The blower with fan motor sub-assembly operates according to signals from the air conditioning amplifier assembly. The blower with fan motor sub-assembly speed signals are transmitted by changes in the duty ratio. Duty Ratio: The duty ratio is the ratio of the blower with fan motor sub-assembly on time (T1) to the total of the blower with fan motor sub-assembly on and off time (T2). The air conditioning amplifier assembly controls the blower with fan motor sub-assembly speed.
WIRING DIAGRAM
INSPECTION PROCEDURE
NOTICE:
Inspect the fuses for circuits related to this system before performing the following inspection procedure.
1. PERFORM ACTIVE TEST USING INTELLIGENT TESTER (BLOWER WITH FAN MOTOR)
Select the Active Test, use the intelligent tester to generate a control command, and then check that the blower with fan motor sub-assembly operates (Click here).
Air Conditioner
Tester Display
Test Part
Control Range
Diagnostic Note
Blower Motor
Blower with fan motor sub-assembly
Min.: 0, Max.: 31
-
OK:
Blower with fan motor sub-assembly operates and blower motor speed changes.