If the windshield frequently fogs up even though the air conditioning system is operating, the following factors may be the cause.
| Symptom | Factor |
|---|---|
| Windshield frequently fogs up | ·
Compressor with pulley assembly malfunction ·
Refrigerant volume (low) ·
Cooler expansion valve (opened excessively) ·
No. 1 heater control sub-assembly malfunction ·
Defroster damper control cable sub-assembly malfunction ·
Air conditioning radiator assembly malfunction |
Check that the following conditions are met and perform the refrigerant shortage check according to the display on the GTS.
| Item | Condition |
|---|---|
| A/C switch | On |
| Ambient temperature*1 | 0 to 49°C (32 to 120°F) |
| Blower speed | HI |
*1: If the ambient temperature is not within the range shown, do not perform this check.
| Tester Display |
|---|
| Refrigerant Gas Volume Check |
| Result | Amount of Refrigerant |
|---|---|
| Refrigerant correct | Correct |
| Refrigerant shortage | Insufficient |
"Refrigerant correct" is displayed on the GTS.
| Result | Proceed to |
|---|---|
| OK | A |
| NG (for HFC-134a(R134a)) | B |
| NG (for HFO-1234yf(R1234yf)) | C |
A
B
C
Click hereVehicle Interior>HEATING / AIR CONDITIONING>REFRIGERANT (for HFO-1234yf(R1234yf))>REPLACEMENT
Set the airflow mode control switch to defrost and check that the air outlet mode changes to DEF mode.
The air outlet mode changes to DEF mode.
| Result | Proceed to |
|---|---|
| OK (for HFC-134a(R134a)) | A |
| OK (for HFO-1234yf(R1234yf)) | B |
| NG | C |
A
Click hereVehicle Interior>HEATING / AIR CONDITIONING>REFRIGERANT (for HFC-134a(R134a))>ON-VEHICLE INSPECTION
B
C
Remove the No. 1 heater control sub-assembly.
Inspect the No. 1 heater control sub-assembly.
| Proceed to |
|---|
| OK |
| NG |
OK
NG
Replace the defroster damper control cable sub-assembly with a new or known good one.
Check if the same malfunction recurs.
Malfunction does not reoccur (returns to normal).
| Result | Proceed to |
|---|---|
| OK | A |
| NG (for LHD) | B |
| NG (for RHD) | C |
A
B
C