaks from.
Click hereVehicle Interior>HEATING / AIR CONDITIONING>REFRIGERANT>REPLACEMENT
Repair the identified area of the air conditioning system.
Evacuate the air conditioning system.
| Proceed to |
|---|
| NEXT |
NEXT
Install a manifold gauge set.
Turn the ignition switch to ON.
| *a | Component with harness connected
(Air Conditioning Amplifier Assembly) |
Measure the voltage according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| G81-9 (PRE) - G81-13 (SG-2) | Engine running
Air conditioning system operating Refrigerant pressure:(below 3025 kPa [30.8 kgf/cm2, 439 psi] and higher than 176 kPa [1.8 kgf/cm2, 26 psi]) |
0.62 to 4.73 V |
| Proceed to |
|---|
| OK |
| NG |
OK
NG
Check that the cooling fan(s) operates normally.
for 2AD-FHV (w/ Towing Package):Engine / Hybrid System>2AD-FHV COOLING>COOLING FAN SYSTEM(w/ Towing Package)>ON-VEHICLE INSPECTION
for 2AD-FHV (w/o Towing Package):Engine / Hybrid System>2AD-FHV COOLING>COOLING FAN SYSTEM(w/o Towing Package)>ON-VEHICLE INSPECTION
for 2AD-FTV (w/ Towing Package):Engine / Hybrid System>2AD-FTV COOLING>COOLING FAN SYSTEM(w/ Towing Package)>ON-VEHICLE INSPECTION
for 2AD-FTV (w/o Towing Package):Engine / Hybrid System>2AD-FTV COOLING>COOLING FAN SYSTEM(w/o Towing Package)>ON-VEHICLE INSPECTION
| Proceed to |
|---|
| OK |
| NG |
OK
NG
for 2AD-FHV (w/ Towing Package):Engine / Hybrid System>2AD-FHV COOLING>COOLING FAN SYSTEM(w/ Towing Package)>PROBLEM SYMPTOMS TABLE
for 2AD-FHV (w/o Towing Package):Engine / Hybrid System>2AD-FHV COOLING>COOLING FAN SYSTEM(w/o Towing Package)>PROBLEM SYMPTOMS TABLE
for 2AD-FTV (w/ Towing Package):Engine / Hybrid System>2AD-FTV COOLING>COOLING FAN SYSTEM(w/ Towing Package)>PROBLEM SYMPTOMS TABLE
for 2AD-FTV (w/o Towing Package):Engine / Hybrid System>2AD-FTV COOLING>COOLING FAN SYSTEM(w/o Towing Package)>PROBLEM SYMPTOMS TABLE
Use a refrigerant recovery unit to recover refrigerant.
Evacuate the air conditioning system.
Add an appropriate amount of refrigerant.
Click hereVehicle Interior>HEATING / AIR CONDITIONING>REFRIGERANT>REPLACEMENT
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTC.
| Proceed to |
|---|
| NEXT |
NEXT
Check for DTCs when the following conditions are satisfied.
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Temperature Setting | MAX COLD |
| Blower Speed | Hi |
| A/C Switch | On |
| R/F Switch | Recirculation |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
| Engine Speed | 2000 rpm |
If refrigerant pressure on the high pressure side becomes high, the DTC will be set. It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the DTC may be set after the air conditioning operates for a while.
When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTC. If the DTC is not output after this work, it indicates that the cooler dryer in the condenser is not able to absorb moisture in the refrigerant cycle. It is necessary to replace the cooler dryer in order to complete the repair.
DTC B1423/23 is not output.
| Proceed to |
|---|
| OK |
| NG |
OK
for 3ZR-FE, 3ZR-FAE, 2AR-FE:Vehicle Interior>HEATING / AIR CONDITIONING>CONDENSER(for 3ZR-FE, 3ZR-FAE, 2AR-FE)>REMOVAL
NG
Replace the cooler expansion valve with a new one.
Click hereVehicle Interior>HEATING / AIR CONDITIONING>COOLER EXPANSION VALVE>REMOVAL
Replace the cooler expansion valve with a new one because the expansion valve is either stuck or clogged.
| Proceed to |
|---|
| NEXT |
NEXT
Use a refrigerant recovery unit to recover refrigerant.
Evacuate the air conditioning system.
Add an appropriate amount of refrigerant.
Click hereVehicle Interior>HEATING / AIR CONDITIONING>REFRIGERANT>REPLACEMENT
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTC.
| Proceed to |
|---|
| NEXT |
NEXT
Check for DTCs when the following conditions are satisfied.
| Item | Condition |
|---|---|
| Vehicle Doors | Fully open |
| Temperature Setting | MAX COLD |
| Blower Speed | Hi |
| A/C Switch | On |
| R/F Switch | Recirculation |
| Interior Temperature | 25 to 35°C (77 to 95°F) |
| Engine Speed | 2000 rpm |
If refrigerant pressure on the high pressure side becomes high, the DTC will be set. It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the DTC may be set after the air conditioning operates for a while.
When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
If refrigerant pressure is not normal after replacing the expansion valve with a normal one, the condenser or pipes may be clogged due to dirt, dust or other foreign matter. In this case, clean or replace the condenser or pipes.
DTC B1423/23 is not output.
| Proceed to |
|---|
| OK |
| NG |
OK
NG